| 1 | M& L for Taking up Old unserviceable HT underground cable of any type from the ground, wall, floor etc after disconnecting of any size including cable cover complete all as specified and directed. |
| 2 | Supply, laying, testing and commissioning XLPE insulated, screened, PVC bedded, galvanized strip or armored power cables (heavy duty) with stranded aluminium conductor, 22000 Volts grade underground cable of size 3 core, 95 Sq mm complete all as specified and directed. |
| 3 | Supply and fix cable jointing kit for 22 KV (Earthed) grade cable for straight through heat shrinkable type suitable for underground XLPE cable size 3 core 95 Sqmm 22 KV HT cable complete all as specified and directed. |
| 4 | Supply and fix GI pipe 100 mm dia light grade complete with all fitting for supporting cable on four pole structure complete all as specified and directed. |
| 5 | M&L for PCC 1:4:8 type D-2 using 40 mm graded stone aggregatesfor fixing cable protection pipes at Nalls complete all as specified and directed. |
| 6 | M&L for cable path indicator made with PCC block of size 45x60x10 cm with 1:2:4 using 20mm graded stone aggregates pre cast using 6mm 20cm concrete and grounded in ground, embedded loop/joint on the block in words complete all as specified and directed. |
| 7 | M & L for Excavation in trenches not exc 1.5 m in depth and not exc 1.5 m wide for taking out/laying cable and getting out in Hard rock complete all as specified and directed. |
| 8 | M & L for Excavation in trenches not exc 1.5 m in depth and not exc 1.5 m wide for taking out/laying cable and getting out in Hard/dense soil complete all as specified and directed. |
| 9 | M & L for Removing excavation soil at a distance not exc 50 m and deposited where diverted complete all as specified and directed. |
| 10 | M & L for Returning, filling in including spreading, leveling, watering and well rumming in layers not exc 25 cm complete all as specified and directed. |
| 11 | M & L for Sand cushioningfor cable protection by spreading in trenches crushed stone sand by gently punning down manually complete all as specified and directed.Note:- Punnned thickness shall only be measured and paid. |
| 12 | Supply and laying un reinforced precast concrete cable cover class HV, type-I, flat size 300 mmx 180 mm x 40 mm laid in trenches complete all as specified and directed. |
| 13 | Relaying reinforced precast concrete cable cover of any type complete all as specifed and directed by Engineer-in-Charge.Note : The PCCCoverremoved during removal ofcables be used based on serviceablity state |
| 14 | S&F cable jointing kit for 22 KV (earthed) grade cable for indoor termination heat shrink type joint complete with and including jointing material and accessories suitable for 3 core XLPE armoured aluminium cable of size 95 Sqmm, also including connecting with single thimbles etc after disconnecting of electric supply including removing burnt out jointing kit etc, complete all as specified and directed. |