| 1 | Supply & Erection of Terminal Gantry structure of R.S. joist - 175x85mm 19.5Kg/Mtr. 6.1 meter above the ground and 2.15 mtr. below ground level 1:3:6 cement concrete foundation mounted on a stone pad of 300x300x75mm including earth excavation, back filling, making plinth of required fabricationcomplete in all respect as per direction of Engineer-Incharge. |
| 2 | Supply & Erection of Busbar Gantry structure of R.S. Joist 150x150mm 37kg/m 5.2 meter above ground level and 1.20 meter below in 1:3:6 cement concrete foundation mounted on a stone pad of 200x200x75mm including earth excavation, back filling, making plinth of required fabrication complete in all respects as per direction of Engineer-Incharge. |
| 3 | Supply & Erectionof 33 KV Line Isolator/Busbar Isolator structure made of 125x65mm 13.10Kg/Mtr. Channel at a height of 2.8 mtr. Above ground and 1 meter below ground on a cement concrete pad of 75mm thick with 1:3:6 cement concrete foundation including excavation, back filling, making plinth of required height & with required fabrication for bracing of M.S. flat 50x6mm2.4kg/Mtr. and top of M.S. angle 75x75x8mm 8.9 Kg/Mtr. as per direction of the Engineer-Incharge. |
| 4 | Supply & Erection of 33 KV lighting arrestors/post Insulator /C.T. structure made ofM.S. channel 100x50mm9.56kg/mtr. Top of M.S. angle 50x50x6mm 4.5 Kg./mtr. Lighting arrestors/post Insulator are to be mounted on M.S. plate of 200x150x8mm Height of structure as to be 2.8 Mtr. above ground and 1 Mtr. below ground on a 75mm thick cement concrete pad with 1:4:8 cement concrete foundation, making plinth of required height including all fabrication as per direction of Engineer-Incharge. |
| 5 | Supply & Fixing of 33 KV pin insulator with pin on main Terminal Gantry as per direction ofEngineer-Incharge. |
| 6 | Supply & Fixing of 11 KV Disc Insulator 12000 Kg. E/M Strength complete in all respects as per direction ofEngineer-Incharge. |
| 7 | Supply & Fixing of 33 KV tension fitting for panther conductor with D-shackle (B & S type) suitable for 12000kg mechanical strength disc insulator set complete in all respects as per direction ofEngineer-Incharge. |
| 8 | Supply & Erection of Main Bus bar on bus bar gantry with ACSRDeer & panther conductor including laying, stringing & binding etc. as per UP PWD SOR2018 S.No. No 627 |
| 9 | Supply & Fixing of P.G clamps suitable forpanther conductor for jumpering as per direction ofEngineer-Incharge. |
| 10 | Supply & Fixing of Earth mat in the switch yard of the sub station for all Electrical Equipments and structure by laying of M.S rod of 32mm dia in 750mm deep trenches and earth electrode 3.0M long of M.S round bar 32mm dia 0.5M below ground level. The work includes bending/flooring of M.S. round bar and connection of all steel structure in switch yard with earth mat by means of M.S strip of size 50x6mm including all labour, materials T & P etc. required for proper completion of the work as per detailed specification of UPPCL. |
| 11 | Supply & Making suitable earthing of outdoor/indoor structure, Equipments through the earth mat laid in switch yard by means of 50x6mm M.S. strips including all labour, material, T & P etc., required for proper completion of workas per direction ofEngineer-Incharge. |
| 12 | Supply & fixing of 33 KV bustype Isolator with all necessary material required for proper fixing of structure includinglabour, material, T & P etc. required for proper completion of the work as per direction ofEngineer-Incharge. |
| 13 | Supply & Fixing of 33 KV line isolator of approved quality and make with all necessary material required for proper fixing on structure includinglabour, material, T & P etc. required for proper completion of the work as per direction ofEngineer-Incharge. |
| 14 | Supply & Fixing of 33 KV lighting arrestor (03 Nos.) of approved quality and make with all necessary material required for proper fixing on structureincludingmaterial, labour,T & P etc.for proper completion of the work as per direction ofEngineer-Incharge. |
| 15 | Supply & Fixingof 33 KV C.T of approved quality and make with all necessary material required for proper fixing on structure including material, labour, T & P etc.for proper completion of the work as per direction ofEngineer-Incharge. |
| 16 | 33KV CT 400/200/1A |
| 17 | 33KV CT 200/100/1A |
| 18 | Supply, Installation, Testing & Commissioning with loading &unloadingof10 MVA33/11 KV, 3 Phase 50 HzVector Group Dyn 11, ON AN Cooled, Copper wound (Outdoor Type) Step Down Power Transformer with Off Circuit Tap changer having tappings (+5%) to (-15%) in step of 2.5 % complete with first filling of ISI Marked Transformer and all other fittings/accessories as per IS: 2026 and latest specification of MVVNL.(Make: TRANSTRON/MODERN /ELECON or Whose Latest GTPApproved in MVVNL having valid CPRI/ERDA Type Test Report) |
| 19 | Construction of Power Transformer Plinth of Size 3.50 x 3.50 x 1 Mtr. and the top of Plinth 30 cm R.C.C. Work 1:2:4 with fixing of 02 Nos. Rail l.b. complete in all respect with required all material such as steel bar, brick, coarse sand, cement, labour and T&P etcfor proper completion of the work as per specification of M.V.V.N.L. |
| 20 | Supply, Installation, tesing and commissioning of INDOOR TYPE11KV, HT VCB 1250Amp 25KA rms-3sec panel with SCADA Campatibility Board having 2 Nos. Incomers, 1 No. Bus-coupler and 9 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 11KV, 1250Amp, 25kA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 110V DC. The Board shall consist of following panels : |
| 21 | 11KV INCOMER VCB PANEL : |
| 22 | 11KV, 1250Amp, 25KA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit Breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (110V DC) |
| 23 | Current Transformers :1 set of 3 Nos. Single Phase, 11KV, 800/400/5+5+PS Class, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2) |
| 24 | Potential Transformers : 1 set of 3 Nos. Draw-out Type Feeder Connected PTs having ratio 11KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protection |
| 25 | Accessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device |
| 26 | Indications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC Healthy |
| 27 | Metering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make |
| 28 | Protection & Auxiliary Relays : |
| 29 | 1 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing Over Current (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%), Earth Fault (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%). |
| 30 | 1 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (45% - 90% in steps of 1%), No Voltage Protection (3% - 20% in steps of 1V). |
| 31 | 1 No. Trip Circuit Supervision Relay |
| 32 | 1 No. High Speed Master Trip Relay |
| 33 | Additional Accessories and Features : |
| 34 | Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of supplies |
| 35 | Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 110V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. Make:- ABB/Schneider/Siemens |
| 36 | 11KV OUTGOING VCB PANEL : |
| 37 | Same description as INCOMER PANEL above except following changes : |
| 38 | Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing Panels |
| 39 | Current Transformers : 1 set of 3 Nos. Single Phase, 11KV, 200/100/1+1, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA. Make:- ABB/Schneider/Siemens |
| 40 | 11KV BUS-COUPLER VCB PANEL : |
| 41 | Same description as INCOMER PANEL above except following changes : |
| 42 | Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary RelaysMake:- ABB/Schneider/Siemens |
| 43 | Supply/Installation, testing & commissioning of 11 KV Outdoor APFC pannel 12.65KV, 3960KVAr, 3- phase, 50 C/s housed in indoor type CRCA panel, capacitor bank having two variable steps of 1188 KVAR.and two variable steps 792 KVAR Aluminium busbars, Epoxy insulators, HT HRC fuse, Surge Suppressor etc. with details are follows-(10 11 KV, aluminium wound, Dry type series reactors a) 1188 KVAR, 11KV 0.2% for 1188 KVAR step-6 Nos., b) 0.792KVAr for 1188 KVAr 0.2% for 792 KVAR step-6 Nos., (2) 11 KV, 3- Phase dry type RVT-1 No. (3) 12 KV 3 Phase indoor type metal enclosed vacuum contactor-12 Nos. (4) Indoor type automatic PFcorrector unit-1 No. (5) IP 42, Indoor CRCA cubicle panel for accommodating capacitors,series reactor, Vacuum contactor, surge suppressor etc. -1set. Make:- ABB/Schneider/Siemens |
| 44 | 9 KV,10 KA, Class lll surse arrestor |
| 45 | Control cables, lungs/thimble, Junction Box etc. |
| 46 | 11 KV 3 core al, XLPE Insulated 3x300 mm sq. Cable |
| 47 | 11 KV XLPE cable (3x300sq.mm) heat shrinkable jointing kit indoor. |
| 48 | 11 KV VCB Switchgear for capacitor bank with complete arangement Adddisnal pannel for connetion with existing 11 KV bus bar. |
| 49 | Casting of civil foundation. |
| 50 | Cable trench for laying of power/control cables. |
| 51 | Earthing for panel by Chemical pipe earthing. |
| 52 | Supply and fixing of Run through clamp for L.A./P.I. as per direction of Engineer in charge. |
| 53 | S/F of 200Amp./ 415volt Havy Duty bouble break complete with HRC fuse and 200A 4way Al Bus Bar on angle iron frame complete in all respect as per direction of Engineer in charge. |
| 54 | S/F of 32Amp. 415V. Metal clad TPN rewireable type switch fuse unit on angle iron bracket complete in all respects. as per PWD SOR 2018 SI No. 315 Cat.B |
| 55 | Providing necessary T&P and furniture for maintenance staff as per Item Given below. |
| 56 | 12 mm thick Rubber mat of size 2x 1 m PWD S.O.R. 2018 S.No. 1136 Nos. 4 |
| 57 | Brass Earth chain Nos. 2 |
| 58 | Rubber hand gloves tested on 1100V. Pair 4 |
| 59 | Maximum load/ minimum load tripping board complete with all necessary equipments. No. 1 |
| 60 | Single line diagram with board complete. No. 1 |
| 61 | Notice board. No. 1 |
| 62 | Wall clock No. 1 |
| 63 | First aid boxNo. 1 |
| 64 | Sign. board of S/S with stand. No. 1 |
| 65 | Key board No. 1 |
| 66 | Table with drawer & sunmica Armed chair No. 1 |
| 67 | Armed chair No. 6 |
| 68 | Rack No. 2 |
| 69 | Bench No. 2 |
| 70 | Making fire fighting arrangements in the control room building as per Item Given below. |
| 71 | Cost of Fire extinguisher 4.5 kg capacitycomplete with stand No. 4 |
| 72 | Cost of Fire bucket completeNo. 6 |
| 73 | Cost of Fire bucket stand for 6 Nos. bucket made of M.S. Angle 45x45x6mm. No. 1 |
| 74 | Supply & Laying of following sizeArmoured control cable. Make Polycab/Gloster/Havells/Universal/KEI/Finolex |
| 75 | 4x2.5 Sqmm |
| 76 | 6x2.5 Sqmm |
| 77 | Supply, Installation, Testing & Commissioning of 24V, 20A Trickle cum Boost Battery Charger suitable for 24V 70AH Battery Bank and also to feed 5A Power to External Load such as Emergency Light etc.70AH, 30V Battery Bank SMF batteries with Mounting Rack & along with connecting Leads and other associated accessories. The Charger shall be suitable to operate Emergency Light Load along with 33kV HT VCB Closing / Opening and also 11kV VCB Closing & Opening. |
| 78 | Supply & Filling of Local Earth (including royality) by mechanical transport from outside of scheme from 8 km also including ramming & Watering of the earth in layers not exceeding 20cm to required levels and slopes complete as per direction of E/I. |
| 79 | Construction of control cable trench of required size 0.30x0.45 Mtr. M-15 class brick work including plastering etc. and covered with R.C.C. slab (0.50x0.60M) size complete with all material, labour and T&P etc. required for proper completion of work as per direction of E/I. |
| 80 | Supply & Filling of 20mm stone grit in yard100mm thick complete in all respects as per direction of E/I. |
| 81 | Supply & Laying of following type high conductivity aluminium strand compacted circular conductor XLP (E) armoured 11KV cable neutral earthed system confirming to IS 7098-Part-II(1985) with latest ammendment at a depth of 1 Mtr. Below ground level over a cushion of 75mm thick sand around and protect with brick on sides and top of cable shall be properly connecting with the earth conductor by clamps etc. with the cost of all material, labour, T&P etc. required for proper completion of the work. Make Polycab /Gloster/Havells/Universal /KEI /Finolex |
| 82 | 70 Sqmm 3 Core as per PWD SOR 2018 S.No.506 (d) |
| 83 | 400 Sqmm 3 core |
| 84 | Supply & Jointing of following sizes 11KV 3Core Indoor/out door type (Heat shrinkable) Jointing KitComplete in all respects.Make:- Raychem/3M/Densons |
| 85 | Indoor type 70 Sqmm As per DSR 2022 SI no. 10.4.1 |
| 86 | Outdoor type 70 Sqmm As per DSR 2018 SI no. 10.5.1 |
| 87 | Indoor type 300-400 Sqmm As per DSR 2022 SI no. 10.4.4 |
| 88 | Outdoor type 300-400 Sqmm As per DSR 2018 SI no. 10.5.4 |
| 89 | Supply and Erection of cable stand of size 3.00x0.50m above G.L. duly grouted with cement concrete upto 50 cm. depth for laying cables made of angle iron size (65x65x6mm) having welded M.S. flat of size 50x6mm on top middle, and 45mm above ground level for fixing cable by clamping with M.S. flat of 40x4mm size as per direction of E/I. |
| 90 | Supply,Installation, Testing and Commissioning of 33 KV 1250 A 31.5KA/3Secoutdoor type Vacuum Circuit Breaker including loading, unloading, carriage & erection of the same of plinth with required channels, nut & boltsmaking all necessary connectionetc. as per direction of E/I.Make:- ABB/Schneider/Siemens |
| 91 | Construction of 33 KV VCB plinth of size 2.25x2.25Mtr. with all material, labour and T&P required for proper completion of the work as per direction of E/I. |
| 92 | SI.T.C of protection cum control pannel SCADA compatibility INC 33/11 KV 10MVA Double CKT. T/F with Installation, Testing & Commissioning etc. complete in all respects as per directionof E/I. |
| 93 | S.I.T.C of protection cum control pannel SCADA compatibility INC 33 KV line feeder double ckt.complete with Installation, Testing & Commissioning ,etc. complete in all respects as per direction of E/I. |
| 94 | Supply and Erection of Double Pole Structure made of following types of support duly grouted in 1:4:8 cement concrete (1 cement, 4 coarse sand and 8 grit of 20mm nominal size plinthed plastered & painted in the same manner as already specified for respective supports suitable for Pole mounted type substation with different types of M.S. Channel and angle iron duly fabricated for disc fittings D.O. fuse set, TPMO ladder stand projecting outside dropper and bracings, including cost of all material, labour and T & P required for proper completion of work as per direction of E/I. (Make:- Manufacturers Whose Latest G.T.P. Approved in MVVNL) |
| 95 | With 11 Mts. long 410 SP 55 S.T. Pole |
| 96 | Supply and Erection of 11 KV TPMO set complete in all respects as per direction of E/I. |
| 97 | Supply and Erection of 11 KVD.O. fuse set complete in all respects. as per direction of E/I. |
| 98 | Supply and fixing of H.T./L.T. jumpering and connections on double pole/four pole, lightning arrestor and transformer. The rates include the cost of all materials, labour and T & P etc. required for proper completion work as per direction of E/I. |
| 99 | Supply Installation, Testing and Commissioning with loading & unloading of 63 KVA, 11/0.433 KV \"Energy Efficient (Level-1)\" Aluminium wound, Outdoor Delta-Star Distribution Transformer as per BIS 1180-2014 Standards and latest specification of MVVNL.(Make: TRANSTRON/MODERN/ELECON or Whose Latest GTPApproved in MVVNL having valid CPRI/ERDA Type Test Report) |
| 100 | Supply & Fixing of lighting arrestor set (3 Nos.) suitable for mounting on steel supports complete with all materials, labour and T & P required of proper completion of work as per direction of E/I. |
| 101 | Supply & Fixing of following Size GIpipe \"B\" class for cable duly clamped with supports by 3 nos. with clamps of 20x3mm M.S. flat bolts nuts & washers required for proper completion of work. Make:- JINDAL/TATA/SAIL |
| 102 | 100 mm Dia |
| 103 | Supply & Laying of following SizeGIpipe \"B\" class for cable complete in all respect as per direction of E/I. Make:- JINDAL/TATA/SAIL |
| 104 | 150 mm Dia |
| 105 | Supply & Laying of Al. conductor PVC insulated armoured served sheathed cables 1100V grade at a depth of 750mm below GL over a cushion of 75mm thick sand all around & protected with burnt bricks on sides andon top. On surface the cable run shall be fixed on M.S clamps etc. of suitable size or as directed by the Engineer- Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.Make Polycab /Gloster/Havells/Universal /KEI /Finolex |
| 106 | 10 sqmm4 core as per PWD SOR-2018 SI No. 501(h) |
| 107 | 16 sqmm 4 core as per PWD SOR-2018 SI No. 501(i) |
| 108 | 50 Sqmm 3.5 core as per PWD SOR-2018 SI No. 501(l) |
| 109 | Supply and fixing of plain or pin type copper tin plated cable socket (lugs) to the cable leads, insulating with tape and making connection etc. complete in all respects. |
| 110 | 10 Sqmm as per PWD SOR-2018 SI No. 501(c ) |
| 111 | 16 Sqmm as per PWD SOR-2018 SI No. 501(d) |
| 112 | 25 Sqmm as per PWD SOR-2018 SI No. 501(e) |
| 113 | 50 Sqmm as per PWD SOR-2018 SI No. 501(g) |
| 114 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc.. Complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of E/I. |
| 115 | 10 Sqmm 4 core As per PWD SOR 2018 SI no. 503 (h) |
| 116 | 16 Sqmm 4 core As per PWD SOR 2018 SI no. 503 (i) |
| 117 | 50 Sqmm 3½ core As per PWD SOR 2018 SI no. 503 (l) |
| 118 | Supply & fixing of 7mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thick) having 3mm thickness with Single arm bracket (1Mtr length) onRCC foundation including the cost of 4 way connector with bakelite sheet fixed in G I Pole ,foundation, foundation bolts, excavation & back filling and Required T&P complete in all respect. as per PWD SOR 2018 SI No-641 Make:- BAJAJ/VALLMONT/RRISPAT CONSOUL |
| 119 | Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser/Reflector with 1.0 Sqmm 3 core multistand copper unarmored cable suitable lenght and 1 no 6 Amp SPMCB Complete driver set suitable for 30 to 40 watt. Confirming to IP 65 Protection Including Street light Bracket (60 cm long) with pole cap suitable for Street light Fittings complete in all respect as per PWD SOR 2018 SI No-1420 CAT-AAA Make:- Havells/Polycab/Philips/Jaquar |
| 120 | Supply and Burring of Safe Earthing Electrode T-39 Zn-Zinc Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 S.No. 726 (D) |
| 121 | Supply and Burring of Safe Earthing Electrode T-39 Cu Copper Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 S.No. 727 (D) |
| 122 | Supply & Erection of 11 KV Section Double pole structure (Riser)Bottom Portion Galvanised made of following types of supports duly grouted 1:4:8(1 cement, 4 coarse sand and 8 brick blast 40 mm size Plinthed plastered and painted in the same manner as already specified for respective supports with Two nos. channels of size 100x50mm, Two no. 75x40 mm, in help of 75x10mm, MS Clamp and 65x65x6 mm angle iron bracing 3 no. Pin Insulator, etc. complete with all material and T&P etc. required for proper completion of work. (Make:- Manufacturers Whose Latest G.T.P. Approved in MVVNL) |
| 123 | Double Pole S.T. Pole SP-55, 11.00 M. Long |
| 124 | Making suitable earth of GI pole with 2.5 Mts. long 20mm M.S rod connected with 7/16 SWGG.S. wire duly clamped & binded on pole including the cost of materials, labour and T & P required for proper completion of work as per direction of E/I. |
| 125 | Supply of following Size 11 KV Standered Compacted Aluminium Conductor Screen with Extruded Semi conducting compound, XLPE Insulated, insulation screening with Extruded Semi conducting compoundin combination with Copper Tape, Cores laid up, innersheath of PVC, Galvanised steel strip Armoured & overall PVC sheathed cable confirming to IS 7098 ( Part-2) 2011 with up to date ammendments forproper completion work.Make Polycab /Gloster/Havells/Universal /KEI /Finolex |
| 126 | 300 Sqmm 3 core |
| 127 | Supply of HDPE pipe upto PN-6 working pressure Rating material Grade PE-80 Nominal dia (OD) 160 mm 9.50 mm thicknesscomplete in all respect as per relevants I.S. Technicals specification. |
| 128 | Drilling of Road Parallely & Road Crossing at a depth of 2 to 3 Mtr. as required & laying charges of cable & 160mm Dia HDPE Pipe complete with all material, labour, Drilling machine & required T&P etc. required for proper completion of work as per Direction of E/I. |
| 129 | Supply and laying of 32mm x6 mm G.I strip Compete as per PWD SOR-2018 S.No. 717 |
| 130 | Supply and laying of 32mm x6 mm Copper strip Complete as per PWD SOR-2018 S.No. 720 |
| 131 | Supply & Fabrication of 8 SWG G.I. Wire mesh Security fencing by providingvertical supports of 50 x 50 x 6mm long including cutting bending at top at a distance of 0.60 Mtr. Including welding, cutting and Bending atbottom at a distance of 0.15 Mtr. Drilling of 04 Nos. Holes of 6mm Dia on Top for Holding the Barbed Wire at a distance of 125 mm hole to hole and 7 Hole in vertical position of 10mm Dia at a distance of 280mm hole to hole for riveting the chain link mesh of size 2\" x 1\" and MS Flat 50 x 6mm& 25x3mm and fixing the vertical support in plumb including brick work in repair wall with supply of all material, labour, T&P etc. required for proper completion of the workas per MVVNL Specification |
| 132 | Construction of security Fencing plinth size (30 x 14M) of required size M-150 class Brick including plastering etc. and 4.5m x 3.0m size material, labour and T&P etc. required for proper completion of the work |
| 133 | Supply & Fixing of 1200 mm Sweep of CeilingFans with Fan Motorof A.C. Permanentinsulation capacitor rating confirming BEE 5 Star rating and IS: 374/79 and also comply with IS:1709/1984 with Latest ammendment. The rated voltage 220/240 Volts, 50 Hz, I-ph AC the fan assemble should consists of down rod blades, shackle canopies etc. and double ball bearing system. complete in all respectMake Havells/ Bajaj/ Crompton |
| 134 | Supply & Fixng of 300 mm Sweep Heavy Duty 950 RPM 230 Volt single Phase Exhaust Fan. Complete in all respect Make Havells/ Bajaj/ Crompton |
| 135 | Supply & Fixng of 450 mm Sweep Heavy Duty 950 RPM 230 Volt single Phase Exhaust Fan. Complete in all respect Make Havells/ Bajaj/ Crompton |
| 136 | Supply & Fixing of 16 SWG M.S Drum with Livers duly painted including making hole in the wall for exhaust fan and finishing properly complete in all respect as per PWD SOR 2018 SI No. 1122 (A) |
| 137 | Supply & Fixing of Shock Treatment Chart (Prescribed Under I.E. Rules) duly framed with glass and supported from back with hard board or soft board with supply of all material, labour, T&P for proper completion of work Complete in all respect. as per PWD SOR 2018SI No. 1134 |
| 138 | Supply & Fixing of Recess/ Surface/ Pendent Mounting Round 10 to 15 Watt L.E.D. Down lighter having powder coated Die cast Aluminium Housing with Heat Sink, Diffuser/ Reflector and Driver set complete in all respectas per PWD SOR 2018 S. No. 1402 Cat AAA Make:- Havells/Polycab/Philips/Jaquar |
| 139 | Supply & Fixing of L.E.D. Tubelight with Batten suitable for up to 1x22 Watt L.E.D. Tubelight including Tube on surface complete in all respect as per PWD SOR 2018 S.No. 1413 Cat AAA Make:- Havells/Polycab/Philips/Jaquar |
| 140 | Supply & Fixing of L.E.D. Street Light Fittings having Die cast Aluminium Body and diffuser/ Reflector with 1.0sqmm 3 core Multistrand copper unarmoured cable suitable length ,1 no. 6 Amp. SPMCB complete Driver Set suitable for 45 to 50 Watt confirming to IP 65 Protection including street light Bracket (60 cm long) with Pole cap suitable for street light fittings complete in all respect as per Direction of E/I. PWD SOR 2018 S.No. 1421 Make:- Havells/Polycab/Philips/Jaquar |
| 141 | Making & Fixing of Retro Radium Board frame with 50sqmm Hollow M.S. Pipe & ACP Sheet 3mm & Retro Radium base 3mm thick including all materials, Labour, T&P etc. and Fixing at Site |