Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 10-03-2025 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 17-03-2025 |
| 2 | 28-02-2025 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 10-03-2025 |
| Sl. No. | Item Description |
| 1 | A. Civil Works |
| 2 | Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge |
| 3 | Removing existing PVC flooring & skirting, cleaning the surface by suitable thinner and disposal of unserviceable material from the area to the identified place in the SCL campus, stacking etc. all complete as per the direction of Engineer-In-Charge. |
| 4 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. |
| 5 | In cement mortar |
| 6 | Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead |
| 7 | For thickness of tiles 10 mm to 25 mm |
| 8 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 9 | Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer\"s specifications including appropriate priming coat, preparation of surface, etc. complete as per directions of E-I-C. |
| 10 | Note: The work includes (Preparing the old painted surface by sandpapering with emery paper, filling the crevices and smoothning wall surface with two coats of suitable epoxy putty where ever required.)Painting the old prepared wall surface with two or more coats of approved Epoxy Coating of approved brand and colour to give an even shade with lamb wool roller/spray to give a required finish. Including scaffolding, etc. complete all as per manufacturer\"s specification and direction of deptt. |
| 11 | On Wall Surface |
| 12 | Providing and laying homogeneous flexible 2mm thick PVC ESD Conductive sheet/roll flooring conforming to Group P of Wear Resistance as per EN 649, Flammability class Bfl-s1 as per EN-13501-1, Slip Resisitance as per DIN 51130 group of R9, Colour Fastness rating > 6 as per ISO 105-B0, Thermal Resistance of 0.06 W/m.k as per EN 12664 with resistancelevel of1 x 10^6 to1 x 10^9 ohms suitable for Clean Room with load carring capacity of 750PSI confirming to BS 2050. Thejointsshall be welded bythermochordweldofapprovedmake/shade, including providing& laying (P/L) suitable copper strip (foil) grid of size 10\" x 10\" or less as recommended by manufacturer andwhich shall beconnectedto the existing earthingasper SCL\"s requirement. Work includes preparation of existing surface (includes removal of existing PVC flooring) with suitable self levelling compound as specified by the manufacturer so as to make the surface free fromanyundulations, fixing withconductiveadhesiveof approved make (Fevicol Floorfix VT or equivalent as per manufacturer\"s recommendation),rolling and sealing up the joints with fuse welding as recommended in the manufacturer\"s specification and direction of E-I-C. |
| 13 | Brick work with F.P.S bricks of class designation 7.5 in foundation and plinth in: |
| 14 | Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 15 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : |
| 16 | For fixed portion |
| 17 | Powder coated aluminium sections (minimum thickness of powder coating 50 micron) |
| 18 | For shutters of doors, windows & ventilators including providing and fixing SS hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket, brush beading etc. required (Fittings shall be paid for separately). |
| 19 | Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 20 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer-In-Charge. (Cost of aluminium snap beading shall be paid in basic item) |
| 21 | With float/froast glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm) |
| 22 | Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main \"T\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross \"T\" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main \"T\" at 600 mm center to center to form a grid of 1200x600mm and secondary cross \"T\" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \"T\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. |
| 23 | GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending. |
| 24 | Structural steel work riveted, bolted or welded in built up sections, trusses , framed work, stringer , treads and landing of staircases, railing , guard bar, gratings , gatesand similar work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 25 | 12mmcement plaster of mix : |
| 26 | 1:6 (1 cement: 6 coarse sand) |
| 27 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : |
| 28 | Two or more coats on new work over an under coat ofsuitable shade with ordinary paint of approved brand and manufacture |
| 29 | Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates, bolts, nuts, cutting rivets, welding etc. including dismembering and stacking within 50metres lead. |
| 30 | Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 metres lead. |
| 31 | Disposal of building rubbish / malba / similar unserviceable,dismantled or waste materials by mechanical means, including loading, transporting, unloading to the authorised Mohali Municipal Dumping Groundor as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved. |
| 32 | Impt Note: 1. Measurement for disposal shall be taken by measuring the size of the trolly. The net volume of the malba disposed shall be reduced by 20% for voids for making payment. |
| 33 | Electrical works |
| 34 | Supply ofsurface/recess mounted, Vertical TPN MCCB DB, double door, 24 Way(MCCB+ 72 MCB O/G Modules), 415V, 160A I/C , IP42/43 Metal door, MCCB DB, including incomer MCCB and outgoing MCBs, 200A rated copper busbar, confirming IEC 61439-1&3,including, Top and Bottom cable end boxes detailed as per attached technical specifications. Incomer MCCB of 160A25 kA - 1no.Outgoing : 72 way , populated withTP MCB (6A to 63A) and SP MCB (16A to 40A) detailed as per enclosed specificationMake of DB & Switchgear: Legrand/ Schneider /ABB / Siemens / L&T or their authorised system integrator as per the attached list.Note: Item includes supply of DB, Incomer & Outgoing switchgear, Top and Bottom cabling boxes along with associated accessories as required as per technical specification. |
| 35 | Installation, testing, commissioning and labelling ofsurface/recess mounted, Pre-fabricated, Vertical TPN MCCB DB, double door, 24 Way(MCCB+ 72 MCB O/G Modules), 415V,160A I/C , IP42/43 Metal door, MCCB DB, including incomer MCCB and outgoing MCB,s , 200A rated copper busbar, confirming IEC61439-1&3,including, Top and Bottom cable end boxes detailed as per attached technical specifications. Incomer MCCB of 160A25 kA - 1no.Outgoing : 72 way , populated withTP MCB (6A to 63A) and SP MCB (16A to 40A) as per the detailed as per enclosed specification. |
| 36 | Supply of pre-fabricated surface/ recess mounting, vertical type, 8 Way(MCCB+ 24 MCB O/G Modules), 415V, 100A I/C , IP42/43 Metal door, MCCB DB, including incomer MCCB and outgoing MCB,s, 200A rated tinned copper busbar, common neutral link, earth bar, din bar for mounting MCBs confirming to IEC61439-1&3,detailed as per attached technical specifications. Incomer MCCB of 100A25 kA - 1no.Outgoing : 24 way, populated withTP MCBand SP MCB) as per the enclosed specification.Make of DB & Switchgear: Legrand/ Schneider /ABB / Siemens / L&T. |
| 37 | Installation, testing , commissioning and labelling of pre-fabricated surface/ recess mounting, vertical type, 8 Way(MCCB+ 24 MCB O/G Modules), 415V, 100A I/C , IP42/43 Metal door, MCCB DB, including incomer MCCB and outgoing MCB,s, 200A rated tinned copper busbar, common neutral link, earth bar, din bar for mounting MCBs confirming to IEC61439-1&3,detailed as per attached technical specifications. Incomer MCCB of 100A25 kA - 1no.Outgoing : 24 way, populated withTP MCBand SP MCB. |
| 38 | Supply ofsurface/recess mounted, Pre-fabricated,TPN Horizontal DB , 415V,IP43 Double door,8- WayDB (32A FP RCBO asI/C+24 O/G Modules 6A B-curve MCB\"s) with suitable size comb type copper busbar, neutral bar, earth bar confirming to relevant IEC/IS standards as per detailed technical specification.Make of DB & Switchgear : Legrand/ Schneider /ABB / Siemens / L&T.Note: Item includes supply of DB, Incomer & Outgoing switchgear. |
| 39 | Installation, testing , commissioning and labelling of surface/recess mounted, Pre-fabricated,TPN Horizontal DB , 415V,IP43 Double door,8- WayDB (32A FP RCBO asI/C+24 O/G Modules 6A B-curve MCB\"s) with suitable size comb type copper busbar, neutral bar, earth bar confirming to relevant IEC/IS standards, as per detailed technical specification. |
| 40 | Supply of 3.5C x 120 Sq. mm Aluminium conductor, XLPE insulated, extruded inner PVC sheet, flat strip armoured and overall FRLS PVC outer sheathed1.1 KV grade cable (A2XFY), as per IS 7098 ( Part I) on existing cable tray /wall /surface/ as required.Make: Finolex/Havells/KEI/Polycab/RPG/CCI. |
| 41 | Laying of 3.5C x 120 Sq. mm Aluminium conductor, XLPE insulated, extruded inner PVC sheet, flat strip armoured and overall FRLS PVC outer sheathed1.1 KV grade cable (A2XFY), as per IS 7098 ( Part I) on existing cable tray /wall /surface/ as required.Note: Cable shall be laid on existing cable tray which is at an elevation of approx. 4-5 meter. |
| 42 | Supply of 4C x 25 Sq. mm stranded Copper , XLPE insulated, extruded inner PVC sheet, flat strip armoured and overall PVC outer sheathed1.1 KV grade cable (2XFY), as per IS 7098 ( Part I) on existing cable tray /wall /surface/ as required.Make: Finolex/Havells/KEI/Polycab/RPG/CCI. |
| 43 | Laying of 4C x 25 Sq. mm stranded Copper , XLPE insulated, extruded inner PVC sheet, flat strip armoured and overall PVC outer sheathed1.1 KV grade cable (2XFY), as per IS 7098 ( Part I) on existing cable tray /wall /surface/ as required.Note: Cable shall be laid in existing cable tray is at an elevation of approx. 4-5 meter. |
| 44 | Supply of indoor end termination with nickel coated brass double compression gland and Aluminium lugs for 3.5C x 120 Sq. mm size XLPEinsulated , PVC inner sheath, flat strip armoured and overall PVC outer sheathed Aluminium conductor cable of 1.1 KV grade as requiredMake: Dowells, 3M, Hex, Comet |
| 45 | Making indoor end termination with nickel coated brass double compression gland and Aluminium lugs for 3.5C x 120 Sq. mm size XLPEinsulated , PVC inner sheath, flat strip armoured and overall PVC outer sheathed Aluminium conductor cable of 1.1 KV grade as required. |
| 46 | Supply of indoor end termination with nickel coated brass double compression glandand Copper lugs for 4Cx25 sq.mm size of XLPEinsulated , PVC inner sheath, flat strip armoured and overall PVC outer sheathed copper conductor cable(28 mm) of 1.1 KV grade as requiredMake: Dowells, 3M, Hex, CometItem Code:401172295 |
| 47 | Making indoor end termination with nickel coated brass double compression glandand Copper lugs for 4Cx25 sq.mm size of XLPEinsulated , PVC inner sheath, flat strip armoured and overall PVC outer sheathed copper conductor cable(28 mm) of 1.1 KV grade as requiredItem Code: NA |
| 48 | Supply of following size, perforated, hot dipped galvanised Iron cable tray (Galvanisation not less than 50 microns) with perforation not more than 17.5 % in convenientsection, joined with connectors, with clamps of cable tray including supply of support materials such as unistrut, clamping rods, nuts, bolts, washersetc.and minor civil work as required. Make: CABLOFIL/OBO/L&T/Profab/Sintex or equivalent. |
| 49 | (a) 100mm(W) x 50 mm(D) x1.6 mm(T) |
| 50 | (a) 300mm(W) x 50 mm(D) x1.6 mm(T) |
| 51 | Installation of following size, perforated, hot dipped galvanised Iron cable tray (Galvanisation not less than 50 microns) with perforation not more than 17.5 % in convenientsection, joined with connectors, with clamps of cable tray including supply of support materials such as unistrut, clamping rods, nuts, bolts, washersetc.and minor civil work as required. |
| 52 | (a) 100mm(W) x 50 mm(D) x1.6 mm(T) |
| 53 | (a) 300mm(W) x 50 mm(D) x1.6 mm(T) |
| 54 | Supply of plug and socket DBs on ACP cladding, suitable for 32 Amps 415 volts ,3P+N+E (5 Pin) complete with FP RCBO (300mA, Type-A), neutral link and top plug as per IS 8623 and complete with connections, testing and commissioning etc. as required. Make : Siemens/Schneider/ABB/Legrand |
| 55 | Fixingof plug and socket DBs on ACP cladding, suitable for 32 Amps 415 volts ,3P+N+E (5 Pin) complete with FP RCBO (300mA, Type-A), neutral link and top plug as per IS 8623 and complete with connections, testing and commissioning etc. as required. |
| 56 | Supplying of 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.Make: Legrand, L & T, ABB, Anchor, Schneider/Siemens |
| 57 | Fixing of 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 58 | Supplying of following Size of ISI marked HGMS conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall/floor and making good the same in case of recessed conduit, including supply of necessary hardware suchnuts, bolts, washers, MS clamps, welding etc. , as required. |
| 59 | a) 20mm |
| 60 | b) 25mm |
| 61 | c) 32mm |
| 62 | Fixing of following Size of ISI marked HGMS conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall/floor and making good the same in case of recessed conduit, including supply of necessary hardware suchnuts, bolts, washers, MS clamps, welding etc. , as required. |
| 63 | a) 20mm |
| 64 | b) 25mm |
| 65 | c) 32mm |
| 66 | Supply of 450 x 150 x 75 mm (lxbxd) Galvanized Iron (GI) sheet conduit loop-in loop-out Junction box along with accessories in surface/recess including GI sheet cover,including supply of necessary hardware suchnuts, bolts, washers, MS clamps, welding etc.,as required. |
| 67 | Fixing of450 x 150 x 75 mm (lxbxd) Galvanized Iron (GI) sheet conduit loop-in loop-out Junction box along with accessories in surface/recess including GI sheet cover,including supply of necessary hardware suchnuts, bolts, washers, MS clamps, welding etc.,as required. |
| 68 | Supply of5 x 4.0 sq.mm (5 runs of 4.0sq.mm wire) FRLS PVC insulated copper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Make of wire : Finolex/Havells/KEI/Polycab/RPG/CCINote: Colour of wire Insulation shall be Red-Yellow-Blue for phase, black for neutral and yellow-green stripe for earth. |
| 69 | Drawing of5 x 4.0 sq.mm (5 runs of 4.0sq.mm wire) FRLS PVC insulated copper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Note: Item includes drawing of five runs of wire and installation of corresponding end ferrules. |
| 70 | Supply of3 x 4.0 sq.mm (3 runs of 4.0sq.mm wire) FRLS PVC insulated copper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Make of wire : Finolex/Havells/KEI/Polycab/RPG/CCINote: Colour of wire Insulation shall be Red-Yellow-Blue for phase, black for neutral and yellow-green stripe for earth. |
| 71 | Drawing of3 x 4.0 sq.mm (3 runs of 4.0sq.mm wire) FRLS PVC insulated copper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Note: Item includes drawing of three runs of wire and installation of corresponding end ferrules. |
| 72 | Supply of 3 x 2.5 sq.mm (3 runs of 2.5sq.mm wire)FRLS PVC insulated copper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Make of wire : Finolex/Havells/KEI/Polycab/RPG/CCINote: Colour of wire Insulation shall be Red-Yellow-Blue for phase, black for neutral and yellow-green stripe for earth. |
| 73 | Drawing of 3 x 2.5 sq.mm (3 runs of 2.5sq.mm wire)FRLS PVC insulated copper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Note: Item includes drawing of three runs of wire and installation of corresponding end ferrules. |
| 74 | Supply of 3 x 1.5 sq.mm (3 runs of 1.5sq.mm wire)FRLS PVC insulated copper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Make of wire : Finolex/Havells/KEI/Polycab/RPG/CCINote: Colour of wire Insulation shall be Red-Yellow-Blue for phase, black for neutral and yellow-green stripe for earth. |
| 75 | Drawing of 3 x 1.5 sq.mm (3 runs of 1.5sq.mm wire)FRLS PVC insulated copper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Note: Item includes drawing of three runs of wire and installation of corresponding end ferrules. |
| 76 | Supply of 1 x 16 sq.mm (1 run of 16 sq.mm wire)FRLS yellow-green PVC insulatedcopper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Make of wire : Finolex/Havells/KEI/Polycab/RPG/CCI |
| 77 | Drawing of 1 x 16 sq.mm (1 run of 16 sq.mm wire)FRLS yellow-green PVC insulatedcopper conductor, single core cable in the existing conduit/ raceway / Trunking conduit as required. Note: Item includes drawing of one run of wire and installation of corresponding ring terminals/end ferrules. |
| 78 | Supply of following size crimp type end sealing brass/copper ferrules with plastic sleeveMake: Reputed |
| 79 | a) 1 x 1.5 sq mm |
| 80 | b) 1 x 2.5 sq mm |
| 81 | c) 1 x 4.0 sq mm |
| 82 | d) 1 x 16 sq mm |
| 83 | e) 2 x 1.5 sq mm |
| 84 | f)2 x 2.5 sq mm |
| 85 | Supply of following size/ modules, GI box along with modular base & cover plate for modular switches in recess/wall etc. as required.Make: Legrand/ABB/L&T/Crabtree/Roma |
| 86 | a) 1 or 2Module (75mmX75mm) |
| 87 | b)6 Module (200mmX75mm) |
| 88 | c)8 Module (250mmX75mm) |
| 89 | Installation, testing and commissioning of following size/ modules, GI box along with modular base & cover plate for modular switches in recess/wall etc. as required.Make: Legrand/ABB/L&T/Crabtree/Roma |
| 90 | a) 1 or 2Module (75mmX75mm) |
| 91 | b)6 Module (200mmX75mm) |
| 92 | c)8 Module (250mmX75mm) |
| 93 | Supply of following size stainless steel Floor box conforming to EN60670-1 and EN60670-23 along with back box, 20A Switch, 6/16A 3 pin socket, modular base & cover plate for modular switches in floor slab including cable exit accessories etc. for smooth installtion complete as required. The finished installation shall have an ingress protection of IP66.Make: Legrand/ABB/L&T/Crabtree |
| 94 | a) 4 Module |
| 95 | Installation, testing and commissioning of following size Floor box conforming to EN60670-1 and EN60670-23 along with back box, 20A Switch, 6/16A 3 pin socket, modular base & cover plate for modular switches in floor slab including cable exit accessories etc. for smooth installtion complete as required. The finished installation shall have an ingress protection of IP66 or better. Minor civil work for grouting and making good the floor slab will be part of the scope. |
| 96 | a) 4 Module |
| 97 | Supply of following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. Make: Legrand/ABB/L&T/Crabtree/Roma |
| 98 | a) 5/6 amps switch |
| 99 | b) 3 pin 5/6 amp socket outlet |
| 100 | c)15/16 A switch |
| 101 | d) 6 pin 15/16 A socket outlet |
| 102 | Fixing of following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 103 | a) 5/6 amps switch |
| 104 | b) 3 pin 5/6 amp socket outlet |
| 105 | c)15/16 A switch |
| 106 | d) 6 pin 15/16 A socket outlet |
| 107 | Supply of Clean room LED light fixture, 600mm x 600mm, ceiling mounted, IP65, dust free, bottom opening, single phase, 80W Rated for 230V ac with operating voltage range of140V-270V AC, 50Hz, minimum 4000 lumens with minimum 100 lumens/watt, phosphochromate treated, powder coated CRCA / SS enclosure, high quality polycarbonate opal diffuser, Integral SELV Output electronicIsolated LED driver with Surge protection, output Short-circuitprotection, Ithd <10% & other Safety test as per IS 15885, certified minimum 50,000 lamp life hours L70, CRI 80, CCT 4800k, suitable for semi conductor fab clean rooms equivalent to LC20-102-XXX-57-G2 of Wipro make. The scope includes all the accessories like mounting frame,supports,etc. as required for smooth installation of the fixture in the clean room on existing/new ceiling grid as per site requirement. Make: Astra/Wipro/Signify/Phillips/Havells/LUG/Kenall/Terra Universal.Note: Party to provide technical documents for suitability of fixture in clean rooms. |
| 108 | Installation, testing & commissioning ofClean room LED light fixture, 600mm x 600mm, ceiling mounted, IP65, dust free, bottom opening, single phase, 80W, Rated for 230V ac with operating voltage range of140V-270V AC, 50Hz, minimum 4000 lumens with minimum 100 lumens/watt, phosphochromate treated, powder coated CRCA / SS enclosure, high quality polycarbonate opal diffuser, Integral SELV Output electronicIsolated LED driver with Surge protection, output Short-circuitprotection, Ithd <10% & other Safety test as per IS 15885, certified minimum 50,000 lamp life hours L70, CRI 80, CCT 4800k, suitable for semi conductor fab clean rooms. The scope includes all the accessories like mounting frame,supports,etc. as required for smooth installation of the fixture in the clean room on existing/new ceiling grid as per site requirement |
| 109 | Supply of GI Strip of 25x5mm size on wall/floor/recess including connection termination with GI nut, bolt, spring washer as required (Jointing shall be done by overlapping with 2 sets of brass nut bolt and spring washer spaced at 50mm) |
| 110 | Laying of GI Strip of 25x5mm size on wall/floor/recess including connection termination with GI nut, bolt, spring washer as required (Jointing shall be done by overlapping with 2 sets of brass nut bolt and spring washer spaced at 50mm) |
| 111 | Supply of Cu Strip of 20x3mm size on wall/floor/recess including connection termination with brass nut, bolt, spring washer as required (Jointing shall be done by overlapping with 2 sets of brass nut bolt and spring washer spaced at 50mm) |
| 112 | Laying of Cu Strip of 20x3mm size on wall/floor/recess including connection termination with brass nut, bolt, spring washer as required (Jointing shall be done by overlapping with 2 sets of brass nut bolt and spring washer spaced at 50mm) |
| 113 | Providing of 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ sub main wiring/ cable as required. |
| 114 | Fixing of 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ sub main wiring/ cable as required. |
| 115 | Supply of items for maintenance free earthing with UL listed 17.2mm copper bonded rod of length 3 mtrs with copper thickness of minimum 250 microns cadweld to 25 x 5 mm electrolytic copper strip with holes for connection to 16sqmm copper wire in concrete chamber conforming to IS:3043 with latest amendments including supply of corrosion inhibiting backfill compound providing inspection chamber complete as required.Make: OBO Bettermann/Furse/DEHN/Globetek/Axis Electricals |
| 116 | Installation testing and commissioning of maintenance free earthing with UL listed 17.2mm copper bonded rod of length 3 mtrs including boring of appropriate size hole, packing the hole with backfill compound and construction of earth inspection pit for connection conforming to IS:3043 with latest amendments. |
| 117 | Public Address (PA) system |
| 118 | Supply of24W, Ceiling mounted, speakerson the false ceiling at a height of 3 meter by making a speaker size cut out on ceiling and fixing the same by min 6 SWG wire to be clamped on existing MS purlin at about 2.2 mts from false ceiling similar to LBC 3099/41 model of Bosch.Make: Bosch/Honeywell/Ahuja or equivalent. |
| 119 | Installation, Testing and Commissioning of24W, Ceiling mounted, speakerson the false ceiling at a height of 3 meter by making a speaker size cut out on ceiling and fixing the same by min 6 SWG wire to be clamped on existing MS purlin at about 2.2 mts from false ceiling similar to LBC 3099/41 model of Bosch. |
| 120 | Supply of 2Cx1.5mm2 Copper, twisted pair , overall FRLS PVCouter sheath cable along with 25mm size, Rigid/flexible GI conduit for laying cable and making connection from junction box to the paging speaker on existing cable tray/surface/wall at a height of approx. 4-5 meter, detailed as per specifications and as required by EIC.Make: Finolex/Havells/KEI/RPG/ECKO/CCI |
| 121 | Installation of 2Cx1.5mm2 Copper, twisted pair , overall FRLS PVCouter sheath cable along with 25mm size, Rigid/flexible GI conduit for laying cable and making connection from junction box to the paging speaker on existing cable tray/surface/wall at a height of approx. 4-5 meter, detailed as per specifications and as required by EIC. |
| 122 | Analog Telephone |
| 123 | Supplying of krone type telephone tag block in steel sheet enclosure, IP 54 rated, with its accessories suitable for 20 pair telephone cable of dia 0.5 mm as incomer and suitable number of 1, 2 and 4 pair telephone cables at outgoing. Make: |
| 124 | Installation, Testing and Commissioning of krone type telephone tag block in steel sheet enclosure, IP 54 rated, with its accessories suitable for 20 pair telephone cable of dia 0.5 mm as incomer and suitable number of 1, 2 and 4 pair telephone cables at outgoing |
| 125 | Supply of 20 pair, 0.5 mm dia FRLS PVCinsulated annealed tinned copper conductor, colour coded twisted pairs, armoured telephone cable.Make: Havells, KEI, RPG, Polycab, lapp, Finolex. |
| 126 | Laying of 20 pair, 0.5 mm dia FRLS PVCinsulated annealed tinned copper conductor, colour coded twisted pairs, armoured telephone cable. |
| 127 | Supply of end termination for 20 pair, 0.5 mm dia, colour coded twisted pairs, armoured telephone cable with gland and lugs as required.Make: 3M, Dowell, hex, Hensel or equivalent. |
| 128 | Making of end termination for 20 pair, 0.5 mm dia, colour coded twisted pairs, armoured telephone cable with gland and lugs as required. |
| 129 | Supplying of 1 pair 0.5 mm dia FRLS PVCinsulated annealed tinned copper conductor, colour coded twisted pairs, unarmored telephone cable.Make: Havells, KEI, RPG, Polycab, lapp, Finolex |
| 130 | Drawing of 1 pair 0.5 mm dia FRLS PVCinsulated annealed tinned copper conductor, colour coded twisted pairs, unarmored telephone cable. |
| 131 | Supply of modular type Telephone Outlets ( RJ — 11 ) with shutter on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Make: L&T, Legrand, Siemens, Schneider, Hager, ABB. |
| 132 | Fixing modular type Telephone Outlets ( RJ — 11 ) with shutter on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 133 | FIRE DETECTION WORKS |
| 134 | Supply of Fire alarm active repeater panel (ZXr-A) , operated at 24V DC power with built in silence, mute, reset, accept, evacuate and test controls , for integrating with Morley IAS make ZXse/DX/Max control panels, including all necessary accessories/ drivers required for ready interface similar to part number 709-601-001of Morley IAS make, certified by applicable latestEN54 standards.Make: Morley IAS / Honeywell /System Sensor/Notifier |
| 135 | Installation testing and commissioning of Fire alarm active repeater panel (ZXr-A) , operated at 24V DC power with built in silence, mute, reset, accept, evacuate and test controls , for integrating with Morley IAS make ZXse/DX/Max control panels, including all necessary accessories/ drivers required for ready interface similar to part number 709-601-001of Morley IAS make, certified by applicable latestEN54 standards.Make: Morley IAS / Honeywell /System Sensor/Notifier |
| 136 | Supply of Addressable photo thermal Multi sensor Smoke Detector Ivory, with base, compatible for Morley IAS protocol, along withbase on ceiling / in the void between false ceiling, similar to HM-PTSE-AP.Make: Morley IAS / Apollo/ Honeywell /System Sensor/Notifier or equivalent. |
| 137 | Installation, testing and commissioning of Addressable photo thermal Multi sensor Smoke Detector Ivory, with base, compatible for Morley IAS protocol, along withbase on ceiling / in the void between false ceiling, similar to HM-PTSE-AP. |
| 138 | Supply ofAddressable, Flex Manual Call Point (MCP) without isolator along with flexible element and surface back box as required., compatible for Morley IAS protocol, similar to MI-MCP-FLEX model of Morley IAS make.Make: Morley IAS / Apollo/ Honeywell /System Sensor/Notifier or equivalent. |
| 139 | Installation, testing and commissioning ofAddressable, Flex Manual Call Point (MCP) without isolator along with flexible element and surface back box on the wall/Surface as required., compatible with Morley IAS protocol, similar to MI-MCP-FLEX model of Morley IAS make. |
| 140 | Supply of Addressable Intelligent Wall Mounted Sounder Strobe, Pure White Skirt Red Lens with built in isolation, compatible for Morley IAS protocol, similar to WSS-PR-I05 model of Morley IAS.Make: Morley IAS / Apollo/ Honeywell /System Sensor/Notifier or equivalent. |
| 141 | Installation, testing and commissioning of Addressable Intelligent Wall Mounted Sounder Strobe, Pure White Skirt Red Lens with built in isolation, compatible for Morley IAS protocol, similar to WSS-PR-I05 model of Morley IASfor installation on wall just below the ceiling/ any other suitable surface as per the requirement of EIC. |
| 142 | Supply ofaddressable type Intelligent Duct Smoke Detector complete with base, sampling tube suitable to operates in air speeds of 0.5m/s to 20m/s, built in transparent cover to view detector head LED and integrated test port suitable to operate on Morley IAS communication protocol on existing duct, certified by applicable latestEN54 standards. |
| 143 | Installation, testing and commissioning ofaddressable type Intelligent Duct Smoke Detector complete with base, sampling tube suitable to operate in air speeds of 0.5m/s to 20m/s, built in transparent cover to view detector head LED and integrated test port suitable to operate on Morley IAS communication protocol on existing duct, certified by applicable latestEN54 standards. |
| 144 | Supply of addressable, Morley IAS protocol, Input/ Output Module with base as required,similar to MI/D2ICMOE model of Morley IAS make, certified by applicable latestEN54 standards.Make: Morley IAS / Apollo/ Honeywell /System Sensor/Notifier or equivalent. |
| 145 | Installation testing and commissioning of addressable, Morley IAS protocol, Input/ Output Module with base on ceiling / in the void between false ceiling/ on existing structure/wall as required.Make: Morley IAS / Apollo/ Honeywell /System Sensor/Notifier or equivalent. |
| 146 | Supply of 2Cx1.5mm2 Copper, extruded PVC inner sheath, armoured and overall FRLS red/black color PVC outer sheathed1.1 KV grade cable , as per IS 7098(Part-1,bearing ISI certification.) detailed as per specifications and as required by EIC.Make: Finolex/Havells/KEI/RPG/ECKO/CCI |
| 147 | Laying of 2Cx1.5mm2 Copper, extruded PVC inner sheath, armoured and overall FRLS red/black color PVC outer sheathed1.1 KV grade cable, on existing cable tray/wall at a height of approx. 4-5 Mtr, detailed as per specifications and as required by EIC. |
| 148 | Supply of indoor end termination with brass/nickel coated, doublecompression gland and end insulated ferrule type copper lugs for 2Cx1.5mm2 Copper cable.Make: Dowells/ 3M/ Hex/ Comet. |
| 149 | Making indoor end termination with brass/nickel coated, doublecompression gland and end insulated ferrule type copper lugs for 2Cx1.5mm2 Copper cable in existing MS Box of installed above the false ceiling/ wall/ surface as required. |
| 150 | Supply of powder coated MS/Polycarbonate box, Size 4\"X4\" with ELMEX type terminal block for loop in loop out of 2C x1.5 sq. mm copper armoured cable and connection to the fire detector device, at ceiling/wall/surface/recess including wall cutting and providing necessary hardware for mounting /fixing,including all material for fixing as required.Make: Reputed |
| 151 | Installation of powder coated MS box, Size 4\"X4\" with ELMEX type terminal block for loop in loop out of 2C x1.5 sq. mm copper armoured cable and connection to the fire detector device, at ceiling/wall/surface/recess including wall cutting and providing necessary hardware for mounting /fixing,including all material for fixing as required. |
| 152 | GI duct for modification of Supply and return air Chutes, using 0.63 mm thickGI sheet, 120 gsm, complete with all the fittings |
| 153 | Nitrile rubber insulation , 19 mm thick,Al. foil backed,closed cell, Class ‘O’, density 50 kg/m3 (approx.) |
| 154 | Supply Air diffuser in Four way square construction with 450 mm x 450 mm neck size and suitable for 600 mm x 600 mm grid size and complete with volume control damper, removale core and fittings. |
| 155 | Return Air diffuser in Four way square construction with 450 mm x 450 mm neck size and suitable for 600 mm x 600 mm grid size and complete with removable core fittings. |
| 156 | Cutting and dismantling of GI duct to align the diffusers with the ceiling grid |
| 157 | Supply, Installation & Testing of sprinkler range pipe consisting of following as defined inscope of work mentioned below |
| 158 | Providing, laying, testing and commissioning of MS ‘C’ Class Pipe confirming to IS: 1239 Part 1 and ISI marked includingwelding, fittings like threadedelbow, tees and fixing the pipe with clamp / support frame and paintingwith one coat of primer and two coat of PO Red Enamel paint of following sizes. Make Jindal Star/ TATA |
| 159 | Size 50mm Ø |
| 160 | Size 32mm Ø |
| 161 | Size 25mm Ø |
| 162 | Providing and fixing, testing & commissioning of Sprinkler Head 68°C Pendant Type fast response with required Accessories(SS Rosette plate) Make Tyco/ viking, UL/ FM approved |
| 163 | Dismantling and Re-installation of sprinkler range pipe of MS ‘C’ Class. And stacking the sameoutside the building as per the directions of Engineer In Charge |
| 164 | Size 50mm Ø |
| 165 | Size 32mm Ø |
| 166 | Sprinkler Head Size-15mm |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy