| 1 | Disconnecting & taking out defective under ground LT cable from trenches, pole, pipe,floor ,wall etc including bricks ,GI pipes and removing from work site of unserviceable material all as specified and directed.(Excavation/earth work shall be measured & paid separately under relevant item of this schedule) |
| 2 | Supply, Laying,testing and connecting XLPE sheathed,PVC insulated screened PVC bedded,galvanised steel strip of wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volt grade of size 4.0 core 10 sqmm. , laid in trenches/surface of wall/in GI pipe along with pole for connection to OH lines,includingBrass Compression Cable Gland, Terminal Lugs,clamps,nut & bolts etc all as specified |
| 3 | All as per BOQ Item No 2.00 here-in-before but of size 4.0 core 16 sqmm. ,complete all as specified |
| 4 | All as per BOQ Item No 2.00 here-in-before but of size 3.5 core 25 sqmm. ,complete all as specified |
| 5 | All as per BOQ Item No 2.00 here-in-before but of size 3.5 core 50 sqmm. ,complete all as specified |
| 6 | All as per BOQ Item No 2.00 here-in-before but of size 3.5 core 70 sqmm. ,complete all as specified |
| 7 | All as per BOQ Item No 2.00 here-in-before but of size 3.5 core 95 sqmm. ,complete all as specified |
| 8 | Laying onlyand connecting XLPE sheathed,PVC insulated screened steel strip of wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volt grade of size 4 core 10 sqmm . , laid in trenches/surface of wall/in GI pipe along with pole for connection to OH lines,includingBrass Compression Cable Gland, Terminal Lugs,clamps,nut & bolts etc all as specified |
| 9 | All as per BOQ Item No 8.00 here-in-before but of size 4.0 core 16 sqmm. ,complete all as specified |
| 10 | All as per BOQ Item No 8.00 here-in-before but of size 3.5 core 25 sqmm. ,complete all as specified |
| 11 | All as per BOQ Item No 8.00 here-in-before but of size 3.5 core 50 sqmm. ,complete all as specified |
| 12 | All as per BOQ Item No 8.00 here-in-before but of size 3.5 core 70 sqmm. ,complete all as specified |
| 13 | Excavating in trenches , n.exc 1.5 m wide and n.exc 1.5 m depth for foundation etc or for shafts, wells, cesspits ,manhole pier hole, taking out and laying of cableetc n.exc 10 sqm on plan and n.exc 1.5m in depth and getting out in any kind of soilNote : Manual excavation to be done. During excavation if any damage occured to existing cable any type/ water pipe line, it will be contractor responsibilty to get it repair and make functional by providing jointing kit etc without any extra cost. Contractor has to repair it within 24 hrs so that essential service can not be effected due to such damage.If contractor fails to repair it within 24 hrs penalty @ Rs 500/- will be charged to contractor. In this GE decision will be final, conclusive and binding. |
| 14 | Returning, Filling in, including Spreading, Levelling, Watering and Well Ramming in Layers not exc. 250mm in Soft/Loose Soil, complete all as specified and as directed. |
| 15 | Removing excavated Materials (Soils) not exc. 50.00 mtr and depositing where directed at a level not exc. 1.50 mtr above the Starting Point in Soil, complete all as specified and as directed. |
| 16 | M&L Sand Cushioning (dry) in Trenches for protec-tion of UG Cables (below, above and around the UG Cable laid in Trenches) of 230mm Spread thick -ness and consolidated (punned) upto 180mm thickness, complete all as specified and as directed. (NOTE : For the purpose of Payment, Punned thick-ness of Sand Cushioning only shall be Measured and Paid ). |
| 17 | M&L for fly ash bricks locally availablelaid dry width wise across the line of cable in trenches for protection of UG cable, complete all as specified and as directed. |
| 18 | Supplying and fixingGalvanised mild steel pipe /tubing, light grade complete with all fittings of 80 mm bore dia, laid in trenches / under roads, fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers as in cable protection complete all as specified and directed. |
| 19 | Supplying and fixingGalvanised mild steel pipe /tubing, light grade complete with all fittings of 50 mm bore dia, laid in trenches / under roads, fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers as in cable protection complete all as specified and directed. |
| 20 | Supplying and fixingGalvanised mild steel pipe /tubing, light grade complete with all fittings of 100 mm bore dia, laid in trenches / under roads, fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers as in cable protection complete all as specified and directed. |
| 21 | M & L for Boring of horizontal hole under road, pavement, hardstandingsuitable for passing through up to 80 mm bore,complete all as specified.Note : (i) One run of boring of horizontal hole will be measured as one unitlength.(ii) All the precaution to be taken by the contractor before drilling the bore. The contractor has to take plan of existing cables any type and pipe line in existing area before drilling the bore.(iii) Any damage to existing cables any type and pipe line in the way of drilling the bore will be repaired and make good by the contractor. No extra cost will be paid on this account.(iv) Contractor has to get the survey of route, length and depth for boring before quoting the rate. |
| 22 | M&L for straight through joint (heat shrinkable) complete suitable for LT 1100 Volt aluminium conductor cable of size3.5/4 x 10-16 sqmm and testing after jointing of following sizes of cables. Note Payment will be released only after submission of PV anf test certificate |
| 23 | M&L for straight through joint (heat shrinkable) complete suitable for LT 1100 Volt aluminium conductor cable of size3.5/4 x 25-50 sqmm and testing after jointing of following sizes of cables,Note Payment will be released only after submission of PV anf test certificate |
| 24 | M&L for straight through joint (heat shrinkable) complete suitable for LT 1100 Volt aluminium conductor cable of size3.5 x 70-150 sqmm and testing after jointing of following sizes of cables.Note Payment will be released only after submission of PV anf test certificate |
| 25 | Supplying and fixingHigh density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 complete with all fittings of 25 mm bore dia, laid in trenches / under roads, fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers as in cable/earth strip protection complete all as specified and directed. |
| 26 | Supplying and fixingHigh density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 complete with all fittings of 40 mm bore dia, laid in trenches / under roads, fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers as in cable/earth strip protection complete all as specified and directed. |
| 27 | Supplying and fixingHigh density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 complete with all fittings of 50 mm bore dia, laid in trenches / under roads, fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers as in cable/earth strip protection complete all as specified and directed. |
| 28 | Supplying and fixingHigh density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 complete with all fittings of 100 mm bore dia, laid in trenches / under roads, fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers as in cable/earth strip protection complete all as specified and directed. |
| 29 | Material andlabour for earthing complete with Galvanised steel earth plate electrode 600x600x6 mmmm buried directly in ground (Earthpit not less than2.25m below ground level) with top edge of theplate not less than 1.5m below normal groundlevel, connected to GI strip 32x6 mmasearth lead by means of bolt, nuts, check nutsandwashers of galvanised iron or steel, upto 7.5mlength, earth strip protected by andincluding 40 mm diaGI pipe (light grade) andconnected to main test point or body of pole/pannel or lightening arrester of main controlling switch as directed including concrete pit in PCC(1:3:6)type C1 , Precast RCC(1:2:4)TypeB1 coverslab of size 54x54x5 cm reinforced with 8 mm dia TMT bars @ 100mm C/C bothwayswith onehandle for lifting made out of 10 mm dia TMT bar embedded in precast cover slab, funnel, wire mesh, 20 mm boreGI Pipe (Medium Grade) for watering, Charcoal andsalt in alternate layers of 15 cm (Compacted Thickness) around the earth electrode including necessary excavation, earth work in any typeof soil anddisposal of spoil to a distance n.exc50 m andnecessary testing complete all asshown in Electrical Plate No 3 of SSRPart-I.NOTE : 1. The unit rare includes for protectionh GI pipe of 40mm and watering pipe of 20mm bore including excavation for earth pit in any type of soil/disintegrate rock. 2. Contractor has to bring agriculture soil from outside of defence land and fill in earth pit to acheive desired result as the soil resisitivity is very high. 3. The cost of GI strip of 32x6mm including protection pipe,from top of earth plate upto 7.5 meter above/below ground level is deemed to be included in the unit rate. 4. All the joints in GI strip and connectgion with earth plate to be welded through brazing and in addition by providing double brass nut bolt and washer. 5.Costing of welding and nut bolts are deemed to be included in the unit rate |
| 30 | Dismantling existingLT panels of any type, any size carefully for reuse including necessary excavation demolition of concrete,disconnecting of earthing,cable, taking out burn out lugs,MCCBs,bus bars,insulators and other connected works ,surface levelling etc. andreinstall the LT panels after repair/replacement ofburn out lugs,MCCBs,bus bars,insulators, wiring etc including re-connection of earthing,cables with new foundation of panels,brick works,PCC works etc complete including testing all as specified and as directed by Engr-in-charge.(NOTE : Earth Work,brick works, foundation work, PCC, lugs, switch gear, metering devices, bus bar,insulators, cable for wiring etc will be Measured and Paidseparately under relevant Items as supply only). |
| 31 | Labour only for disconnecting, isolating and taking out burned/unserviceable lugs, switchgear, metering devices, wiring, bus bar etc from any type of pannel/board and replacing the same with new ones including testing completee al as directed by Engr-in-Charge. Note(i): New parts will be measured and paid separately under respective items as supply only.(ii). The item will not be operated simultaniously alongwith the item No 30.00 |
| 32 | Supply only the followings ( to be incorporated against Item No 30.00 and 31.00 only) |
| 33 | 06 sqmmto 16 sqmm |
| 34 | 25 sqmmto 50 sqmm |
| 35 | 70 sqmmto 95 sqmm |
| 36 | 120 sqmmto 240 sqmm |
| 37 | Epoxy type insulator upto 1100Volt for LT panel bus bar including nut bolts etc. complete all as specified and as directed. |
| 38 | Single core stranded Copper conductor FRLS of size 16 sqmm including copper lugs at both ends |
| 39 | Single core stranded Copper conductor FRLS of size 10 sqmm including copper lugs at both ends |
| 40 | Aluminium Busbars electrolytic grade of as per site required Amps and KA rating, bus barswith RYB & black colour coding including drilling , cutting and suitable size of galvanised or codmium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 41 | S&F of Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete including takig out the existing. |
| 42 | M & L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections includings nuts, bolts,washers, welding,bending cold or hot drilling holes for bolts, in any shape of size as indicated or directed and inclusive ofone primer coat, one under coat and one finishing coat of aluminium paint including preparation of surfaces complete all as specified and directed |
| 43 | M&L for cement concrete ( 1:3:6) type C-2 using 40mm graded crushed stone aggregate as in pole foundation, filling and mass concretecomplete all as specified |
| 44 | M&L for cement concrete ( 1:2:4) type B-1 using 20mm graded crushed stone aggregate as in coping of pole including weathering, slightly rounded or chamfered angles and throating, necessary formwork as directed complete all as specified |
| 45 | M/L brick work with flyash bricks old size straight or curved on plan to any radius exc 6m mean radius build in CM 1:6 complete all as specified and directed. |
| 46 | M&L for15mm thick in CM 1:4 rendering on brick or concrete surfaces finished fair and even on wall complete all as specified and directed. |
| 47 | M & L for Hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface as specified and directed. |
| 48 | M&L SS pasivated Screw Bolts (Machine Made) with Hexagonal Head at one End and screwed the other Ends, each screwed End to be fitted with Washers and One Hexagonal Nut, diameter of Shank 5 to 10mm Length of Bolt exc. 50mmcomplete all as specified and as directed. |
| 49 | M&Lfor preparation of existing surface of LT Panel by srapping down peeled off old paint, cleaning etc and applying Two coat of Siemens Grey Paint by using spray machine and Black paint on Angle Iron over a coat of red oxide primercomplete all as specified and directed by Engr in Charge. |
| 50 | Supply and Fix Metal cable route indicator of height 750 mmMS Flat of 40 mm x 4 mm with Circular 100 mm diameter MS Sheet of minimun thickness 3 mm duly engraved \" LT CABLE\" including Aluminium paint over it and to be fixed 150 mm below ground level with PCC (1:3:6) (40 mm aggregate) of size 250x250x300 mmall as directed by Engr-in-Charge. |
| 51 | Taking down/dismantling of unserviceable LT panels complete all as specified and directed by Engineer-in-Charge. |
| 52 | Supply & fixingLED flood light 60 watt (Min) 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, BIS approved silicon zel fitted potted driver with impact and corrosion resistant complete with driver and lamp, Aluminum die cast housing witg toughened glass secondary lenses High efficiency long life LED package in integral module with lumen efficacy of 120 lm/W (Min) , electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge protection & other reliability test as perlatest IS. LED operational voltage of 170 volts to 270 volts, frequency of 50 Hz,protection grade IP 66, IK-08 CRI greater than or equal to 70%, CW available CCT of 5700K/6500K, power factor of minimum 0.95 , life span of minimum 50000 working hours cincluding necessary electrical connections by PVC sheathed copper conductor wireof 3 core x 1.5 Sqmm and necessary fixing arrangement all as specified.Note : (i) The minimum requirement of lumen efficiency, lumen output and power consumption has been specified. However,as per availability, the bidders may opted higher specification with out any extra cost. The quoted rate is deem to be included for that and no extra payment will be made on this account.(ii) The fittings should be marked \"Date of installation\" and \"Date of Procurement\" with marker pen. |
| 53 | Supply,designing ,install, testing & commission 3 phase and neutral, 415 volts outdoor type, CPRI type tested having certification of IEC-61439 , factory made , dust and vermin proof, cubical type LT panel of size 1.20m x 0.45m x 1.20m, with canopy fabricated from 3.00 mm thick CRCA sheet for outer shell and 2 mm thick for non load bearing with angle iron frame of 50 x 50 x 6 mm, double door, front and back openable type, double door system, hinged opening, rubber lining, locking arrangement, with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade, protection class IP-66 fully compartmentalize design with 4 Nos of bus barmade ofaluminium, 400 Amps rated (electrical grade aluminium complying with the requirements of latest BIS, colour coded), busbar extensions for cable connections of electrolytic grade.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated pre-wired with suitable size of copper strip/copper wire with colour code for connecting out going MCCB/MCB\"s, including suitable aluminium earth strips conforming to IS with danger notice plate, necessary cable glands, cable connection with proper lugs, making electrical connection and circuit wiring for street light auto ON/OFF control timer by using desired electrical parametersPCC foundation and pedestal for fixing pillar feeder box/LT Panel with PCC 1:3:6, 15 cm thick in foundation, brick (Fly ash) / PCC block work in CM 1:6, rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grounting bolts etc for panel. The platform shall be of 450 mm height above ground level all as specified with supply and fixing the following accessories including taking out the existing one : |
| 54 | (A) IncomingMCCB200 Amps rating,FP ,415 V, AC, 50 HZ, adjustable thermal anf fixed magnetic settingIcs-100 % Icu , service breaking capacity 36 KA --- 01 Nos. (B) Outgoing(b) MCCB40 Amps rating,FP ,415 V, AC, 50 HZ, adjustable thermal anf fixed magnetic settingIcs-100 % Icu , service breaking capacity 16 KA --- 03 Nos.(c) MCCB25 Amps rating,FP ,415 V, AC, 50 HZ, adjustable thermal anf fixed magnetic settingIcs-100 % Icu , service breaking capacity 16 KA --- 05 Nos(d) MCCB16 Amps rating,FP ,415 V, AC, 50 HZ, adjustable thermal anf fixed magnetic settingIcs-100 % Icu , service breaking capacity 16 KA --- 03 Nos(e) Digital voltmeter 0-500 volt with selector switch -01 No (f) Digital amp meter 0-100 Amp with set of current transformer of suitable rating and selector switch -01 No (g) Indicator lamp (RYB) LED type - 01 set(h) Control MCB 2.0 Amps SP- 03. Nos |
| 55 | All as per BOQ Item No 57.00here-in-before but of size 1.00m x 0.45m x 1.00mwith the following incoming and outgoing accessories :-BUS BAR4 Nos of bus barmade ofaluminium, 250 Amps rated (electrical grade aluminium complying with the requirements of latest BIS, colour coded), busbar extensions for cable connections of electrolytic grade(A) IncomingMCCB125 Amps rating,FP ,415 V, AC, 50 HZ, adjustable thermal anf fixed magnetic settingIcs-100 % Icu , service breaking capacity 16 KA --- 01 Nos. (B) Outgoing(b) MCB25 Amps rating,TPN ,C series 10 KA ,- 04 Nos andMCB16 Amps rating,TPN , \"C\" series 10 KA- 04 Nos.(c) Digital voltmeter 0-500 volt with selector switch -01 No (d) Digital amp meter 0-100 Amp with set of current transformer of suitable rating and selector switch -01 No (e) Indicator lamp (RYB) LED type - 01 set(f) Control MCB 2.0 Amps SP- 03. Nos |
| 56 | All as per BOQ Item No 57.00here-in-before but but of size 1.20m x 0.45m x 1.20m with the following incoming and outgoing accessories :-BUS BAR4 Nos of bus barmade ofaluminium, 500 Amps rated (electrical grade aluminium complying with the requirements of latest BIS, colour coded), busbar extensions for cable connections of electrolytic grade(A) IncomingMCCB250 Amps rating,FP ,415 V, AC, 50 HZ, adjustable thermal anf fixed magnetic settingIcs-100 % Icu , service breaking capacity 36 KA --- 01 Nos. (B) Outgoing(b) MCCB63 Amps rating,FP ,415 V, AC, 50 HZ, adjustable thermal anf fixed magnetic settingIcs-100 % Icu , service breaking capacity 16 KA --- 02 Nos.(c) MCCB40 Amps rating,FP ,415 V, AC, 50 HZ, adjustable thermal anf fixed magnetic settingIcs-100 % Icu , service breaking capacity 16 KA --- 04 Nos(d) Astronomical Timer Switch 1 outlet 16 A-250V,vertical dial N/O contact,power supply 230V,50/60Hz,three position override switch \"ON-AUTO-OFF\" on front panel-01 Nos, 25A ,2 NOContactor 3 phase, with 230V coil-01 Nos, 32 A MCB TPN-01Nos with suitable relay and other accessoris .(e) Digital voltmeter 0-500 volt with selector switch -01 No (f) Digital amp meter 0-100 Amp with set of current transformer of suitable rating and selector switch -01 No (g) Indicator lamp (RYB) LED type - 01 set(h) Control MCB 2.0 Amps SP- 03. Nos |