| 1 | Supply and fixing ofCausewayMini Lighting Pole,Height-3000mm [Model K-Lite Pole-4335] / Equalent with necessarywires from fuse box to the fitting of 1.5 sqmm PVC insulated copper cable with necessary connection. The pole itselfjunction box 4 way terminal blocks with Hylum sheet with 1No. 6A SP MCB with 27W LED Warm white Light FITTING PRINCE ORNA MIDI [Model K-Lite light fixture-4984]/EqualentwithCRI <80, IP -54, Colour Temperature 3000Kconnection complete, testing and commissioning as directed by the departmental officers. [DATA-1] |
| 2 | Supply and fixing of 50W LED Flood light with integrated driver with PDC housing with IP66 protection, heat resistance tempered glass for protection with 5KV Surge protection on the existing angle iron frame work with PVC unsheathed leads with painting of suitable colour for focusing of approach road.[DATA-2] 9TFS 504-50-51-NL-SL-GL-NBKY |
| 3 | Supply and fixing of 13-20W CFLED Prince Orna RookModel K-Lite Pole-4535 [Model K-Lite Pole-4535] /Equalentwith 15W LED bulb necessary service wires from fuse box to the fitting of 1.5 sqmm PVC insulated copper cable with necessary connection. The inbuiltjunction box 4 way terminal blocks with Hylum sheet with 1No. 10A SP MCB (Higher end) with connections complete, testing and commissioning as directed by the departmental officers. [DATA-3] |
| 4 | Supply and fixing ofArchitectral surface spot LED light fitting ( In-Ground) with Wattage : 3W LEDAsymmetricalLuminaire, CRI <80, IP -67, Colour Temperature 3000K , Dimension: Ø88 x 117mm, ( Model:K-Lite-4093 )/ Equalent with necessary service wires from fuse box to the fitting of 1.5 sqmm PVC insulated copper cable with necessary connection. connection complete, testing and commissioning as directed by the departmental officers. [DATA-4] |
| 5 | Supply and providing cable end termination of 3-1/2x25 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete.(SD 213) |
| 6 | Supply and fixing of brass cable gland for 3½ x 25 sqmm PVC armoured LTUG cable with earth connection. [SD 164] |
| 7 | Supply and layingof 3 ½ x 25 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good.[SD 182] |
| 8 | Supply and clarnping of 3 ½ x 25sq.mm. PVC LTUG armoured cable on post or on wall with MS clamps. [SD 200] |
| 9 | Supply and Laying of 4 x 16 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good. (SD 658) |
| 10 | Supply and fixing of Fabricatedstreet light control panel ofsize not less than 3\" x 3\" x 1.5\" made out of16SWG CRCA sheet steel with lock and key arrangementsto be mounted on a suitable pillar boxwith following provisions : 1) Supply and fixing of 63A Four pole isolator in suitable sheet steel enclosure (Incomer). 2)Supply and fixing of digital weekly programmable timer switch with shortest switching time of 1 minute to turn on /off the lights. 3)Supply and fixing of 63A Four pole contactor4) Supply and fixing of Vertical type 8 way triple pole neutral MCB distribution boardin sheet steel enclosure double door type (Metal) with IP42 protectionwith 1 no. 63A 4 pole MCB isolator as incoming,6 Nos 32A 3pole MCB ,and 6 Nos 6-32ASP MCB as outgoingon suitable angle framework with earth connection complete. The MCBDB and MCB\"s should be Higher End make only. (DATA - 5) |
| 11 | Solar Plant:- Supply, Installation, Testing, Commissioning and Handing over of 3.27 Kwp Roof topSolar offround PV System Scheme complete as detailed below.Design, Engineering, Manufacturing, Procurement, Supply of materials to project site, project management, installation of mechanical equipment, cabling & appurtenances, instrumentation and electrical system and other equipment, as detailed in this section.Scope of the proposala)Solar Modules (Crystalline Silicon type mono perc half cut -as per MNRE specifications)b)Mounting Structure (Design to Maduariambient condition)c) Inverter, distribution boards, junction boxes, cablesd)Earthing for Solar modules and inverter.e) Lightning Protectionf) Installation and commissioning |
| 12 | TECHNICAL SPECIFICATIONS 1.SOLAR PV MODULES AND ARRAY SITC of off grid Solar PV Modules 3270WP of the crystalline silicon type- mono perc Half cut,Conforming to MNRE specification mounted on Aluminium frame(minimum thickness 35 mm) With minimum module efficiency of 20%, manufactured in India. As perlatest edition of IEC PV module qualification test or equivalent BIS standards Crystalline Silicon. Matching IEC 61215/IS14286and IEC 61730 Part-1 & Part 2 standards or equivalent BIS.With neccessary MC4 connectors (IP66) ,Interconnecting between panels using solar dc cable of min 4 sqmm and installation on exsisting structure .Solar crystalline modules of minimum 540 Wp (6 Nos) or above wattage With Protectivedevices against surges at the PV module.Along withLow voltage drop bypass diods . Solar Panels should be tested in the IEC authorized test centers. The rated output tolerance should be + 3 % . 10 years of product warranty 25 Years of linear power output warranty (90% of rated output at the end of 10years and 80% of rated output at the end of 25 years )• Makes- Havells, Power/Equalent |
| 13 | 2. MOUNTING STRUCTURESThe PV modules will be mounted on fixed metallic structures of adequate strength and appropriate design, which can withstand load of modules and high wind velocities up to 160 km per hour. The support Rails will be Hi-strength AluminumThe \"Mounting Structure\" should have the following features:The rails will be pasted in GI Roofing sheet using Spliced Metal chemical bonding paste with a Hi strength tested and durable till the life of the GI Roofing Sheet. |
| 14 | 3. INVERTER:SITC of MPPT Solar off Gridinverters having Capacity 3.7KvA/3KW Load output: 300WP(With IP65) with Canopy made of GI sheet of thickness 1.6 mm .BIS standard for efficiency measurements and environmental tests as per standard codes IEC 61683/IS 61683 and IEC 60068- 2(1,2,14,30) /Equivalent BIS Std.The charge controller (if any) / MPPT units environmental testing should qualify IEC 60068-2(1, 2, 14, 30)/Equivalent BIS Std. The junction boxes/ enclosures should be IP 65 (for outdoor)/ IP 54 (indoor) and as per IEC 529 specifications. The PCU/ inverters should be tested from the MNRE approved test centres / NABL /BIS /IEC accredited testing- calibration laboratories.Max. efficiency 98.80 %.European weighted efficiency 98.20 %THDi <3 % Manufacturing warranty-10years.There should be a provision of free energy monitoring for 25years through portal.Make :Havells, / Equalent |
| 15 | 5.Cables and accessoriesAll the cables shall be supplied conforming to IEC 60227/IS 694 & IEC60502/IS 1554 shall be of 1.1 kV grade as per requirement. Only PVC copper cables shall be used. The size of the cables between array interconnections, array to junction boxes, junction box to PCU, PCU to AC Distribution Box etc shall be so selected to keep the voltage drop and losses to the minimum. Permissible Wire Drop on DC side shall be <= 1% The bidder shall supply installation accessories, which are required to install and successfully commission the power plant. |
| 16 | 6.Earthing:-Earthing: The array structure of the PV yard shall be grounded properly using adequate number of earthing kits. All metal casing or shielding of the power plants shall be thoroughly grounded to ensure safety of the solar power plants.7.OPERATION AND MAINTENANCEMANUALAn Operation and Maintenance Manual, in English and Tamil, should be provided with the solar PV power plants.The following minimum details must be provided in the Manual:About Photo Voltaic &PV Module Clear instructions about mounting of PV module.About electronics used inDO\"s and DONT\"s,Clear instructions on regular maintenance and Trouble Shooting of the power plants.Name & address of the person or Centre to be contacted in case of failure or complaint.The equipment/materials and the whole system should be operated by trained personnel of the purchaser after giving training.The periodical maintenance, cleaning of the Solar Panels should be done by the firm/Supplier/Contractor for a period of five years. |
| 17 | 8.OFF Grid Solar PV Systemi)Solar PV Modulesii)Structure for mounting modulesiii)Drive iv)Cabling to PV module to drivev)Installation and Commissioning 9.WARRANTY (i)Solar panel at 90% efficiency - 10 years (ii) Solar panel at 80% efficiency - 25 years (iii) Inverter-10years 10. Battery Type C-10 umbular 12 V [200AH]-4Nos Warranty Havells/Exide/Amaron/EQualent WARRANTIES & GUARANTIEES:The goods supplied under this contract are new, unused, of the most recent or latest technology and incorporate all recent improvements in design and materials. This warrantee will also be covering the rectification of any and all defects in the design of equipment, materials and workmanship including spare parts for the guarantee period specified by MNRE/ TEDA from the date of commissioning. All the Guarantees / Warrantees of the different components will be transferred to Owner of the project. (Make :-Tata Power/Havells/Equalent |
| 18 | CCTV: Supply and installation of4MP high resolution IR Bullet Camera with 1/3\" Progressive scan CMO,HD video output,Day &Night IR Cut Filter,4MM (Angle of View 80degree)Lens,Low illumination,maximum 20fps,3D DNR & DWDR & BLC,IR range: up to 30m,Water and dust resistant (IP67) Make and Model:Hikvision or Dahua or equivalent [DATA-6] |
| 19 | Supply and installation of 10 / 100/1000Mbps 24 Port Gigabyte PoE Switch with 8 × Gigabit PoE ports, 2 × Gigabit fiber optical ports. Make and Model:Netgear or Cisco or D link or equivalent. [DATA-7] |
| 20 | Supply and installation of 6TB Hard Disc drive recording capacity NVRwith USB 3.0 connectivity.Make and Model:Western /seagate/ Equivalent .(M-2222) |
| 21 | Supply and run of UTP Cat6 unarmoured cable through existing pipe concealed in thewall/ceiling with necessary connection Make : Finolex or Dlink or equivalent.[DATA-8] |
| 22 | Supply and run of UTP Cat6 armoured cable through existing pipe concealed in thewall/ceiling with necessary connection Make : Finolex or Dlink or equivalent [DATA-9] |
| 23 | Supply and laying of ISI approved 25 mm PVC rigid pipe concealed on wall and ceiling with painting of suitable colour.Make : Finolex or Dlink or equivalent [DATA-10] |
| 24 | Supply and run of 1.50Sqmm Copper cable (Powercable) in existing PVC rigid pipe on wall and ceiling with painting of suitable colour with necessary electrical accessories. Make:Finolex or Orient or Polycab / Equalent [DATA-11] |
| 25 | Supply and erection, testing, commissioning uninterrupted power supply OFFLINE (Sinewave) Digital Inverter with copperwound Transformer of 1100VA with Input supply of230V, 50Hz AC supply with 150 AH Tubular Battery to work at full load capacity including transportation with following specification. 1) InputVoltage : 230, 50Hz single phase AC supply2) Output Voltage: 220V to 240V 50HZ AC supply3) Battery charging device of suitable rating4) Circuit board of suitable capacity5) Over load and short circuit protection 6) Visual Indication for ON/OFF / Trip / battery charging/mains failure/ Low Battery etc., 6) Mode setting for Bypass/Reset8) 12V 150AH fall tubalar battery - 1 No.7) Trolly for heavy UPS & Battery(Make : Exide / Microteck/Amron/Lumnious/Equivalent)[DATA-12] (CCTV &LAN) |
| 26 | Supply and installation 6U MS Rack for housingSwitches,Jack Panel with top and Bottom Cable Entry provision along with necessary power distribution unit,cable manager,fan and Lockable Toughened Glass Door. [DATA-13] |
| 27 | Supply and fixing of 65 mm (2½\") GI pipe (Class \"B\")of 6 mt. Length with300mm x 300mm x 6mm MS base plate, duly welded at the bottom with concreting with construction of Masonary pedestal with necessary clamps, on the above post withpainting of suitable colour. [DATA-14] |
| 28 | Earthing as per the ISI specification with an earth electrode of 2.10 metre Class\"B\" GI pipe of dia not lessthan 40mm with copper earth plate of size 125mmx50mmx6mm with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry.(SD-211) |
| 29 | Supply and Run of 1 of No.8 SWG copper wire for earth connection.(SD-370) |