| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 01-04-2025 | extension3rd | Date | 04-04-2025 |
| 2 | 25-03-2025 | 2nd Extension | Date | 01-04-2025 |
| 3 | 08-03-2025 | 1st Extension | Date | 24-03-2025 |
| 4 | 03-03-2025 | Pre Bid Corrigendum | Other | 07-03-2025 |
| Sl. No. | Item Description |
| 1 | Supply,installation & testingof PUF insulation with 100 mm PUF insulation material for chilled cold room -PUF Panel for Wall & Ceiling of 100 mm thickness, inclussive of all accessories as per specifications -a) Insulation material -PUF Panels.b) Density -40 +/- 2 Kg/M3c) Thickness of sheet - 0.5 mm TCT, PPGId) Total Thickness-100 mme) Thermal Conductivity -0.023 W/mK f) Compressive Strength -2.1 kg/ m2 (at 10% deformation) f) Make- Kingspan Jindal,Rinac,Lioyd |
| 2 | Supply, installation & testing of Chilled Cold RoomFloor with, Insulation Material- PUF slab of 80 mm thickness (in 2 layers of 40 mm each), Vapour Barrier, inclusive of all accessories and chemical: - a) Insulation Material - PUF slabb) Density - 40 +/- 2 Kg/M3c) No. of Layers - 2 layers ( 40 mm each)d) Total Thickness - 80 mme) Vapor Barrier - Tarfelt, Polythene Sheet 250 micron thickf) Make- Kingspan Jindal,Rinac,Lloyd,BNAL, INDUSTRIAL FOAMS |
| 3 | Supply,installation & testing of PUF insulation with 150 mm PUF insulation material for freezer cold room -PUF Panel for Wall & Ceiling of 150 mm thickness, inclussive of all accessories as per specifications -a) Insulation material -PUF Panels.b) Density -40 +/- 2 Kg/M3c) Thickness of sheet - 0.5 mm TCT, PPGId) Total Thickness-150 mme) Thermal Conductivity -0.023 W/mK f) Compressive Strength -2.1 kg/ m2 (at 10% deformation) f) Make- Kingspan Jindal,Rinac,Lioyd |
| 4 | Supply,installation & testing of Freezer Cold Room Floor with, Insulation Material- PUF slab of 120 mm thickness (in 2 layers of 60 mm each), Vapour Barrier, inclusive of all accessories and chemical: - a) Insulation Material - PUF slabb) Density - 40 +/- 2 Kg/M3c) No. of Layers - 2 layers ( 60 mm each)d) Total Thickness - 120 mme) Vapor Barrier - Tarfelt, Polythene Sheet 250 micron thickf) Make- Kingspan Jindal,Rinac,Lioyd,BNAL, INDUSTRIAL FOAMS |
| 5 | Supply,installation & testingof PUF insulation with 80 mm PUF insulation material for chilled & Frozen cold room ante chamber and Loadidng Unloadidng Area-PUF Panel for Wall & Ceiling of 80 mm thickness, inclussive of all accessories as per specifications -a) Insulation material -PUF Panels.b) Density -40 +/- 2 Kg/M3c) Thickness of sheet - 0.5 mm TCT, PPGId) Total Thickness-100 mme) Thermal Conductivity -0.023 W/mK f) Compressive Strength -2.1 kg/ m2 (at 10% deformation) f) Make- Kingspan Jindal,Rinac,Lioyd,BNAL, INDUSTRIAL FOAMS |
| 6 | Supply, Installation, Testing and Commisssioning of Hinge Door for Emergency Exit, 80mm thickness, Dimensions -1200 mm x 2100mmcomplete with all accessories as per specification :- Type of Door -Swing Doorb)Dimensions-1200 X 2100MMc)Type of panel-Sandwich panels constructed of a core of 80 mmPUF on both sides covered with 0.6 mm galvanized steel plate finished with 20mucoating. The panels are supplied with thermal bridge-free PVC surrounding profilesd) Sealing -All round with triple rubber profilee)Colour outside-RAL 9002 (white)f)Colour inside-Standard colour RAL 9002 (white/grey)g)Hardware-Galvanised Steelh)Finish of opening-To be Includedi)Door Operation - Manualj)Locking Arrangement -To be Includedk) Emergency Door Opening- to be provided(Make: Shakti Hormann, Metaflex, Infraca, Hicon) |
| 7 | Supply, Installation, Testing and Commisssioning of Horizontal Automatic Sliding Door for Freezer Cold Room, 120mm thickness, Dimensions -2400 mm x 4600mm ( clear) complete with all accessories as per specification:- a) Door Size: 2400 mm x 4600 mmb) Complete with All Accessories, Thickness of insulation – 120 mm Minimumc) No. of cycle- 500/Day d) Control Panel - Plastic control cabinet IP65, travel limit adjustment, membrane push button Open Emergency Stop-Close with integral automatic timer Sheet Thickness for Door 120mm minimume) Safety devices - Two pair of safety photocellf) Surface door closer to be providedg) Curtain - Made from modular sectionh) Vertical Pullman latch with rod and cover modular to be providedi) Single point surface panic push bar to be providedj) Door Operation – Soft based canopy cover(Make: Shakti Hormann, Metaflex, Infraca) |
| 8 | Supply, Installation, Testing and Commisssioning of Horizontal Automatic Sliding Door for Antechamber, 80mm thickness, Dimensions -1800 mm x 2400mm ( clear) complete with all accessories as per specification:- Type of Door -Manual Sliding Door (Reference Makes: Metaflex/ Shakti Horman/Infraca/Equivalent make confirming to the product specification & standards mentioned)b)Dimensions-1800 X 2400MMc)Type of panel-Sandwich panels constructed of a core of 80 mmPUF on both sides covered with 0.6 mm galvanized steel plate finished with 20mucoating. The panels are supplied with thermal bridge-free PVC surrounding profilesd) Sealing -All round with triple rubber profilee)Colour outside-RAL 9002 (white)f)Colour inside-Standard colour RAL 9002 (white/grey)g)Hardware-Galvanised Steelh)Track Rail -Drop/Lift rail systemi)Finish of opening-To be Includedj)Door Operation - Manualk)Locking Arrangement -To be IncludedL) Emergency Door Opening- to be provided |
| 9 | Supply, Installation, Testing and Commissioning ofAnte-chamber High Speed Roll Up door Size- (4600mmX2400mm)as per specifications:- a) Door Size: 2400 mm x 4600 mm of insulation thickness 1.3mm Thick Polyester Fabric PVC Coated (Self Extinguishing),Galvanised Steel Painted Side Guides and Frameb) Complete with All Accessories, Thickness of insulation – 1.2 mm Minimumc) No. of cycle- 500/Day d) Control Panel - Plastic control cabinet IP65, travel limit adjustment, membrane push button Open Emergency Stop-Close with integral automatic timer Sheet Thickness for Door 1.2mm minimume) Safety devices - Two pair of safety photocellf) Surface door closer to be providedg) Curtain - Made from modular sectionh) Vertical Pullman latch with rod and cover modular to be providedi) Single point surface panic push bar to be providedj) Door Operation – Soft based canopy cover(Make: Shakti Hormann, Metaflex, Infraca) |
| 10 | Supply, Installation, Testing and Commissioning of Hydraulic Dock Leveller of Size 2000mm X 2500mm with 6 MT capacity as per specifications:- a) Overall Dimension: 2000mm x 2500mm b) Operator and control unit: Electro hydraulic operator 415V- 3 Phase, 50Hz and control voltage 24V with minimum IP54 protection. Membrane Push Button with press and Hold actuation and emergency stop integrated in IP65 enclosure. c) DL Upwards Movement – As per European Standardd) DL Downward Movement - As per European Standarde) Hydraulic Cylinder – 2 nos.f) Load Capacity – 6 MT (Dynamic load)g) Temperature Range of operations – 5 to 10 Deg Ch) Foot Protection Plates on sides – as per EN1398i) Lip length – 405mm min.(Make: Metaflex, Shakti Hormann, Godrej, Gandhi Automation ) |
| 11 | Supply, Installation, Testing and Commissioning of Automatic Overhead sectional Door of Size 2500mm X 3000mm as per specifications:- a) Overall Dimension: 2500mm x 3000mm b) Material - Door leaf Galvanised steel, 0.5 mm PPGI, double-skinned, 40mmc) Door Construction - Self-supportingd) Closing edge safety device - Sensor controlled safety devices to monitor the bottom edge of the door. Instant stoppage and reversing on encountering any obstruction while closing.e) Colors - Inside panel & Outside color is standard RAL 9002.f) Operation - Normal lift elevation considering room height(Make: Metaflex, Shakti Hormann, Infraca) |
| 12 | Supply, Installation, Testing and Commissioning of Rectractable Dock Shelter of Size 3400mm X 3400mmas per specifications:- a) Overall Dimension: 3400mm x 3400mm (depth 500mm) +/- 100mm (Clear Opening - 2100x2400mmb) Link arm construction with link arms fitted on back frame. c) 3-side front and back frame made of galvanized steel profiles d) Flexible frame connection by link arms made of galvanized steel profiles e) Side and top flaps: to be fixed by using weather strip anodized locating profiles(Make: Metaflex, Shakti Hormann, Gandhi Automation, Infraca) |
| 13 | Supply, Installation, Testing and Commissioning of Single stage reciprocating Compressor (1 nos. working) to be provided for catering to the refrigeration load of around 316 KW for New Chilled Cold Rooms. The system offered should be energy efficient with flexibility in operations to allow for multiple storage of products and partial loads in cold rooms incorporating latest technology. This compressor is proposed as additional capacity to theexisting compressor and allied equipment and should be incorporated with existing refrigeration system. This includes all miscellaneous spare parts and ancillaries required to complete the work. The refrigeration system to be provided for all-new 10 nos. chilled cold rooms and 05 nos. frozen cold rooms (when operating as chilled rooms under dual temperature system) and ante-chamber & loading unloading area of frozen cold rooms. Supply, installation, testing and commissioning of evaporators of required capacity for ante-chamber (12 kw) and loading-unloading area (8 kw) of frozen cold room.a) Compressor system to be provided of following specifications:1. Compressor shall be 1 No. (working) 2. Evaporating SST – 5Deg C3. Condensing SDT +40 Deg C4. Refrigerant - Ammonia5. Refrigeration System – Pump feed, single stage reciprocating compressors6. Type of Compressor -Single stage Reciprocating with belt driven drive through 7. Compressors should be provided complete with all accessories including suction and discharge manifolds with isolating valves; safety relief valve; High/Low oil pressure gauge along with panel board; oil separator; High, low and differential pressure cuts out of Danfoss/ equivalent make; Oil gauge glass with valves, high pressure gauge and cut outs; other standard accessories including drive set, flywheel, belt guard, driven V-belts, base frame, toolkit, set of spare gasket, oil paper and wire filters.8. LPR system integration to be provided9. Capacity controller for multiple compressors and individual compressor steps10. 4 pole TEFC squirrel cage induction motor of 1440 RPM of suitable HP. (Make: ABB/CGL/Kirloskar/Siemens)11. Complete Selection to be submitted for approval before execution of work at site.12. Make: Bitzer /Kirloskar - KCX 6/ Frick /Mycom b) Low Pressure Liquid Receiver integration to be done.c) High Pressure Liquid Receiverintegration to be done.d)Refrigeration Piping, Fittings, Valves & Controls (1 lot)The interconnecting ammonia piping between the various parts of the plant shall be scheduled seamless pipes upto 25mm NB and ERW C-class Heavy Duty Pipes thereafter (Makes – Jindal/ Tata/ equivalent). The piping scope shall include supply of pipe lengths, necessary liquid feed assemblies comprising of solenoid valve, liquid strainer, stop valves, accessories like elbows. Tees, reducers, thermal break, clamps, threaded ends and fastener material etc. wherever required. Also included are primary and secondary steel structure and additional constructions for mounting the pipes and coolers and connecting the complete equipment. Valves for controlling the interlinked equipment like compressor, condenser, cooling water pumps, liquid ammonia receiver, chiller etc.and controls shall be viz. electronic float valve, ammonia solenoid valves, temp. humidity and pressure indicators, flow switches etc. (Make: Danfoss/ Manik/ equivalent). Digital temperature indicator cum controller of range -50 to +50 deg C (Make: AKO/Dixel/Equivalent) to control the auto run & defrost cycles with help of inbuilt timers & controls. Ammonia Gas leak detection system with alarms to be provided.e) Refrigeration line insulation & drain pipes(1 lot)RPUF sections of suitable thickness with cladding of 26 gauge aluminium sheet is used for insulating the Ammonia pipes cold surface including intercooler, LPR etc. Drain Piping with GI ‘B’ class pipe from units to outside the chiller shall be provided. Type of insulation for the drain pipe shall be Armoflex/ Vedoflex insulation along with heaters. f) VFD cum MCC Electrical Starter Panel (1 lot)The MCC Panel shall be fabricated by MS Powder coated cubicle type Panel board, dust and vermin proof having isolating switch, fuse, contractors, circuit breaker, hour meter with bus bar suitable for 400/440 volts giving output and PLC touch operated auto/manual system suitable for VFD of all compressor motor each, DOL/Star Delta Starters for cooling tower motor, condenser pumps. Electrical cables for supply items. All the main ACB/MCB/ Relays shall be of Siemens/ABB/Schneider/ L&T make and only standard components will be used for fabricating the panel. The bus bar and the mains component capacity shall be strictly based as per the power requirement sheet. Distribution panels shall be provided wherever found necessary.g) Automation Panel – Programmable Logic Controller complete with display for automatic operation and control of refrigeration equipment as per standards. Basic control will consist of :1) Automatic capacity control of compressors2) Sequence control liquid pumps3) Temperature Control and indication; RH control and indication4) Warnings and failures indication5) Possibility for automatic or manual operationNote: Integration of complete facility covering existing and all new cold rooms with automation panel to be done.h) Provision for handling accidental leakage of ammonia including Ammonia sensors in cold chambers near ACUs & plant room; gas leakage alarm system; Emergency ventilation for plant room; ammonia masks.h) Electrical Control Cabling and Wiring/Cable Tray (1 lot)Electrical cabling and wiring between the main switch panel and the refrigeration equipment shall include:-1) Power supply cable2) Control and communication cable with cable trays between the panel and field instruments and PLC and various controls3) Cable ducts etc.4) All cables, trays etc. shall be of approved makes.i) Emergency lights to be provided in all cold room.j) Structure & Support Material (1 lot)M.S. Structure, supports, angles, channel for the equipment etc. for erection of complete refrigeration equipment, pipeline support and others.k) Painting for the equipment and all the pipelines after installation (1 lot)l) First Charge of Ammonia Gas and Oil (1 lot) |
| 14 | Supply, Installation, Testing and Commissioning of Two stage reciprocating Compressor (2 nos. – 1 nos working & 1 nos standby) of around 170 KW for New 05 Nos. Frozen Cold Rooms (Make: Bitzer /Kirloskar - KCX42/ Frick /Mycom). 1. Compressor shall be 2 Nos.2. Evaporating SST – 5Deg C3. Condensing SDT +40 Deg C4. Refrigerant - Ammonia5. Refrigeration System – Pump feed, single stage reciprocating compressors6. Type of Compressor -Double stage Reciprocating with belt driven drive through 7. 4 pole TEFC squirrel cage induction motor of 1440 RPM of suitable HP. (Make: ABB/CGL/Kirloskar/Siemens)b) Low Pressure Liquid Receiver (1 no.) 1. Horizontal Low pressure accumulator 2. Minimum Design pressure for the vessel shall be 18 kg/sqm3. LP vessel to be manufactured as ASME SEC VIII Div-I4. Material of construction MS Plate made of SA 516 Grade 70 material along with all interconnection of piping suitable for supply liquid ammonia at desired temperatures5. Wet return lines and interconnecting flanges to be provided6. Safety valve connection, liquid pump outlet connection, liquid overfeed return line connection all are to be provided as suitable for system7. Stand for the receiver with necessary thermal break for receiver and structure8. Vapour vent line with all necessary interconnecting pipes up to receiver9. Un-insulated pipe for indication of the liquid level in receiver tank10. Standpipe for mounting all the control and level switches11. Valves and controls to be of Danfoss or equivalent make12. LP vessel to be designed considering defrosting air cooling unit at a time13. Liquid Ammonia Pump of 51cum flow rate with bearing work hour indicator complete with all standard accessories and control valves and fittings. The pump should be capable of circulating the liquid ammonia at required ratios and minimum flow/head should be 7.5 HP/40m head. c) High Pressure Liquid Receiver (1 no.) of suitable geometric volume to be provided of following specifications:1. Horizontal Straight through type liquid receiver2. Material of construction MS Plate of SA 516 Grade 70, shell thickness 14mm and dish end thickness 16mm complete with radiography, along with 300 PSIG hydro pressure testing .3. Receiver is provided with suitable valves/nozzles to connect liquid inlet/ outlet connection, pressure gauge connection, safety relief valve connection, liquid level glass connection, base support and other accessories.4. Operating temperature : 40 deg C5. Max. allowed pressured : 21 bar (G)6. The receiver should include stop/service valves; level gauge glass, pressure gauge, safety relief valve, oil drain valves. It should be finished with paint after having been tested at high pressure. d)Refrigeration Piping, Fittings, Valves & Controls (1 lot)e) Refrigeration line insulation & drain pipes(1 lot)RPUF sections of suitable thickness with cladding of 26 gauge aluminium sheet is used for insulating the Ammonia pipes cold surface including intercooler, LPR etc. Drain Piping with GI ‘B’ class pipe from units to outside the chiller shall be provided. Type of insulation for the drain pipe shall be Armoflex/ Vedoflex insulation along with heaters. f) VFD cum MCC Electrical Starter Panel (1 lot)g) Automation Panel (combined for complete plant) – Programmable Logic Controller complete with display for automatic operation and control of refrigeration equipment as per standards. Basic control will consist of :1) Automatic capacity control of compressors2) Sequence control liquid pumps3) Temperature Control and indication; RH control and indication4) Warnings and failures indication5) Possibility for automatic or manual operationNote: Integration of complete facility covering existing and all new cold rooms with automation panel already considered under main item no.2 above to be done.h) Electrical Control Cabling and Wiring/Cable Tray (1 lot)Electrical cabling and wiring between the main switch panel and the refrigeration equipment shall include:-1) Power supply cable2) Control and communication cable with cable trays between the panel and field instruments and PLC and various controls3) Cable ducts etc.4) All cables, trays etc. shall be of approved makes.i) Emergency lights to be provided in all cold rooms.j) Provision for handling accidental leakage of ammonia including Ammonia sensors in cold chambers near ACUs & plant room; gas leakage alarm system; Emergency ventilation for plant room; ammonia masks. (combined for complete plant).Note: Integration of complete facility covering existing and all new cold rooms with Gas Leakage detection & alarm system etc already considered under main item no.2 above to be done.k)Structure & Support Material (1 lot)M.S. Structure, supports, angles, channel for the equipment etc. for erection of complete refrigeration equipment, pipeline support and others.l) Painting for the equipment and all the pipelines after installation (1 lot)m) First Charge of Ammonia Gas and Oil (1 lot) |
| 15 | Supply, Installation, Testing, Commissioning of Evaporators of suitable capacity (reference capacity evaporator of 50 kw in 01 nos of new chilled cold room no. - 01. 1. EVAPORATOR OF REQUIRED CAPACITY OF 50 KW (01 PER COLD ROOM IN CHILLED COLD ROOMS WITH AROUND 4 AXIAL FANS OF AROUND 710MM, FIN SPACING AROUND 4 FPI. DESIRED AIR VOLUME AROUND 52000 CMH, DEFROST - ELECTRIC, MAKES- ALFA LAVAL, THERMOFIN, GUNTNER, STAR COOLER) 2. CONTROLS, ACCESSORIES, etc as required3.Make of Electrical Cable for all connecting cables - Polycab, Havells, Finolex, KEI 4.HANGING ARRANGEMENTS FOR EVAPORATORS FROM PEB BUILDING RAFTERS WILL BE IN CONTRACTOR SCOPE |
| 16 | Supply, Installation, Testing, Commissioning of Evaporators of suitable capacity (reference capacity evaporator of 40 kw in each 03 nos of new chilled cold rooms no. 2,3&4. 1. EVAPORATOR OF REQUIRED CAPACITY OF 40 KW (01 PER COLD ROOM IN CHILLED COLD ROOMS WITH AROUND 3 AXIAL FANS OF AROUND 710MM, FIN SPACING AROUND 4 FPI. DESIRED AIR VOLUME AROUND 39000 M3/HR,DEFROST - ELECTRIC, (MAKES – ALFA LAVAL, THERMOFIN, GUNTNER, STAR COOLER) 2. CONTROLS, ACCESSORIES, etc as required3.Make of Electrical Cable for all connecting cables - Polycab, Havells, Finolex, KEI 4.HANGING ARRANGEMENTS FOR EVAPORATORS FROM PEB BUILDING RAFTERS WILL BE IN CONTRACTOR SCOPE |
| 17 | Supply, Installation, Testing, Commissioning of Evaporators of suitable capacity (reference capacity evaporator of 35 kw in each 06 nos of chilled cold rooms no. 5, 6, 7, 8, 9 & 10. 1. EVAPORATOR OF REQUIRED CAPACITY OF 35 KW (01 PER COLD ROOM IN CHILLED COLD ROOMS WITH AROUND 3 AXIAL FANS OF AROUND 630MM, FIN SPACING AROUND 4 FPI. DESIRED AIR VOLUME AROUND 32000 M3/HR,DEFROST - ELECTRIC, (MAKES – ALFA LAVAL, THERMOFIN, GUNTNER, STAR COOLER) 2. CONTROLS, ACCESSORIES, etc as required3.Make of Electrical Cable for all connecting cables - Polycab, Havells, Finolex, KEI 4.HANGING ARRANGEMENTS FOR EVAPORATORS FROM PEB BUILDING RAFTERS WILL BE IN CONTRACTOR SCOPE |
| 18 | Supply, Installation, Testing, Commissioning of Evaporators of suitable capacity (reference capacity evaporator of 40 kw in 04 nos of Dual Application (0/-25 temp) cold rooms 02 per room (Frozen Cold Room No. - 1, 2, 3 & 4). 1. EVAPORATOR OF REQUIRED CAPACITY OF 20 KW (02 NOS. PER COLD ROOM IN DUAL APPLICATION (0/-25 TEMP. COLD ROOMS WITH AROUND 2 AXIAL FANS OF AROUND 710 MM, FIN SPACING AROUND 3 FPI. DESIRED AIR VOLUME AROUND 26000 M3/HR, DEFROST - HOT GAS, FAN RING HEATER (MAKES – ALFA LAVAL, THERMOFIN, GUNTNER, STAR COOLER) 2.CONTROLS, ACCESSORIES, etc as required3.Make of Electrical Cable for all connecting cables - Polycab, Havells, Finolex, KEI 4.HANGING ARRANGEMENTS FOR EVAPORATORS FROM PEB BUILDING RAFTERS WILL BE IN CONTRACTOR SCOPE |
| 19 | Supply, Installation, Testing, Commissioning of Evaporators of suitable capacity (reference capacity evaporator of 30 kw in 01 no. of Dual Application (0/-25 temp) cold rooms 02 per room (Frozen Cold Room No. - 05). 1. EVAPORATOR OF REQUIRED CAPACITY OF 15 KW (02 NOS. PER COLD ROOM IN DUAL APPLICATION (0/-25 TEMP. COLD ROOMS WITH AROUND 2 AXIAL FANS OF AROUND 630 MM, FIN SPACING AROUND 3 FPI. DESIRED AIR VOLUME AROUND 21000 M3/HR, DEFROST - HOT GAS, FAN RING HEATER (MAKES – ALFA LAVAL, THERMOFIN, GUNTNER, STAR COOLER) 2. CONTROLS, ACCESSORIES, etc as required3.Make of Electrical Cable for all connecting cables - Polycab, Havells, Finolex, KEI 4.HANGING ARRANGEMENTS FOR EVAPORATORS FROM PEB BUILDING RAFTERS WILL BE IN CONTRACTOR SCOPE |
| 20 | Supply,Installation,Testing & Commissioning of Ethylene Scrubber system 01 no in each of 10 nos New Chilled Cold Room to allow for mixed storage of fruits and vegetables to protect product quality during storage due to ethylene, Minimum ethylene absorption capacity of media: 4+ Litres/Kg. Supplier must Provide a test certificate from an accredited laboratory toconfirm the absorption capacity of the media. Media should be packed tightly in modules that fit inside the ethylenescrubbe and contracor will provide a spare kit of Media. The system should be suitable for cold room as per specification Make - Green Keeper, BE Fresh |
| 21 | Supply, Installation, Testing and Commissioning of G+5 Shuttle Racking Structure for 05 nos. Frozen Cold Rooms with total Nos. of Pallet Position in Shuttle racking will be 750 Pallets as per specification:- The storage of frozen foods, butter, ice cream, fruits and other perishable commodities in pallets has been planned at six levels within the dual temperature Cold Rooms viz. ground plus 05 racking level at an elevation of 1500mm plus without shuttle height which can be accommodated within these rooms having internal height of 12.0 m. Heavy duty racking frame arrangements must be provided within the cold rooms. The heavy duty racking (MS painted in any durable long lasting colour with anti-rusting treatment and powder coated finish suitable for high humidity conditions in cold rooms with load bearing capacity of 1000 kg per pallet. Racking system will have five nos. of shuttle with additional battery bank and charger with each shuttle. The system will be suitable for 750 pallets storage in all dual temperature Cold Rooms.1. All basic structural components of the system such as column, and beams should be Conform to Latest Euro code EN15512 standard/equivalent.2. Components & Raw material used for construction of Shuttle Racks System and Load bearing members of the system to be made out of high strength HR steel having properties equivalent to grades specified by IS 5986:2002 / IS 2062:2006/Equivalent. Upright: IS: 5986 – ISH430LA or equivalent, 355 MPa, Beam: IS: 5986 – ISH410S or equivalent, 255 MpaThe different types of material used for load bearing members such as uprights and beams should have minimum guaranteed yield strength of 355MPa. (Reference Steel type IS:5986-Fe 410/ Equivalent or IS:2062-E 350/Equivalent). The raw material used for structural load bearing members should have necessary impact strength for cold room applications of UPTO -25 Deg C. 3. Fasteners used should be with galvanized finish suitable for cold store application. 4. All powder coated components should have a proper anti-rust treatment to ensure long life and protection from corrosion in HIGH HUMIDITY CONDITIONS IN cold ROOM. The final paint finish should be tested as per IS 101:1964/Equivalent.5. Installation of Shuttle Rack System:The shuttle rack system should be provided in knock down condition to be assembled and installed at site. The complete system should have grouted on floor using expansion bolts considering that it is to be installed within cold rooms where no welding can be permitted NEITHER PUNCTURE OF INSULATION LAID BELOW THE COLD ROOM FLOOR. Shuttle 02 nos. for Frozen Storage application of -25 deg C application)Functions to be provided in shuttle: Feature should be in shuttle remote like - Start Stop, Low battery warming, Failure warning, Running Deceleration sensor, road wheel - 4, Battery coverAdditional battery and charger will be provided with each shuttle.Bollards to be provided in cold rooms for protection from accidental damage / Collison of forklift movement.Protective bollards grouted in floor of ante-chamber passage complete with paint finish of suitable strength for protection against accidental damage to cold rooms walls and doors by forklift movement. ERP Software loaded on computer shall be provided to record and monitor the placement of pallets in various pallet positions across all the cold rooms for easy monitoring and operationsNote: The total reference tonnage of steel for complete shuttle rack system frame in each cold room and execution drawing shall be approved by site engineer. 6. Standards –a) Shuttle racking component design as per EN 15512 racking standardb) European code -stringent safety factors, which ensures a safer rack, durable & reliable.c) OEM should adhere to following design standard.d) BS5950-5:1998 – code of practice for design of cold formed thin gauge sectionse) FEM 10.2.02 – The design of static steel pallet rackingf) FEM 10.3.01 – Adjustable beam pallet racking, tolerances, deformations and clearancesg) EN: 15512: 2009 – Steel static storage systems - Adjustable pallet racking systems –Principles for structural design., 7. Manufacturinga) OEM should have the In-house Manufacturing capability to Process and Manufacture cold rolled essential components of the racking system. Details to be provided by bidderb) OEM should have in-house production capability for slitting, blanking, shearing lines.c) OEM should have Raw material of upright, beam and guide rail should be tested from NABL approved lab of every component to their original raw material for the storage racking system.d) OEM should have experienced Design, R&D facility in the field of Storage system. The evidence shall include:3. Eco friendly Supplier –a) PAINT SUPPLIED MUST BE LEAD FREE – CERTIFICATION OF THE PAINT MANUFACTURER TO BE ATTACHED8. Shuttle Racking Specs –a) Shuttle support beams deformation is restricted to 5mm in designb) Shuttle racking component design as per EN 15512 racking standardc) Supply of the entire bid quantity in single lot without splitting of orderd) Compliance to all design standards relevant to the supply - OEM must be following quality design standards and relevant design patents to prove superior product.e) Upright: shall be manufactured from HR steel as per IS2062/IS1079 confirming to 355mpa.f) Omega profile, Rolled Formed, 12 bend, Single piece. g) BEAM, BASE PLATE: SHALL BE MANUFACTURED FROM HR IS2062/IS1079 GRADE STEEL. h) For the affixing of the structure to the floor use of chemical fastener should be preferred. (Reference Make for Racking System: - Godrej, Silverlining, Craftman, Giraffe, Racks & Rollers, Equivalent make confirming to the product specification & standards mentionedNOTE: The design &drawing of racking structure would be checked for economical design & Structural safety by a 3rdparty designer as per the instruction of the Engineer In-charge/J K Agro official and thereafter the same design and drawing shall be vetted from any IIT/NIT. The fees for proof checking of the design drawing by the 3rd party designer and vetting by IIT/NIT will be borne by the agency/contractor.(Reference Make for Racking System: - Godrej, Silverlining, Craftman, Giraffe, Racks & Rollers, Equivalent make confirming to the product specification & standards mentioned |
| 22 | Supply, Installation, Testing and Commissioning of 03 nos. shuttle for G+5 Shuttle Racking Structure for in 05 nos. Frozen Cold Rooms negative temperature -25 deg C as per specification: -Shuttle Equipment: (Make: Godrej, Automah, Adverb, Craftman, Equivalent make confirming to the product specification & standards mentioned) 1. Standard Shuttle weight 230 Kg (approximate) Standard carrying load 1500 KgTemperature range for frozen cold room-25°C to -1°CHumidity (ST & BZ) 10% to 85% (Not condensed)Wheels 4/8 wheels (Polyurethane)Battery type Litio (lithium-ion battery)Min. charging life Min 900 charging (Battery life of 4 to 5 years)Battery working range 8 to 10 hours (room temperature) Charging time 100% 5 hours2. Remote Controller:a) Manage up to 4 shuttles.Remote control Radio frequencyPower supply Rechargeable batteryProtection IP65Temperature range-25°C to -1°CWorking range Up to 60meterStand by function Standby mode active after 3 Min of not use.b) Shuttle should be able to count the pallets in single or multiple racks. The overall number of the pallets on the rack or in the warehouse is shown on the display of the transmitter. |
| 23 | The storage of fruits and other perishable commodities in crates, cartons, bags have been planned at five levels within the New Chilled Cold Rooms Nos. 1 to 10 (Total 10 Chambers) viz. ground plus four (G+4) mezzanine level at an elevation of around 2.4 m and which can be accommodated within these rooms having internal height of 12.0 m. Heavy duty self-supported mezzanine column/frame arrangements have been planned within the cold rooms. Access to the upper levels is planned through an internal staircase. The heavy duty mezzanine (MS painted in any durable long lasting colour with anti-rusting treatment and powder coated finish) to be provided in each cold room should be of height around 2.4m with load bearing capacity of 1000 kg/m2. A Staircase to be provided 2.4m height to access the upper levels of cold rooms. All basic structural components of the system such as column, and beams to be Conforms to Latest Euro code EN15512 standard or applicable British and IS code.Components & Raw material used for construction of mezzanineLoad bearing members of the system to be made out of high strength HR steel having properties equivalent to grades specified by IS 5986:2002 / IS 2062:2006/Equivalent. The different types of material used for load bearing members such as uprights and beams should have minimum guaranteed yield strength of 255MPa. (Reference Steel type IS:5986-Fe 410/ Equivalent or IS:2062-E 350/Equivalent). The raw material used for structural load bearing members should have necessary impact strength for cold room applications of 0 Deg C. Fasteners used should be with galvanized finish suitable for cold store application. All powder coated components should have a proper anti-rust treatment to ensure long life and protection from corrosion in cold store. The final paint finish should be tested as per IS 101:1964Perforated decking panel/Grating (catwalk surface of the mezzanine used for storage of material) suitable to allow for smooth air flow within the cold room.Staircase should have anti-skid embossed type steps complete with safety railing. For the affixing of the structure to the floor use of chemical fastener should be preferred.Installation of Mezzanine The mezzanine system should be provided in knock down condition to be assembled and installed at site.The complete system should have grouted on floor using expansion bolts considering that it is to be installed within cold rooms. Note: The total reference tonnage of steel for complete mezzanine frame in each cold room and execution drawing shall be approved by the site in-charge / PMC.The design & drawing of mezzanine structure would be checked for economical design & Structural safety by a 3rdparty designer as per the instruction of the Engineer In-charge/J K Agro official and thereafter the same design and drawing shall be vetted from any IIT/NIT. The fees for proof checking of the design drawing by the 3rd party designer and vetting by IIT/NIT will be borne by the agency/contractor.(Make: Godrej, Silverlining, Craftman, Giraffe, Racks & Rollers, Jay Equipment, Equivalent make confirming to the product specification & standards mentioned) |
| 24 | Supply, Installation, Testing and Commissioning of reach truck 10000 mm. lifting height as per specification:- (Make: Godrej/Linde/Toyota/Jungheinrich, Equivalent make confirming to the product specification & standards mentioned) a) Capacity: 1600 kg or 1.60 Tonsa) Capacity: 1600 kg or 1.60 Tonsb) Load Centre: 600 mm c) Lift Speed: 0.40 ms /0.50ms approxd) Fork Length: 1200 e) Battery Carrier: To be providedf) Control type: Control with AC Induction Motorg) Lift Height – 10000 mm minimum, Maximum mast height 4500 mm.h)Additional Battery and Charger to be provided along with each Reach Truck.i) Lift capacity at maximum load height of 10000 mm should be minimum 1000 kg j) Wireless camera system for reach trucks to be provided k) Operating temperature within cold rooms shall be minimum -25 Deg and maximum 12 Deg C. |
| 25 | Supply, Installation, Testing and Commissioning of hand pallet truck with 2500 kg lifting capacity as per specification:- (Make: Godrej/Mahindra Stiller/Lokpal/Maini, Equivalent make confirming to the product specification & standards mentioned) a) Load Capacity : 2500 kgb) Fork Length : 1100 mm min.c) Fork Width : 150 mm min.d) Out Side Fork Spread : 550 mm min.e) Inside Fork Spread : 250 mm min. |
| 26 | Supply, Installation, Testing and Commissioning of Plastic pallets of outer dimensions 1200mm x1000mm x 150mm for dynamic load 1200kg and static load 4000kg, made of HDPE 100% virgin material with 04 steel bones with Reusable Pallet Strap - : 4no’s, Pallet Dimension (outer) 12000mmx1000mmx150mm a)Dynamic load 1200kgb)Perforatedc)Material of Construction HDPE 100% virgin materiald) Pallet strap specifications (4 nos with each pallet, total - 3200 nos.): Velcro Type/PP straps, weight bearing capacity of 500kgs.e) Client name and No. will be printed on each pallet with reflective paint. |
| 27 | Supply, Installation, Testing and Commissioning of Fire Doors with 2hrs. Fire rating for required size of 1.5 x 2.1 mtr. with vision glass and signage board. |
| 28 | Diesel Generator set:- Supply, installation, testing & commissioning of Diesel Generating Set of 400KVA rating Silent Type Radiator type, suitable for of 415V, 3 phase 4 wire, 0.8 pf. (lagging) 50c/s A.C supply complete with engine (1500 RPM) and alternator DG Set controller with accessories including residential type silencer and manual control panel fuel service tank as per standard, battery and battery charger with all associated accessories including MCCB of suitable rating & standard set of tools and anti-vibration mounting pads etc. The specification shall be as per CPCB IV specification attached. The instalation, testing, commissioning shall be done as per CPCB IV. |
| 29 | Supply of 12\" (305mm) dia (900 rpm) single phase Exhaust fan with louvres complete as required. For toilet |
| 30 | Supply of following sizes alluminium conductor, XLPE insulated, armoured, PVC sheathed cable 1100 V grade complete as required.4X10 Sq. mm |
| 31 | Supply of following sizes alluminium conductor, XLPE insulated, armoured, PVC sheathed cable 1100 V grade complete as required.3.5C x 240 Sq. mm |
| 32 | Supply of following sizes copper conductor, XLPE insulated, armoured, PVC sheathed cable 1100 V grade complete as required.4C x 6 Sq. mm for street lights |
| 33 | Supply of following sizes alluminium conductor, XLPE insulated, armoured, PVC sheathed cable 11000V grade complete as required. 3X70 sq mm |
| 34 | Providing and fixing Carbon-di-oxide fire extinguishers consisting of welded M.S cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 30cms long high pressure discharge hose, dischargenozzle, suspension bracket, confirming to IS: 2878 finished externally with redenamelpaint andfixed towall with brackets with rawl plug/dash fasteners complete with internal charge. Capacity 4.5 kg. ISI Marked. |
| 35 | Providing and fixing mechanicalfoam type (ISI marked) fire extinguishers consisting of weldedM.S. cylindricalbody squeeze lever dischargevalve 30 cm long high pressure dischargehose, discharge nozzle suspension bracket ISI marked finished externally with red enamel paint and fixed to wall with brackets complete with internal charger.. 50 liters capacity (trolley mounted)( IS. 13386) |
| 36 | Providing and fixing waterCo2(ISI marked) extinguishers includingall accessoriesas per IS specification. (IS 940) with wall bracket with rawl plug. Capacity 9 liters. |
| 37 | Providing and fixing ABC powder type fire extinguishers consisting of welded M.S. cylindrical body automatic modular ABC powder type extinguisher actuated through a sprinkler head mounted on The extinguisher body finished externally with red enamel paint and fixed to ceiling with brackets complete with internal charge. [For Transformer/DG/LT panel room]. Capacity 5 Kg. |
| 38 | Providing and Fixing Fire Bucket with Stand 9Lts. Capacity with 4 Bucket |
| 39 | Transformer Input: 11KV+/- 5% in steps of 2½ %, 3 Phase, 50Hz, Dyn11, ONAN, Copper wound, Indoor, oil cooled, Temperature rise: 50/55⁰C. Indoor Cable end box.Output 433v, 3 Ph, 50 Hz, + Neutral.LTCable end box suitablefor 2Nos 3½X 240 mm² LT cables in outgoing. All mounted accessories shall be there as per latest IS specifications. Capacity 315KVA . This transformer shall run in parallel with the existing 315KVA transformer with equal load sharing. Vendor to satisfy the conditions before procurement. |
| 40 | Supply, Installation, Testing & Commissioning of indoor type Free standing main LT Panel suitable for 415A, 3P + N +E, 50HZ, 50KA, including 130 KVAR capacitor section with following switch gears:- Design as per SLD. This panel shall be coupled with the existing running panel after the Bus coupler of the existing panel. Vendor to coordinate this coupling and panel sizing. Incomers: 1 Nos 630A MCCB, 1 no 800A MCCB as per SLD. 5 NOS 63 A MCCB, 2 Nos 200A MCCB,2 Nos 160A MCCB,1 No 250A MCCB, 1 No 320A MCCB, with 130KVAR capacitor bank (25#4No + 15KVAR#1 +10KVAR#1 + 5KVAR#1) with APFCR. Outgoings:5 NOS 63 A MCCB, 2 Nos 200A MCCB,2 Nos 160A MCCB,1 No 250A MCCB, 1 No 320A MCCB, with 130KVAR capacitor bank (25#4No + 15KVAR#1 +10KVAR#1 + 5KVAR#1) with APFCR. Main busbar 75X10 mm Al. for Phases and 75X6mm Al for neutral |
| 41 | Supply of prewired box type LED luminaires, ceiling/ surface mounted with all accessories as per standard items, connection with 1.5 sq. mm. PVC insulated wire complete as required and as per approved makes. Simillar to Wipro Cat. No LH09-851-060-50-VS 4065W,IP66 PROTECTION or equivalent |
| 42 | Supply of prewired box type LED luminaires, ceiling/ surface mounted with all accessories as per standard items, connection with 1.5 sq. mm. PVC insulated wire complete as required and as per approved makes. Simillar to WIPRO Cat. No. LE20-491-XXX-57-XXLED IP65 39W or equivalent. |
| 43 | Supply of prewired box type LED luminaires, ceiling/ surface mounted with all accessories as per standard items, connection with 1.5 sq. mm. PVC insulated wire complete as required and as per approved makes. Similar to WIPRO Cat LE20-491-XXX-57-XX IP65 39W or equivalent |
| 44 | Supply of prewired box type LED luminaires, ceiling/ surface mounted with all accessories as per standard items, connection with 1.5 sq. mm. PVC insulated wire complete as required and as per approved makes. 2x20w LED WALL Light. Similar to WIPRO Cat WIO922208+LL13+181+65SE |
| 45 | Supply of prewired box type LED luminaires, ceiling/ surface mounted with all accessories as per standard items, connection with 1.5 sq. mm. PVC insulated wire complete as required and as per approved makes. 2x20w LEDLight. Similar to WIPRO Cat WIO922208+LL13+181+65SE |
| 46 | Supply of prewired box type LED luminaires, ceiling/ surface mounted with all accessories as per standard items, connection with 1.5 sq. mm. PVC insulated wire complete as required and as per approved makes. 18W LED Down Light. Similar to WIPRO Cat CRDL-1150-23HP-57 |
| 47 | Supply of prewired box type LED luminaires, ceiling/ surface mounted with all accessories as per standard items, connection with 1.5 sq. mm. PVC insulated wire complete as required and as per approved makes. Similar to WIPRO Cat LD90-231-XXX-65-XX 18W or equivalent |
| 48 | Supply of prewired box type LED luminaires, ceiling/ surface mounted with all accessories as per standard items, connection with 1.5 sq. mm. PVC insulated wire complete as required and as per approved makes. Similar to WIPRO Cat LR02-781-XXX-57-G2IP65 70W or equivalent |
| 49 | 1.3 Wiring for light point/fan point/exhaust fan point/call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm.FRLS PVC insulated copper conductor single core cable etc as required. For Cold Room, Sorting grading, Loading Unloading, galleries, Ante Chambers etc. 1.3.3 Group C |
| 50 | 1.5 Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class steel conduit alongwith 1 Nos 4 sq. mm FRLS PVC insulated copper conductor single core cable cable for loop earthing as required. |
| 51 | 1.7 Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed steel conduit as required1.7.3 2 X 4 sq.mm +1 X 4 sq.mm earth wire |
| 52 | 1.24 Supplying and fixingfollowing modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required1.24.1 5/6 amps switch |
| 53 | 1.24 Supplying and fixingfollowing modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required1.24.3 15/16 amps switch |
| 54 | 1.24 Supplying and fixingfollowing modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required1.24.4 3 pin 5/6 amps socket out let |
| 55 | 1.24 Supplying and fixingfollowing modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required1.24.5 6 pin 15/16 amps socket outlet |
| 56 | 1.25 Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 57 | 1.27 Supplying and fixing following size/ modules, GI box along with modular base & cover plate & for modular switches in recess etc as required. 1.27.1 1 or 2 Module (75mmX75mm) |
| 58 | 1.27 Supplying and fixing following size/ modules, GI box along with modular base & cover plate & for modular switches in recess etc as required. 1.27.2 3 Module (100mmX75mm) |
| 59 | 1.27 Supplying and fixing following size/ modules, GI box along with modular base & cover plate & for modular switches in recess etc as required. 1.27.3 4 Module (125mmX75mm) |
| 60 | 1.27 Supplying and fixing following size/ modules, GI box along with modular base & cover plate & for modular switches in recess etc as required. 1.27.4 6 Module (200mmX75mm) |
| 61 | 1.27 Supplying and fixing following size/ modules, GI box along with modular base & cover plate & for modular switches in recess etc as required. 1.27.5 8 Module (125mmX125mm) |
| 62 | 1.27 Supplying and fixing following size/ modules, GI box along with modular base & cover plate & for modular switches in recess etc as required. 1.27.6 12Module (200mmX150mm) |
| 63 | 1.18 Supplying and drawing of following pair 0.5 sq.mm FRLS PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/ recessed steel/ pvc conduit as required. 1.18.2 2 Pair |
| 64 | 1.41 Installation, Testing and commissioning of pre-wired fluorescent fitting/compact fluorescent fitting of all types, complete with all accessories and tube etc. on wall / cieling and connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 65 | 1.50.1 Installation of exhaust fan upto 450 mm sweep in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning etc as required. |
| 66 | 1.51 Extra for fixing the louvers/ shutters complete with FRLSame for a exhaust fan of all sizes. |
| 67 | 2.4 Supplying and fixing following ways, surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted inclusive oftinned copper bus bar, common nutral link, earth bar, din bar for mounting MCB\"s (but without MCB\"s and incomer) as required.2.4.3 8 way (4 + 24), Double Door |
| 68 | Supplying and fixing following ways, surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted inclusive of 200 amps tinned copper bus bar, common nutral link, earth bar, din bar for mounting MCB\"s (but without MCB\"s and incomer) as required. Vertical type with 8 Nos 3phase outgoings. 2.5.3 12 way (4 + 36), Double Door |
| 69 | 2.2.4 200A, 16KA, TPMCCB |
| 70 | 2.14 Supplying & fixing following rating double pole 240V RCCB in existing DBs 2.14.3 63A |
| 71 | 2.10 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve,miniature circuit breaker suitable for lighting and other loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc.as required. 2.10.1 Single pole |
| 72 | 2.10 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve,miniature circuit breaker suitable for lighting and other loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc.as required. 2.10.4 Triple Pole 32 Amps |
| 73 | 2.15 Supplying & fixing following rating for pole (three phase and neutral) 415V RCCB having sensivity current 30 mA in the existing MCB DB complete with connection, testing commissioning etc. as required 2.15.3 63A |
| 74 | 2.18 Supplying and fixing of 20 Amps, 240 Volts, SPN industrial type socket outlet with 2 pole and earth, metal enclosed plug top along with 20 amps C curve SP MCB in sheet steel enclosure on surface or recessed with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required.(For Dock Leveller, Shuttle Chargers, Doors) |
| 75 | 2.20 Supplying and fixing of 30 Amps, 415 Volts, TPN industrial type socket outlet with 2 pole and earth, metal enclosed plug top along with 20 amps C curve TP MCB in sheet steel enclosure on surface or recessed with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required. For Fork lift charger. |
| 76 | 4.1 Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended FRLSom the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required. 4.1.7 600 mm width X 50 mm depth X 2.0 mm thickness |
| 77 | 4.1 Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended FRLSom the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required. 4.1.4 300 mm width X 50 mm depth X 2.0 mm thickness |
| 78 | 5.2 Earthing with GI pipe 4.5 meter long , 40 mm diaincluding accesoried , and providingmasonary enclosurewith cover platehaving locking arrangement and wateringpipe of 2.7m long etc. with charcoal/coke and salt as required. For Lightning Arrestors. |
| 79 | 5.6 Earthing with Copper earth plate 600mm x 600mm x 3mm thick including accesories, and providingmasonary enclosurewith cover platehaving locking arrangement and wateringpipe etc. with charcoal/coke and salt as required. For Neutral Earth. |
| 80 | 5.4 Earthing with GI earth plate 600mm x 600mm x 6mm thick including accesories, and providingmasonary enclosurewith cover platehaving locking arrangement and wateringpipe etc. with charcoal/coke and salt as required. For Equipment Body Earth. |
| 81 | 5.8 Supplying and laying 25X5mm Copper Strip at 0.5 mtr below ground as strip earth electrode, including connection/termination with nut bolt spring washer, etc as required.(Jointing shall be done by overlapping with 2 sets of brass nut bolt and spring washer spaced at 50mm) |
| 82 | 5.9 Supplying and laying 25X5mm GiStrip at 0.5 mtr below ground as strip earth electrode, including connection/termination with nut bolt spring washer, etc as required.(Jointing shall be done by overlapping with 2 sets of GI nut bolt and spring washer spaced at 50mm) |
| 83 | 5.18 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 84 | 6.2 Providing and fixing of lightning conductor finial, made of 25 mm dia 300mm long, G.I. tube, having single prong at top, with 85mm dia 6mm thick G.I. base plate including holes etc. complete as required. |
| 85 | 6.7 Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 86 | 6.8 Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 87 | 6.12 Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 88 | 6.14 Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. |
| 89 | 7.5 Laying of one number PVC insulated PVC sheathed / XLPE power cable if 1.1KV grade of the following size in existing RCC/ Hume/ Metal pipe in ground. 7.5.1 Upto 35 sq mm |
| 90 | 7.5 Laying of one number PVC insulated PVC sheathed / XLPE power cable if 1.1KV grade of the following size in existing RCC/ Hume/ Metal pipe in ground. 7.5.4 above 185 sq.mm. upto 400sq. mm |
| 91 | 7.8 Laying and fixing of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size on cable tray as required. 7.8.1 Upto 35 sq.mm (clamped with 1mm thick saddle) |
| 92 | 7.8 Laying and fixing of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size on cable tray as required. 7.8.4 Above 185 sq.mm and upto 400 sq.mm (clamped with 40x3mm MS flat clamp) |
| 93 | 9.1 Supplying and making end termination with brass compression gland and aluminium lugs for the following sizes of PVC insulated PVC sheathed /XLPE aluminium conductor cableof 1.1KV grade as required. 9.1.32 4X10/6 sq. mm |
| 94 | 9.1 Supplying and making end termination with brass compression gland and aluminium lugs for the following sizes of PVC insulated PVC sheathed /XLPE aluminium conductor cableof 1.1KV grade as required. 9.1.29 3.5 X 240 sq. mm |
| 95 | 14.14 Providing, laying, and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortor 1:2 ( 1 cement, 2 fine sand) including trenching (75cm deep) and refilling as required. For cables from transformer, DG Sets, Stabiliser etc. 14.14.4 300 mm dia |
| 96 | 8.4 Laying of one No. PVC insulated, PVC Sheathed/XLPE power cable of 11KV grade of following size in existing masonary open duct as required. 8.4.1 Upto 120 SQ. mm |
| 97 | 10.1 Supply and making indoor cable end jointing with cast resin compound including lugs and other jointing material for the following 3 core XLPE aluminium conductor 11KV grade as required 10.1.1 3X70 sq.mm |
| 98 | 17.1.11 Supply , installation testing, commissioning of main control and indicating panel made out of 16 SWG sheet to accommodate the following items, duly powder coated in approved color with louvers for ventilation, locking arrangement, audio / visual indication for fire alarm and PA system, monitoring system system including connection, interconnection etc complete as required. 6 Zone panel for Fire Alarm system. 100 W amplifier racks suitable for operation on 230V AC/ 24V DC supply conforming to IEC 268-3 complete with all accessories as required. 2 Nos. Talk back master station with LED Push to talk push button for operation on 230V AC/24VDC supply conforming to IEC 268 for simplex mode of operation/ communication suitable for 20 Nos talk back unit - 1 set. Amplifier change over switch for interchanging amplifer -1 no. Montor panel for loud speaker complete output selector ON/OFF switch, fuse visual indications etc complete as required. - 1 no. Gooseneck microphone with stand and ON/OFF switch - 1 No. Mains ON/OFF switch, fuse indcating lamps, DC & AC Voltmeter and ammeter, terminal blocks etc complete as required. - 1 set. Battery charger trickle cum boost to take complete load of Fire Alarm and PA system complete with all accessories including providing and fixng 2 Nos 12V 30AH each sealed maintenance free batteries - 1 set |
| 99 | 17.1.2 Supply, Installation, testing & Commisioning ofSmoke Detector with builtin LEDand mounting base complete with all connection as required |
| 100 | 17.1.7 Supply, Installation, testing & Commisioning of fire alarm sounder with facility to make announcement mounted in ABS box with hinged cover plate and suitable for operation with amplifier i/c line matching transformer etc complete as required. |
| 101 | 17.1.4 Supply, Installation, testing & Commisioning of manual call box of ABS type in surface / recessed with Stainless Steel chain and hammer assembly complete with glass, push button etc as required. |
| 102 | 17.1.1 Supply, Installation, testing & Commisioning of heat detector operating at 54°C /57°C with rate of rise cum fixed temperature( dual thermister) type with mounting base complete with all connections etc as required. |
| 103 | 17.1.5 Supply, Installation, testing & Commisioning of response indicator on recess/surface MS Box having two LEDs metallic cover complete with all connectionsetc as required |
| 104 | 17.5.2 supplying and layng of 2X1.5 mm² fire survival armoured cable, 600V/1000V rated with annealed copper conductor having XLPE insulated steel wire armoured and FRLS outer sheath complete as required. |
| 105 | 1. Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operationon 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration pads.1.4 2280 lpm at 88 m Head Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 ressure at the highest/farthest point. |
| 106 | 2. Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, multistage, centrifugal pump of cast ofiron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office redcolour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 2.4 2280 lpm at 88 m Head. Note: * The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. |
| 107 | 3. Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.180 lpm at 88 m Head. |
| 108 | 5. Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect,suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required : 5.4 Incomings 400A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500AmpsOutgoings( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pumps 125 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 hp pumpwith overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets Jockey Pump 63 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets. Diesel Engine Control Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciationwindow for fault indication, complete as per specification |
| 109 | 6. Providing laying, testing & commissioning of \"C\" class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 6.2 150 mm. Dia |
| 110 | 7. Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 7.1 25 mm dia |
| 111 | 7. Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 7.2 32 mm dia |
| 112 | 7. Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 7.3 40 mm dia |
| 113 | 7. Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 7.5 65 mm dia |
| 114 | 7. Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 7.6 80 mm dia |
| 115 | 7. Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 7.7 100 mm dia |
| 116 | 9. Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steelcoupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : 9.1 Single headed Gunmetal |
| 117 | 10. Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : 10.1 Single headed Gunmetal |
| 118 | 11. Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 11.3 65 mm dia |
| 119 | 11. Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 11.4 80 mm dia |
| 120 | 11. Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 11.5 100 mm dia |
| 121 | 11. Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 11.6 150 mm dia |
| 122 | 12 .Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : 12.3 65mm dia |
| 123 | 12 .Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : 12.4 80mm dia |
| 124 | 12 .Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : 12.5 100mm dia |
| 125 | 12 .Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : 12.6 150mm dia |
| 126 | 13. Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 127 | 14. Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 14.3 65mm dia |
| 128 | 14. Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 14.4 80mm dia |
| 129 | 14. Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 14.5 100mm dia |
| 130 | 14. Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 14.7 150mm dia |
| 131 | 15. Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 15.2 100mm dia |
| 132 | 16. Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : 16.1 Gun Metal |
| 133 | 17. Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 17.1 30 M |
| 134 | 18. Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : 18.1 Gun metal |
| 135 | 19. Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 19.2 4 way - 150 mm dia M.S. Pipe |
| 136 | 20. Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. |
| 137 | 21. Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : 21.1 Pendent Sprinkler |
| 138 | 22. Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 139 | 23. Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 23.2 150mm dia |
| 140 | 24. Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves,MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : 24.3 150mm dia |
| 141 | 25. Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPTfemale thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 25.4 1500mm |
| 142 | 26. Supplying, installation, testing & commissioning of deluge valve (to be used for water curtains) UL listed with wet pilot basic trim assembly for DVA with test and alarm, drip and drain valve with water motor gong complete as required. 26.4 150mm dia |
| 143 | 29. Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
| 144 | 2.6 Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge 2.6.1All kindsof soil. |
| 145 | 2.26 Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials.2.26.1 \"All kindsof soil. |
| 146 | 4.1 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :4.1.8 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 147 | 5.33 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.5.33.1All works upto plinth level.5.33.1.1 Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 148 | 5.33 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.5.33.2 All works above plinth level upto floor V level 5.33.2.1 Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 149 | 5.22 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.5.22.6Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 150 | 5.22A Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. 5.22A.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 151 | 5.9 Centering and shuttering including strutting, propping etc. and removal of form for 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete |
| 152 | 5.11 Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to bemeasured).5.11.1 Suspended floors, roofs, landing, beams and balconies (Plan area to be measured) |
| 153 | 6.1.2 Cement mortar 1:6 (1 cement: 6 coarse sand) |
| 154 | 10.25 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. 10.25.2 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |