| 2 | Providing annual maintenance services for LT Control Panels and Starters at Shahad Water Works item no.01 Maintenance of 15HP/25HP/60HP/75HP/200HP FCMA Soft Starter/Star Delta starter for each pump set with test and trial labour charges at Phase-I & Phase-II UDDS Dombiali, Raw Water Works and Pure Water Works, Shahad. |
| 3 | item no.02 Labour rate for monthly maintenance contract including inspection, checking & servicing of LT motor control panels with MCCB, power contactor for each pump set with appropriate settings / testing of relay timer/contacts, cleaning of all spares/equipments with cleaning spray, etc. complete and giving testing and trials for period of one years. |
| 4 | item no.03 Providing Power Contactor 3 pole 400A MNX type AC3 Duty 240 V coil AC, 2 NO + 2 NC. |
| 5 | item no.04 Providing Power Contactor 3 pole 300A MNX type AC3 Duty 240 V coil AC, 2 NO + 2 NC. |
| 6 | item no.05 Providing Power Contactor 3 pole 250A MNX type AC3 Duty 240 V coil AC, 2 NO + 2 NC. |
| 7 | item no.06 Providing Power Contactor 3 pole 140A MNX type AC3 Duty 240 V coil AC, 2 NO + 2 NC. |
| 8 | item no.07 Providing Power Contactor 3 pole 70A MNX type AC3 Duty 240 V coil AC, 2 NO + 2 NC. |
| 9 | item no.08 Providing Auxilary MXO-Contactor 22E Duty 240V coil AC 2 NO + 2 NC |
| 10 | item no.09 Providing Motor Protection relay MPR D2, Range:2-5.5A, 230V AC, CTR-400/5A, Setting-3.12A. |
| 11 | item no.10 Providing overload relay for motor starter Range6-10 Sec, Relay Range 20-33A. |
| 12 | item no.11 Providing MN12 (CT operated) Thermal overload relay, Relay Range: 180 – 300A. |
| 13 | item no.12 Providing Electronic timer ST 100, on Relay, Range 0.3 Sec-30 min, 240V AC/DC, Selected Range- 3 Min, Setting-30 sec. |
| 14 | item no.13 Providing Current Sensor (S2CTS 1/5) (up to 3.00 H.P.) (5 Amp.) |
| 15 | item no.14 Providing Add on Block D range contactor Rating 45A-80A, TA1-DN-22 2N0 + 2 NC 240 V Coil AC |
| 16 | item no.15 Providing Push Button Illuminated Actuator, Flush (with BA9S Filament Bulb 130V) 220V AC with series resistor. |
| 17 | item no.16 CSupplying, erecting, testing & commissioning LT current transformer with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates. |
| 18 | item no.17 FCMA ELTEC SOFT STARTER Model SS1-150-OE-L1 50KW/ 200 HP / SS -415- 187KW/ 250HP (similar to existing design). |
| 19 | item no.18 Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW-MCCB |
| 20 | item no.19 Providing & erecting 3 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB |
| 21 | item no.20 Providing & erecting 3 Pole MCCB, 415V, 160A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no lineload bias in provided enclosure/panel as per specification no. SW-MCCB |
| 22 | item no. 21 Supplying, erecting & marking TP MCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 23 | itme no.22 Supplying, erecting & marking SP MCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 24 | item no.23 Supplying and erecting panel mounting type digital voltmeter having three and half digit LED display, calibrated for 0 to 750V AC suitable to operate on 500V having accuracy class of 0.5, AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer. |
| 25 | item no.24 Supplying and erecting static energy meter with 240V 50 Hz. AC supply 10 to 60 A, accuracy class 1.0 with backlit LCD display, (measuring and display kWh, kVAh, V,I,PF, frequency, kW, kVA, six months history of energy & MD in kW & kVA) with transparent hinge type box complete erected on polished teak wood board duly wired with required size of weatherproof PVC wires duly tested by electric supply company. |
| 26 | item no. 25 Supplying and erecting panel mounting type digital ammeter having three and half digit LED display, external CT operated, calibrated for suitable to operate on 500V, 0 to 1000A having accuracy class of 0.5, AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer. |
| 27 | item no.26 Providing 315A TPN Switch Fuse Unit (CSSDF315B3N) |
| 28 | item no.27 Providing 160A TPN Switch Fuse Unit (CSSDF160B3N) |
| 29 | item no.28 Providing 125 A TPN Switch Fuse Unit (CSSDF125B3N) |
| 30 | item no.29 Providing 100A TPN Switch Fuse Unit (CSSDF100B3N) |
| 31 | item no.30 Providing 63 A TPN Switch Fuse Unit (CSSDF63B3N) |
| 32 | item no.31 Providing 32 A TPN Switch Fuse Unit (CSSDF32B3N) |
| 33 | item no.32 Providing HRC Fuse Link (DIN Type) 200 A (CSDFL1) |
| 34 | item no.33 Providing HRC Fuse Link (DIN Type) 200 A (CSDFL1) |
| 35 | item no.34 Providing HRC Fuse Link (DIN Type) 100 A (CSDFL00) |
| 36 | item no. 35 Providing HRC Fuse Link (DIN Type) 32 to 63 A(CDFL00 & CSDFL00) |
| 37 | item no. 36 Supplying & erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250V on provided box / panel with necessary material, wiring & connections etc. |
| 38 | item no.37 Supplying and erecting selector switch suitable for voltmeter/ammeter for 3 phase AC supply 500V, 50Hz, on provided box/panel and duly connecting with necessary PVC wire leads and lugs. |
| 39 | sub estimate: Providing annual maintenance for LT control panels and starters at UDDS Dombivali.item no.01 Providing & erecting 4 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB (Note:- 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 40 | item no.02 Providing & erecting 4 Pole MCCB, 415V, up to 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for nstallation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB. (Note:1) For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 41 | item no.03 Providing & erecting 3 Pole MCCB, 415V, up to 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB |
| 42 | item no.04 Supplying, erecting & marking TP MCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 43 | item no.05Supplying, erecting & marking TP MCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 44 | item no.06 Supplying, erecting & marking SP MCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 45 | item no.07 Supplying, erecting & marking FP MCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 46 | item no.08 Providing Power Contactor 3 pole 205A, AC3 Duty 240 V coil AC, 1 NO + 1 NC. |
| 47 | item no.09 Providing Power Contactor 3 pole 185A, AC3 Duty 240 V coil AC, 2 NO + 2 NC (LC1FDP185AE) |
| 48 | item no.10 Providing Power Contactor 3 pole 80A, AC3 Duty 240 V coil AC, 1 NO + 1 NC (TC1-D8011) |
| 49 | item no. 11 Providing Power Contactor 3 pole 32A MNX type AC3 Duty 240 V coil AC, 2 NO + 2 NC. |
| 50 | item no.12 Providing Power Contactor 3 pole 25A MNX type AC3 Duty 240 V coil AC, 2 NO + 2 NC. |
| 51 | item no.13 Providing Power Contactor 3 pole 25A MDX type AC3 Duty 240 V coil AC,1 NO |
| 52 | item no.14 Providing overload relay for motor starter Range 6-10 Sec, Relay Range 65-105A (LR1F105) |
| 53 | item no.15 Supplying and replacing thermal overload relay for motor starter 10 HP to 17.5 HP. |
| 54 | item no.16 Providing Motor Protection relay MPR D2, Range:2-5.5A, 230V AC, CTR-200/5A, Setting-3.12A. |
| 55 | item no.17 Supplying, erecting, testing & commisioning LT current transformer with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates. |
| 56 | item no.18 Supplying & replacing electronic timer above 30 HP motor starter. |
| 57 | item no.19 Providing timer 800SD-2-230, on Relay, Range 30 to 60 Sec, Change over 50/100ms, 2 C/O, 230V AC, |
| 58 | item no.20 Supplying, installing, testing and commissioning air circuit breaker manual fixed type, non-drawout type, 650V, 630A, rated at 50º C without deration, 12kV Impulse, 4 pole (100% Neutral Protection), 50 kA (Ics=Icu=Icw for 1s), with standard accessories with ready to close, individual fault trip, alarm and trip indications, mechanical and electrical anti pumping, soft/hard rating plug (including hard rating plug CT) with Micro-processer based LCD display release with LSIG and temperature rise protection & with 4 C/O contacts for On-Off-Trip indication, min. 5 event and trip history on breaker display on provided iron frame as per specification no. SW-ACB |
| 59 | item no.21 Providing 200A, 4P Switch Fuse Unit ( CSSDF200B4FN) |
| 60 | item no. 22 Providing 100A, 4P Switch Fuse Unit (CSSDF100B4FN) |
| 61 | item no.23 Providing 63 A TPN Switch Fuse Unit (CSSDF63B3N) |
| 62 | item no.24 Providing 32 A TPN Switch Fuse Unit (CSSDF32B3N) |
| 63 | item no.25 Providing HRC Fuse Link (DIN type) 200 A (CSDFL1) |
| 64 | item no.26 Construction of chamber for 100mm sluices valve |
| 65 | item no.27 Providing HRC Fuse Link (DIN type) 32 to 63 A (CDFL00 & CSDFL00 ) |
| 66 | item no.28 Push Button Illuminated Actuator, Flush (with BA9S Filament Bulb 130V) 220V AC with series resistor. |
| 67 | item no.29 Supplying and erecting panel mounting type digital ammeter having three and half digit LED display, external CT operated, calibrated for suitable to operate on 500V, 0 to 1000A having accuracy class of 0.5, AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer. |
| 68 | item no 30 Supplying and erecting panel mounting type digital voltmeter having three and half digit LED display, calibrated for 0 to 750V AC suitable to operate on 500V having accuracy class of 0.5, AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer. |
| 69 | item no.31 Supplying and erecting static energy meter with 240V 50 Hz. AC supply 10 to 60 A, accuracy class 1.0 with backlit LCD display, (measuring and display kWh, kVAh, V,I,PF, frequency, kW, kVA, six months history of energy & MD in kW & kVA) with transparent hinge type box complete erected on polished teak wood board duly wired with required size of weatherproof PVC wires duly tested by electric supply company. |
| 70 | item no.32 Supplying and erecting selector switch suitable for voltmeter/ammeter for 3 phase AC supply 500V, 50Hz, on provided box/panel and duly connecting with necessary PVC wire leads and lugs. |
| 71 | item no.33 Supplying, erecting, testing & commisioning 525 V 3 phase, 50 Hz., MPP type capacitor having minimum overcurrent capacity of 1.8 In, peak inrush current capacity 300 In and minimum life 150000 hours kVAr bank of metalised polypropylene condensers (MPP) with the standard capacities of 2, 3, 5, 7, 10, 12.5 and 15 kVAr units of P.F. correction for operation on 3 phase 50 Hz. with externally discharging resistances, earthing terminals and built on angle iron or channel iron frame work and provided with terminal cover box complete erected on provided iron bracket or on floor duly tested by licensee. |
| 72 | item no.34 LT - MCCBs (SW-MCCB)34.1 Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW-MCCB |
| 73 | 34.2 Providing & erecting 3 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB |
| 74 | 34.3 Providing & erecting 3 Pole MCCB, 415V, 160A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB |