| 1 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 2 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 3 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface /recessed conduit /submain wiring/ cable as required. |
| 4 | Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/Metal pipe as required. a) Upto 35 Sq.mm |
| 5 | b) Above 35 sq.mm and upto 95 sq.mm |
| 6 | Supplying and laying of 63 mm dia (OD-63 mm & ID-51 mm nominal) sizeDWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required |
| 7 | Supplying & installation of7 mtr longG I Octagonal Pole Fabricated Part as per Dimension :- Top Dia-70 mm , Bottom Dia-130 mm ( section Length -7000 mm) Thickness -3 mm Base Plate -220 mm X 220 mm X 12 mm , Foundation Bolt -M20mm X 700 mm x 4 nos \" J \" Type bolt including construction of RCC foundation base 1:3:6 ( 1 Cement : 3 coarse sand : 6Graded Stone) aggregate 40 MM Nominal Size ( minimum CC volume 0.66 cum, reinforcement weight 20 KG). MakeNezone /Utkarsh/Bajaj/CG ( Including accessories 6 AmpSp MCB [8536]curve& 8 way connector with suitable screws for connection of LED ) |
| 8 | Fixing of 45/150 watt LED flood fitting with 3 x 1.5 Sqmm (from looping box to LED fitting), PVC insulated & PVC sheathed multi core, copper conductor cable & making connection of LED flood light fitting etc. |
| 9 | Supplying and fixinglighting bracket made of 1.2 mtr long MS channel of size 75mmx40mm ( type SMC 75 ) welded with 80 mm dia, 30 cm long B class MS pipe and having suitable size holes at suitable places on the top of bracket for fixing 04 Nos 150 watt LED flood light, on GI octagonalpole etc. as required i/c primer and painting of bracket etc as required as per the direction of engineer in charge |
| 10 | Supplying & fixing ofGate light in aluminium die cast with modern artistic design and white PC diffuser suitable with LED lamp etc. as required including making connection etc. as requiredincluding connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc as required CROMPTON /PHILIPS/HAVELLS /WIPRO / BAJAJ |
| 11 | S/ITC of outdoor type feeder piller, Single door made out of 18 SWG CRCA sheet of size 450 mm x 300 mm x 300 mm deep having 160 amps, 04 nos insulated aluminium bus bars and to accommodate following accessories, front door openable & angle iron frame of size 450 mm x 300 mm with 600 mm long legs made out of 40 mm x 40 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, arrangement for incoming / outgoing cabling / cable termination, earthing, locking, interconnection etc. as required. |
| 12 | S/ITC of outdoor type feeder piller, double door made out of 16 SWG CRCA sheet of size 1600 mm x 1500 mm x 350 mm deep having 200 amps, 04 nos insulated aluminium bus bars and to accommodate following accessories, front & back door openable and P & F of internal connection with suitable size of cu wires,& angle iron frame of size 1600 mm x 350 mm with 600 mm long legs made out of 50 mm x 50 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, arrangement for incoming / outgoing cabling / cable termination, earthing, locking, interconnection etc. as required including providing and fixing following switch gears and accessories.(i) 100 Amps, 4 pole, 415 volts, 50 Hz SDFU make L&T code SK95570 = 02 No.(ii) 32 Amps, 4 pole, 415 volts, 50 Hz SDFU make L&T code L&T cat. No. SK95653 = 04 Nos(iii) 100 Amp change over switch disconnector type- C01-100 manual open executed make L& Tpart No.CO11000OOOO = 01 No(iv) MCB [8536] 10KAC Curve SP 32 Amp C curve, 240 V, 50 Hz make L&T BB10320C = 04 Nos(v) RYB LED indicator 415V make L&T=03 Nos |
| 13 | Add GST @ 18% on DSR 22 instead of 12% (Multification factior= 0.0633 on DSR item sr. no. 01 to 05 Rs 1213261) |