Name of Work : Repair / Maintenance of Earthings, Cable Route Indicator, Cable Fault and other misc work at Mil Stn Kanasar
Sl. No.
Item Description
1
Checking of electric connection/ supply in the condition of No light /breakdown (Read below Note carefully) of LT electric supply for street light & guard post at perimeter,Outer & Inner depot area and making new connection after cutting of old worn out cable with proper thimbling & tapping etc as required at site completeall as specified and directed.. NOTE :- (i) 01 x Skilled Electrician and one helpers should be made available for Checking of electric connection/ supply all week days.(ii) Complaints given to contractor\"s rep/electrician shall be Attended with in stipulated time period as directed. (iii) Contractor will arrange all the T&P/ conveynance/transportation veh &Its fuel for electrician & helper to attend Checking of electric connection/ supply . (iv) A penality will be charged for not attending the Checking of electric connection/ supply Within stipulated time period as directed by Engineer-in -charge. (v) Contractor will provide register and maintain the record of Checking of electric connection/ supply.
2
Supply and fixing in replacement of GI strip 32 mm x 6 mm as earthing strip including connecting with nut, bolts etc complete all as specified and directed.
3
M&L for earthing complete with galvanized steel earth plate electrodesize 600 mm x 600 mm x 6.3 mm thick buried directly in groundvertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized iron strip 32 x 6mm as earthing lead and GI protection pipe light grade 40 mm dia connected to main earth strip on panel or control board and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. RCC cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed. Note:-The unit rate includes for protection pipe and GI stripfrom top of earth plate up to 7.5 meter above ground level.
4
Testing and fault locating of LT undergroung cable with the help of cable fault locating machine at site including removal of moisture content from cable complete all as specified and directed.Note:-(i) It is clearly stated that fault locating machine can be called for one fault also, the rate should be quoted considering this.(ii) The machine for locating offault will be arranged by the contractor . (iii) The Contractor must called fault locating machine within 24 Hrs of fault intimation.
5
M & L for repositionig on Cable path of Cable path route indicator in described position and painting with redoxide primer and enamel paint and writing cable size on it with bright colour complete all as directed and specified
6
M& L for cable route indicator made of Jodhpur stone of finished size 90cm x 20cm x 15cm with round top and all finished surfaces duly marked with \"LT\" lettering of size 6cm x 6cm engraved on two sides on two sides of the stone and letters painted with thick synthetic enamel paint of red colour complete all as specified and directed. Notes:- (i) These shall be fixed along the route of cable at 30 meter interval & on every turning & cable point as directed.
7
M & Lfor Cleaning and prepration of old painted surface with amren paper of steel tubular pole 9/9.5 long and painting with one coat of enamelled aluminium paint including clamps etc. and making alternative black and white strips on pole with synthetic enamel paint (each strip 30 cm height) upto 1.5 mtr long height from top of PCC foundation block and writing pole Nos including applying one coat of cement base paint on PCC coping complete all as directed by Engineer-in-Charge.
8
Material & labour for cleaning internal & external surface, removing other foreign material and rubbing of external surface by amren paper of feeder pillarbox/LT panelsand preparing the both surface for paint, spraying by gun one coat of synthetic enamel paint of existing colour of panel on Internal and External surface, including minor repairing of panels like door hinges, locks and making provision for external lock with welding/nuts bolts and providingdetachable gland plate with cable gland with closure for cable entry as required on ground etc complete all as specified and directed .