| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning in replacement of LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be fabricated by CPRI approved manufacturer only.The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, front side double door type with locking arrangementfor front and back side also, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel.The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. |
| 2 | The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc.The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs of suitable capacity and RYB, ON, OFF & Trip LED indicating lamps at incoming.The panel shall be provided with manufacturer\"s name plate, skull & bones danger notice board etc.The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1 mt height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement .All MCCBs shall be provided with spreader links of suitable capacity with phase separators on both side complete all as specified and as directed. The overall size of the panel shall not be less than 1500mmX400mmX1200mm (LxBxH).The panel shall be provided for Cable entry from bottom side for required No of Cable with suitable size of SS Cable Glands including2 Nos of Earting Terminals one on each side of the Panel with earth strip and including following accessories:-Note: (a) Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-Charge.(b) Two stage Factory inspection of the LT Panel (i.e before powder coating and during installation of Switchgears and busbar) shall be arranged by the Contractor to the Engr-in-Charge without any extra cost to the Govt.(a) On Load Change over Switch of 200 Amps, 4 Pole, 415 Volts, AC with all standard connected accessories - 01 No. |
| 3 | (b) MCCB 4 Pole, 415 Volts, 160 Amp, 25 KA, Conforms to IEC-60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Adjustable short circuit setting 1.5-10 x In Manual type (Incoming) - 01 Nos. |
| 4 | (c) MCCB 4 Pole, 415 Volts, 100 Amp, 16 KA, Conforms to IEC-60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Adjustable short circuit setting 1.5-10 x In Manual type (Outgoing) - 02 Nos. |
| 5 | (d) MCB 4 Pole, 415 Volts, 63 Amp, AC (Outgoing) - 04 Nos. |
| 6 | (e) MCB 2 Pole, 230 Volts, 63 Amp, AC (Outgoing) - 03 Nos. |
| 7 | (f) MCB 2 Pole, 230 Volts, 40 Amp, AC (Outgoing) - 03 Nos. |
| 8 | (g) LED type phase indicator lamp RYB, ON, OFF & TRIP. |
| 9 | (h) 3-phase & Neutral bus bars of high conductivity aluminium alloy for phase (R,Y,B) & N suitable for 260 Amp rating. |
| 10 | Supply, installation, testing and commissioning in replacement of LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be fabricated by CPRI approved manufacturer only.The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, front side double door type with locking arrangementfor front and back side also, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel.The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. |
| 11 | The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc.The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs of suitable capacity and RYB, ON, OFF & Trip LED indicating lamps at incoming.The panel shall be provided with manufacturer\"s name plate, skull & bones danger notice board etc.The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1 mt height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement .All MCCBs shall be provided with spreader links of suitable capacity with phase separators on both side complete all as specified and as directed. The overall size of the panel shall not be less than 800mmX350mmX900mm (LxBxH).The panel shall be provided for Cable entry from bottom side for required No of Cable with suitable size of SS Cable Glands including2 Nos of Earting Terminals one on each side of the Panel with earth strip and including following accessories:-Note: (a) Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-Charge.(b) Two stage Factory inspection of the LT Panel (i.e before powder coating and during installation of Switchgears and busbar) shall be arranged by the Contractor to the Engr-in-Charge without any extra cost to the Govt.(a) MCCB 4 Pole, 415 Volts, 100 Amp, 16 KA, Conforms to IEC-60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Adjustable short circuit setting 1.5-10 x In Manual type (Incoming) - 01 No. |
| 12 | (b) MCB 4 Pole, 415 Volts, 63 Amp, AC (Outgoing) - 02 Nos. |
| 13 | (c) MCB 2 Pole, 230 Volts, 40 Amp, AC (Outgoing) - 02 Nos. |
| 14 | (d) LED type phase indicator lamp RYB, ON, OFF & TRIP. |
| 15 | (e) 3-phase & Neutral bus bars of high conductivity aluminium alloy for phase (R,Y,B) & N suitable for 160 Amp rating. |
| 16 | Supply, installation, testing and commissioning in replacement of LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be fabricated by CPRI approved manufacturer only.The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, front side double door type with locking arrangementfor front and back side also, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel.The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. |
| 17 | The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc.The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs of suitable capacity and RYB, ON, OFF & Trip LED indicating lamps at incoming.The panel shall be provided with manufacturer\"s name plate, skull & bones danger notice board etc.The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1 mt height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement .All MCCBs shall be provided with spreader links of suitable capacity with phase separators on both side complete all as specified and as directed. The overall size of the panel shall not be less than 1000mmX350mmX900mm (LxBxH).The panel shall be provided for Cable entry from bottom side for required No of Cable with suitable size of SS Cable Glands including2 Nos of Earting Terminals one on each side of the Panel with earth strip and including following accessories:-Note: (a) Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-Charge.(b) Two stage Factory inspection of the LT Panel (i.e before powder coating and during installation of Switchgears and busbar) shall be arranged by the Contractor to the Engr-in-Charge without any extra cost to the Govt.(a) MCCB 4 Pole, 415 Volts, 125 Amp, 16 KA, Conforms to IEC-60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Adjustable short circuit setting 1.5-10 x In Manual type (Incoming) - 01 No. |
| 18 | (b) MCB 4 Pole, 415 Volts, 63 Amp, AC (Outgoing) - 02 Nos. |
| 19 | (c) MCB 2 Pole, 230 Volts, 40 Amp, AC (Outgoing) - 08 Nos. |
| 20 | (d) LED type phase indicator lamp RYB, ON, OFF & TRIP. |
| 21 | (e) 3-phase & Neutral bus bars of high conductivity aluminium alloy for phase (R,Y,B) & N suitable for 200 Amp rating. |
| 22 | Supply, installation, testing and commissioning in replacement of LT Panel weather proof indoor type single door, fabricated out of 2.0 mm thick CRCA sheet with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be fabricated by CPRI approved manufacturer only.The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-54, front side locking arrangement , comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber.The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. |
| 23 | The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc.The panel shall be provided /installed with Automatic Transfer Switch of 250 Amps, 4 Pole, 440 Volts, 50 Hz having automatic control with inbuilt time delay protection against single phase, over /under voltage and inbuilt phase correction and having rated capacity of microprocessor based MCCB alongwith associated wiring and all standard connected accessories and connection according to site condition and RYB, ON, OFF & Trip LED indicating lamps.The panel shall be provided 4 Nos angle iron supports of adequate height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement .The panel shall be provided for Cable entry from bottom side for required No of Cable with suitable size of SS Cable Glands etc.Note: (a) Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-Charge.(b) Two stage Factory inspection of the LT Panel (i.e before powder coating and during installation of Switchgears and busbar) shall be arranged by the Contractor to the Engr-in-Charge without any extra cost to the Govt. |
| 24 | Supply, installation, testing and commissioning in replacement of LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be fabricated by CPRI approved manufacturer only.The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-54, front side double door type with locking arrangementfor front and back side also, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel.The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. |
| 25 | The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc.The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs of suitable capacity and RYB, ON, OFF & Trip LED indicating lamps at incoming.The panel shall be provided with manufacturer\"s name plate, skull & bones danger notice board etc.The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1 mt height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement .All MCCBs shall be provided with spreader links of suitable capacity with phase separators on both side complete all as specified and as directed. The overall size of the panel shall not be less than 1200mmX400mmX900mm (LxBxH).The panel shall be provided for Cable entry from bottom side for required No of Cable with suitable size of SS Cable Glands including2 Nos of Earting Terminals one on each side of the Panel with earth strip and including following accessories:-Note: (a) Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-Charge.(b) Two stage Factory inspection of the LT Panel (i.e before powder coating and during installation of Switchgears and busbar) shall be arranged by the Contractor to the Engr-in-Charge without any extra cost to the Govt.(a) Changeover Switch 250 Amps, 4 Pole, 415 Volts (Incoming) - 01 No. |
| 26 | (b) MCCB 4 Pole, 415 Volts, 160 Amp, 25 KA, Conforms to IEC-60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Adjustable short circuit setting 1.5-10 x In Manual type (Incoming) - 01 No. |
| 27 | (c) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA, Conforms to IEC-60947-2, Ics = 100% Icu suitable for Isolation and short circuit. (Outgoing) - 03 Nos. |
| 28 | (d) MCB 2 Pole, 230 Volts, 63 Amp, AC (Outgoing) - 06 Nos. |
| 29 | (e) LED type phase indicator lamp RYB, ON, OFF & TRIP. |
| 30 | (f) 3-phase & Neutral bus bars of high conductivity aluminium alloy for phase (R,Y,B) & N suitable for 400 Amp rating. |
| 31 | S & F in replacement of Tap-Off Box Sheet Metal Enclosure of 2 mm thick CRCA Sheet with fixing arrangement at Bus Bar Riser of Legrand make and MCCB 4 Pole, 415 Volts, 160 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu with extended rotary handle (ROH) mechanism, notifying ON/OFF/TRIP position of MCCB including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed.Make : Legrand cat Part No. 65285014P, EN-60439-1/2, IP 55. |
| 32 | S & F in replacement of Tap-Off Box Sheet Metal Enclosure of 2 mm thick CRCA Sheet withfixing arrangement at Bus Bar Riser of Legarand Make and MCCB 4 Pole, 415 Volts, 250 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu with extended rotary handle (ROH) mechanism, notifying ON/OFF/TRIP position of MCCB including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed.Make : Legrand cat Part No. 65285014P, EN-60439-1/2, IP 55. |
| 33 | S & F in replacement On load change over switch four pole with advance Neutral 400 Amps current rating, 415 Volts, 50 Hz, AC, with Steel Sheet Enclosure with staggered terminals conforming to IEC 60947-3 including suitable size of spreader links on both side with galvanised or cadmium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 34 | S&F in replacement existing old/outdated Breaker Control Switch (TNC) to operate ACB\"s including fixing charges including required suitable wiring for ACB\"s including cutting welding etc complete all as specified and directed. |
| 35 | S&F in replacement of existing old/outdated LT ACB, 4 Pole, 1600A, Ics=Icu=Icw=50kA (RMS) for 1 Sec , Electrical draw out type, front operated Air Circuit Breaker suitable for 415 Volts, 3-phase, 4 Wire, 50 Hz, AC supply system complete with microprocessor based protection release with LCD 4 line display and adjustable over current, adjustable short-circuit, adjustable earth-fault, instantaneous protection and over temperature protection feature, breaker shall have minimum breaking apacity of 50 kA (RMS Symmetrical) in-built thermal memory, 5 NO/5 NC auxiliary contacts, ready to close contact, zone selective interlocking, double isolation feature, conforming to IEC:60947/IS:13947, Part-II/1993 (latest version), protection release should be self powered no additional power required for protection function including making modifications in the existing LT Panel by suitable capacity of Bus bar including dismantle old ACB complete all as specified and directed.Make : ABB Cat Part No. New Emax with PR-122 inbuilt protection relay or equivalent in Schneider NW-6P inbuilt protection relay/Siemens 3WL-76B in-built protection relay. |
| 36 | M & L for 6 Way TPN DB-VTPN 160 Amp MCCB DB\"s, as per IEC 61439-3, IP-43, IK-9 with Metal Double Door, suitable for flush mounting and surface mounting with 250 Amp copper busbar for each phase, 2 neutrals bar, 2 earth busbar and cable ties for cable management, fully insulated busbar & shrouded neutral bars, improved Pan assembly for installation, IP-54 with and including. |
| 37 | Preventive Maintenance and Servicing of Servo Voltage Stabilizer, Oil Cooled & Indoor type of Capacity 100 KVA, 3-phase, 415 Volts, 50 Hz, AC Supply by disconnecting carefully its electric cable connection on primary & secondary side, Checking both side bushing, bus bar connections, opening top cover of the Voltage Stabilizer by unscrewing its nuts, bolts, washers etc, rectify the oil leakages issues, if noticed any, during servicing and re-fixing the top cover of transformer according to previous system.Servicing of the Servo Voltage Stabilizer must be done through authorised dealer / service engineer including maintain and submit the inspection and test records of each Servo Voltage Stabilizer to the Engr-in-Charge. Make of Stabilizer : Chime Electronics (Sinetrac)Note 1:Inspection of Servo Voltage Stabilizer shall be comprising :-(a)Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts etc.(b)Checking all brazings, joints, tap heads, gaskets and connection joints etc.(c)Checking all terminations / connections inside Voltage Stabilizer.(d)Checking moving and fixed contacts for contact wear and connection to winding etc in presence of Engr-in-Charge.Note 2:(a)Major Spares found faulty during service, will be replaced and paid separately under respective item of BOQ.(b)The rates quoted against the item is deemed to be included for cost of Labour for replacement of Faulty spare parts & lifting/ transporting to civil workshop and vice-versa from Machine Room at 11th Floor of MBC Bldg by using stairs manually/mechanically, if required as per site requirement without any extra cost to the department. |
| 38 | Supply only in replacement of Synchronous motor single phase, 10 Kg torque motor, 1-ph, 230V, suitable/compatible to existing 100 KVA Valtage stabilizer as per existing make /model (Chime Electronics (Sinetrac)) complete al as specified and directed. |
| 39 | Supply only in replacement of High/Low Voltage cut off PCB Card, suitable / compatible to existing 100 KVA stabilizer as per existing makeand model (Chime Electronics (Sinetrac)) complete all as specified and directed. |
| 40 | Supply only in replacement ofRC Network for motor 10 Kg torque, suitable/compatible to existing 100 KVA Voltage stabilizer as per existing makeand model (Chime Electronics (Sinetrac) ) complete all as specified and directed. |
| 41 | Supply only in replacement of I.C. Electronic Control Card, suitable/ compatible to existing 100 KVA voltage stabilizer as per existing makeand model (Chime Electronics (Sinetrac)) complete all as specified and directed. |
| 42 | Supply only in replacementofMicro switch, suitable / compatible to existing 100 KVA Voltage stabilizer as per existing makeand model (Chime Electronics (Sinetrac)) complete all as specified and directed. |
| 43 | Supply only in replacementofCarbon brush, suitable / compatible to existing 100 KVA Voltage stabilizer as per existing makeand model (Chime Electronics (Sinetrac)) complete all as specified and directed. |
| 44 | Supply only in replacementofNeon Indicator, suitable / compatible to existing 100 KVA voltage stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and directed. |
| 45 | Supply only in replacementofVoltmeter Selector Switch, Rotary type notifying the position as RY-YB-BR as per existing makeand model and directed. |
| 46 | Supply only in replacementofVoltmeter analogue type, suitable /Compatible to existing 100 KVA Voltage Stabilizer as per existing makeand model (Chime Electronics (Sinetrac)) complete all as specified and directed. |
| 47 | Supply only in replacementofAmmeter with suitable size of CT, suitable for 100 KVA Voltage Stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and directed. |
| 48 | Supply only in replacementofcomplete set of Gear of 10 Kg Torque Motor, suitable /Compatible to existing 100 KVA Voltage Stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and directed. |
| 49 | Supply only in replacement control wiring of 1.5 Sqmm single core multi-stranded FRLS copper conductor insulated with heat shrinkable PVC sleeve taggedand secured for indicators / meters/Voltage Stabilizers etc including suitable size of copper lugs, PVC cable ducts, galvanised or cadmium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 50 | All as per item No. 12 above but ofcapacity 50 KVA. |
| 51 | All as per item No. 12 above but ofcapacity 25 KVA. |
| 52 | Supply and filling /topping up of voltage stabilizer oil with di-electric strength not less than 50 KV in to the body tank of the voltage stabilizer installed in Machine Room at 11th Floor of MBC Bldg including maintain & submit the test result complete all as directed by the Engr-in-Charge.Make : Poweroil/ Transol/ Sabitha Chemicals.Note: (i)New Stabilizer oil will be filled in the Voltage Stabilizer only after filteration and de-hydration of existing oil of the Voltage Stabilizer.(ii)Voltage Stabilizer oil shall be supplied in sealed container /barrel with test result and test certificate etc. |
| 53 | M & L for dehydration/filteration of voltage stabilizer oil at site by taking proper shutdown of various capacity of Voltages Stabilizers installed in Machine Room at 11th Floor of MBC Bldg, desired di-electric strength of oil not less then 50 KV complete all as directed and specified and also submit the test result before and after the de-hydration of the stabilizer oil. |
| 54 | S & F in replacement Off Load change over switch four pole with advance Neutral 200 Amps current rating, 415 Volts, 50 Hz, AC, with Steel Sheet Enclosure with staggered terminals conforming to IEC 60947-3 including suitable size of spreader links on both side with galvanised or cadmium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 55 | M&Lfor preparation of existing surface of Voltage stabilizer of 100 KVA, Oil Cooled type by srapping down /peeled off old paint, loose scale grease, Lubricants etc by abrasive paper andapplying one coat of smoke gray paint by spray complete all as specified and directed by Engr- in-Charge. |
| 56 | M & L in replacement for Synthetic insulation mat of size 2m x 1m x 19mm, suitable for 3.3 KV working voltage complete all as directed. |
| 57 | Preventive maintenance and servicing of LT ACB, MDO Type, Rated Current 800/1250A, AC, 50 Hz, Indoor type by taking out the LT ACB trolley from Panel, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of ACB.Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases & Neutral, adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing, rectifying the fault and calibration of relay of LT ACB.This Job must be carried out through authorised dealer / service engineer including maintain and submit the test report to the entire satisfaction of Engr-in-Charge. |
| 58 | Preventive maintenance and servicing of LT ACB, MDO Type, Rated Current 1250/ 1600A, AC, 50 Hz, Indoor type by taking out the LT ACB trolley from Panel, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of ACB.Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases & Neutral, adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing, rectifying the fault and calibration of relay of LT ACB.This Job must be carried out through authorised dealer / service engineer including maintain and submit the test report to the entire satisfaction of Engr-in-Charge. |
| 59 | Preventive maintenance and servicing of LT ACB, MDO Type, Rated Current 1250/1600A, AC, 50 Hz, Indoor type by taking out the LT ACB trolley from Panel, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of ACB.Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases & Neutral, adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing, rectifying the fault and calibration of relay of LT ACB.This Job must be carried out through authorised dealer / service engineer including maintain and submit the test report to the entire satisfaction of Engr-in-Charge. |
| 60 | Supply only in replacementof Spring charging motor includingassemblyand pushbutton etc suitable /compatible to existing LT ACB of 1250/1600A capacity complete all as specified and directed. |
| 61 | Supply only in replacementof Triping coil assembly suitable /compatible to existing make and model of 1250 /1600A, LT ACB complete all as specified and directed. |
| 62 | Supply only in replacementof Under Voltage Release (UVR) Coil assembly, suitable /compatible to existing make and model of 1250 /1600A, LT ACB complete all as specified and directed. |
| 63 | Supply only in replacement earth fault release, suitable / compatible to existing LT ACB MDO type of 1250/1600 Amps capacity as per existing make & model complete all as specified and directed. |
| 64 | Supply only in replacement of operating handle made up of high tensile steel, suitable /compatible to existing LT ACB, MDO Type capacity 1200/1600 Amps as per existing make and model complete all as specified and directed. |
| 65 | Supply only in replacement of Fixed terminal block/Contact, suitable /compatible to existing LT ACB, MDO Type capacity 1200/1600 Amps as per existing make and model complete all as specified and directed. |
| 66 | Supply only in replacement of Moving terminal Block / Contact, suitable /compatible to existing LT ACB, MDO Type capacity 1200/1600 Amps as per existing make and model complete all as specified and directed. |
| 67 | S & F in replacement MCCB 3 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 68 | S & F in replacement MCCB 3 Pole, 415 Volts, 100 Amp, 16 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 69 | S & F in replacement MCCB 3 Pole, 415 Volts, 125 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 70 | S & F in replacement MCCB 3 Pole, 415 Volts, 160 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 71 | S & F in replacement MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 72 | S & F in replacement MCCB 4 Pole, 415 Volts, 100 Amp, 16 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 73 | S & F in replacement MCCB 4 Pole, 415 Volts, 125 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 74 | S & F in replacement MCCB 4 Pole, 415 Volts, 160 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 75 | S & F in replacement MCCB 4 Pole, 415 Volts, 200 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 76 | S & F in replacement MCCB 4 Pole, 415 Volts, 250 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 77 | S & F in replacement MCCB 4 Pole, 415 Volts, 400 Amp, 36 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 78 | S & F in replacement MCCB 4 Pole, 415 Volts, 630 Amp, 50 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 79 | M&L in replacement of GI earthing with New Chemical earthing with copper bond pipe of dia 76 mm & 3 Mtr long including excavation in any type of soil starta. Filled with highly conductive compound which Increase the life of earthing electrode. Composition of chemical filled in electrode water solubility, acid solubility, Grain size 100 mesh, along with BFC Compound non toxic, non reactive, non explosive and non corrosive, longer life easy to maintain less space consistent results including earthing pit and chamber cover complete all as specified and directed at site. |
| 80 | M&L in replacement of old GI strip with New Copper strip of size 20 x 3.15 mm as earth electrode for interconnection the various Eqpts / Machinery/Panel etc with earthing electrode including fixing on any type of wall with suitable size of GI Saddle /clamps, nut, bolts and washers etc complete all as specified anddirected. |
| 81 | S & F in replacement of cylindrical panel locks of suitable size or as per sample including drilling, cutting and welding etc in panel sheets without disturbing to other existing fitments complete all as specified and directed. |
| 82 | S & F Wire mesh Cable Tray Hot Dipped Galvanized size 105 (h) X 600 (w) mm, Trays should comply Standard EN ISO 14 61: at least 550 h of SST. The deflection of cable tray must be no more than 1/200th of the distance between two supports and tested in accordance with the atandard IEC 61537, Wire cable trays must be designed with an optimum span of 1.5 m, taking into account the maximum carrying capacity authorised by the manufacturer including all standard wall mounting accessories e.g. Mounting Bracket (Horizontal & Vertical Both), bends, Fastners, kitastar, nut, bolts and washers etc at suitable intervals complete all as specified and directed.It shall be manufactured with a longitudinal \"T- welded\" safety edge. Make -Legrand |
| 83 | S&F in replacementhigh power Flood Light, LED100W , die castaluminium, IP65suitablefor highlightingarchitectural features and general purposelighting complete all as specified and as directed. |
| 84 | S&F in replacementhigh power Flood Light, LED200W , die castaluminium, IP65suitablefor highlightingarchitectural features and general purposelighting complete all as specified and as directed. |
| 85 | S&F in replacementhigh power Post Top, LED25W, IP 65aesthetically designed with symmetrical light distribution , spun aluminiumlandscape luminaire with high powerLEDs complete all as specified and as directed. Make- Havells cat part No. RUBYPT25WLED757SSYMTOPC. |
| 86 | S&F in replacement high power hanging type Light LED 35 W, suitable for Vertical/Horizontal surface mounting, pressuredie cast aluminium well glass luminaires including hanging arrangement in high raise structure/hanger/garage etc complete all as specified and as directed. |
| 87 | S & F in replacement of Cone NXG LED Bollard, 8 Watt, 230, Volts, IP-65 including suitable size of hot dipped galvanised pole of height not less than 600 mm, Aesthetic and innovative design with uniformli lit diffuser at the upper portion inluding terminal connctions & standard mounting accessories to fix on pole etc complete all as specified and directed at site.Make : Havells Cat Part No. CONENXGBLS8WLEDPSYM857TOPC |
| 88 | S&F in replacement high power LED 120W, Vertical high bay/medium bay LED IP54 luminaire with high power Bay brite flare highbay complete all as specified and as directed.Make- Havells Cat part No BAYBRITEFLAREHB120WLE7857APWBBOLTGor equivalentmodel of makes mentined in PS. |
| 89 | Supply & Fix in replacement on pole, SMC Junction box inner dimensions (270 x 225 x 135)mm (LxBxD), 3 phase 4 wire system, including 1 x 6 Amp DP MCB with mounting SS railing, Cable lugs, glands,suitable to 10/16 Sqmm 4 core cable, connection for incoming and outgoing cables including Fixing arrangement on pole etc complete all as specified and directed by Engr-in-Charge. |
| 90 | Labour for cleaning of Elecrtical Switch Rooms (approx size 4x6x3) Mtr at every floors including basement of MBC Bldg by removing unwanted material i.e. Dust/mud, wastage of Bats, spider web, LT panels, 3 x LT Risers and any other misc scrap items etc complete all as specified and directed.Note: The unwanted material removed from ESR will be thrown away at debries dumping area outside the main building complex (distance not more than 800 mtrs approx one way) without any extra cost to the deptt. |
| 91 | S & Fix in replacement Sheet Metal Enclosures factory made Tripple Pole and Earth enclosure with a three pin and earth plug with 63 Amp Industrial socket complete with one Four Pole MCB of 63 Amp, 415 Volts, 10 KA including wall mouting accessories and connection to Boiler complete all as directed. |
| 92 | S & F in replacement MCCB 4 Pole, 415 Volts, 160 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu with extended rotary handle (ROH) mechanism, notifying ON/OFF/TRIP position of MCCB including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed.Make : L&T/Legrand/ABB. |
| 93 | S & F in replacement MCCB 4 Pole, 415 Volts, 250 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu with extended rotary handle (ROH) mechanism, notifying ON/OFF/TRIP position of MCCB including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed.Make : L&T/Legrand/ABB. |
| 94 | S & F in replacement MCCB 4 Pole, 415 Volts, 400 Amp, 36 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu with extended rotary handle (ROH) mechanism, notifying ON/OFF/TRIP position of MCCB including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. |
| 95 | S&F in replacementStreet Light, LED60W, made up of pressure die cast aluminium housingwith high power LEDaslighting source and lens embedded PC cover having topopeningseparate driver compartment with IP 66 protection and impact resistance of IK07 including driver and suitable for fixing at pole of dia 80 mm complete all as specified and as directed. |
| 96 | S&F in replacementStreet Light, LED90W,made up of pressure die cast housingwithtoughned glassand individual high power LEDwith secondary optics, IP66 protection andimpact resistance of IK07including driver and suitable for fixing at pole of dia 80 mm complete all as specified and as directed. |
| 97 | Preventive maintenance and testing of LT Busbar Riser, 3-phase 4 wire system (Legrand make) (G+11) & (G+3) etc by checking leakages, earthfault, voltages etc by authorised dealer or service engineer and submit the test report to the Engr-in-Charge complete all as specified and directed. |
| 98 | M&Lfor preparation of existing surface of steel tubular pole by srapping down peeled off old paint, cleaning etcof length 8.5/9/11 mtrs and cross arms etc and applying one coat of aluminium paint including rewriting pole Nos with black paint complete all as specified and directed by Engr- in-Charge. |
| 99 | M & L in replacement for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones of Post Office RED Colour and fixed on LT Poles with M.S. clamps, bolts and nuts of required size, for 440 Volts LT of size 200 X 150mm complete including taking down existing one complete all as directed. |
| 100 | S & F in replacement LED Recess Mounted type, Spot Light, Wall washers, tilted 70 deg outwards and swivels 350 deg to offer best illumination on the wall and retail displays including suitable LED Driver with copper flexible PVC insulated wire including clamps and nut & bolts for fixing complete all as specified and directed. |
| 101 | S & F in replacement of MCB 3P 415 Volts, 63 Amps, 10 KA Complete all as specified and directed. |
| 102 | S & F in replacement of MCB 4P 415 Volts, 63 Amps, 10 KA Complete all as specified and directed. |
| 103 | Supply & Laying in replacement Synthetic Rubber Insulated Mats 2 mm thick for Voltage upto 3.3 KV working pressure conforms to IS 15652-2006 (Superseding IS 5424) suitable for Electrical Shock Safety including applying adhesive to fix before laying the new one complete all as specified and directed. |
| 104 | S & F in replacement of 2.5 sqmm 2 core PVC round/flat sheathed flexible Aluminium multistranded cable complete all as specified and as directed. |
| 105 | S & F in replacement of 1.5 sqmm 3 core PVC round/flat sheathed flexible copper multistranded cable including fixing on Cable Tray/in trench/any type of wall/pole etc with suitable size of PVC/GI Saddle, screw etc complete all as specified and as directed. |
| 106 | All as per item Ser No. 61 above but 2.5 sqmm 3 core |
| 107 | All as per item Ser No. 61 above but 4 sqmm 4 core |
| 108 | All as per item Ser No. 61 above but 6 sqmm 4 core |
| 109 | All as per item Ser No. 61 above but 10 sqmm 3 core |
| 110 | Preventive Maintenance and Servicing of On Line UPS of 60 KVA Capacity, 3-phase, 415 Volts, 50 Hz by disconnecting carefully its electric cable connection fron In/Out side, Checking, opening top cover of the On Line UPS by unscrewing its nuts, bolts, washers etc, rectify the fault if noticed any, during servicing and re-fixing the top cover of UPS according to previous system including testing of 12V, 120 Ah maintemance free batteries after applying full load and duration of bakeup.Servicing of the 60 KVA On Line UPS must be done through authorised dealer / service engineer including maintain and submit the inspection and test records to the Engr-in-Charge. Make : VertivNote 1:Inspection of On Line UPS shall be comrpising :-(a)Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts etc.(b)Checking all brazings, joints, tap heads, gaskets and connection joints etc.(c)Checking all terminations / connections inside UPS.(d)Conducting the test as per relavent mfg Instr manual in presence of Engr-in-Charge.Note 2:(a)Major Spares found faulty during service, will be replaced and paid separately under respective item of BOQ.(b)The rates quoted against the item is deemed to be included for cost of Labour for replacement of Faulty spare parts & lifting/transporting to civil workshop and vice-versa from ESR, 1st Floor of MBC Bldg by using stairs manually/mechanically, if required as per site requirement without any extra cost to the department. |
| 111 | Supply only in replcement of Cooling fan, 230 Volts (NISIKI, NISI2038HB2 Model), 19/16 Watt including connecting wiring, suitable /Compatible to existing 60 KVA On Line UPS as per existing make, size and model etc complete all as specified and direcetd. |
| 112 | Fixing in repair of PCB Card, Fuse & Control wiring, suitable /Compatible to existing 60 KVA On Line UPS as per existing make & model etc complete all as specified and direcetd.Note: Cost of transportation from work site to Civil workshop and vice-versa deemed to be included in the quoted rate. |
| 113 | Reboot and re-installation of Vertiv Software after replacement of faulty parts, suitable /Compatible to existing 60 KVA On Line UPS as per existing make & model etc complete all as specified and direcetd. |
| 114 | Fixing in repair of Digital Display Screen of 60 KVA On Line UPS of Vertiv Make by OEM or authorised service dealer complete all as specified and directed.Note: Cost of transportation from work site to Civil workshop and vice-versa deemed to be included in the quoted rate. |
| 115 | Attending breakdown /inspection of Servo Voltage Stablizer, Oil Cooled Type, Indoor type of capacity25 KVA to 100 KVA, 3-phase, 415 Volts by authorised dealer / service engineer and rectify the any type of fault and replace any spares related to breakdown complete all as specified and directed at site.Make of Voltage Stabilizer : Chime Electronics (Sinetrac) |
| 116 | S&F in replacement 2 X 2 panel, ultramodern,recess mountingluminaire with high brightness,LED 36 Watt, Colout Worm /Moon White suitableforarmstrong/ grid ceiling, as light source including connection with flexible wireand all fixing accessories complete all as specified and as directed. (Make - Havells Cat Part No VENUSNEO2x2PLR36W LED840PRALMOD |
| 117 | S & F in replacement of Emergency Switch assembly complete with push button as per existing make and model or suitable /compatible to 3-ph, 415 Volts, 60 KVA On Line UPS including updation of Vertiv software after replacement of faulty emergency switch complete all as specified and directed.Make of UPS : Vertiv |
| 118 | M & Lfor plain concrete cement 1:2:4 type B2 using 40mm graded coarse aggregate for foundation of Feeder Panels/Path Way etc including necessary form work/Shuttering etc complete all as specified and directed. |
| 119 | S&F in replacement of Maintenance Free Rechargeable Type Battery of Capacity 100 Ah, 2 Volts suitable for Battery Bank of LT Panel including complete all as specified and directed.Make : Exide UPST 100 |
| 120 | M&L for preparation of old painted surface of LT Panel, MS Trench Cover, GI tubing etc by brushing/cleaning and removing stains & grease spots with thinner and sand paper and painting the cleaned surface with synthetic enamel paint Black /MES Colour or as approved by the Engr-in-Charge to achieve good finish by applying two coats of paint by spray painting machine carefully complete all as specified and direcetd. |
| 121 | S&F in replacement 2 X 2 panel, ultramodern,Surface mountingluminaire with high brightness,LED 36 Watt, suitableforarmstrong/ grid ceiling, as light source including connection with flexible wireand all fixing accessories complete all as specified and as directed. (Make - Havells Cat Part No. PLANOSURFACE2x2PLS34W LED857S |
| 122 | Supply and laying in replacement (laying in ducts /on Cable trays etcwith new saddles & clamps etc as per site requirement) including testing & commissioning of 1100 Volts grade LT, multistranded AL Conductor, Electric Power Cable (Heavy Duty), XLPE insulated, galvanized steel strip or wire armored of size 16 Sqmm 2 Core complete all as specified and directed.Make : Gloster/Poycab/Havells |
| 123 | Supply and laying in replacement (laying in ducts /on Cable trays etcwith new saddles & clamps etc as per site requirement) including testing & commissioning of 1100 Volts grade LT, multistranded AL Conductor, Electric Power Cable (Heavy Duty), XLPE insulated, galvanized steel strip or wire armored of size 50 Sqmm 3.5 Core complete all as specified and directed.Make : Gloster/Poycab/Havells |
| 124 | Attending breakdown /inspection of On Line UPS of 60 KVA, 3-ph, 4 wire type by authorised dealer / service engineer and rectify the any type of fault including updating of Vertiv Software and clear the breakdown of UPS complete all as specified and directed at site.Make of UPS : Vertiv |
| 125 | S&F in replacement of Battery Lead with stranded bare Copper conductor of size 10 Sqmm single core FRLS cable, PVC insulated Flexible minimum 0.6 mtr long or as per site requirement alongwith Battery terminal for Negative and Positive terminal duly soldered including nut-bolts, washers and terminal cap etc complete all as specified and directed. |
| 126 | Preventive Maint and services of 30 Volts Battery Bank of LT Panel by authorised dealer / service engineer and rectify the faults complete all as specified and directed. |
| 127 | S&F in repair direct on line starter 415 volt, 50 Hz with voltmeter, Ammeter, relay, timer and single phase preventor complete for following pump set capacity (Make - L&T/BCH) :- |
| 128 | 3 to 5 HP Pump Set |
| 129 | 7.5 HP Pump Set |
| 130 | Supply and fixing in repair heavy duty cast brassfoot valve screwtype 50 mm dia, pressure 250 PSIcomplete (Make : Leader/ BIR/ Kirloskar/ Upadhaya/Zoloto/Sant |
| 131 | Suppy only liquid chlorine suitable for water treatment by mannual methed HDPF in 50 litre drum (Make : Davis Chemical/ Prothamesh Trading/ Aditya birla) (Note :- Fresh lot of liquid chlorine shall be supplied with in 45 Days from the date of manufacturing as per monthy demand or as directed. |
| 132 | Supply only bleaching powder Calcium Hypochloride minimum 32% cholorine as per IS-1065:1989 in 25 Kg Bag (Make : Raj/Cambal/DCM/Aditya Birla/Rajendra chemical/RS dye/Kalyani/Guru Kirpa Traders) (Note: Fresh lot of bleaching powder shall be supplied with in 45 Days from date of manufacturing as per monthy demand or as directed) |
| 133 | Material & Labour for replacementofindustrial copper conductor submersible cable, PVC insulated and PVC sheathed cable, 1100 volt grade of size 4 sqmm x 3 core (Make- Finolex/L&T/Anchor/Havells) |
| 134 | Cleaning of underground/semi underground sump/OH tank/fountain sump by taking out all sludge, silt from bottom and cleaning all inside walls with wire brush and brooming the walls and top ceiling/roof including washing the walls with fresh water mixed with bleaching powder and draining out complete sludge, silt etc from bottom of the sump and applying one coat of lime wash for the UG sump of capacity upto 25,000 gallons complete all as directed. |
| 135 | Supply and fixing of DOL pump starter upto 5 to 10HP 7.5 KW 240V relay range 13.2 to 20 A complete all as specified and directed by Engr-in-Charge. |
| 136 | Material & Labour forreplacement ofsteel shaft of centrifugal pump 5 to 10HP including dismantling, opening and refixing the same on its original location all as specified and directed. |
| 137 | Material & Labour forreplacement of steel shaft of centrifugal pump 15 to 20HP including dismantling, opening and refixing the same on its original location all as specified and directed. |
| 138 | Material & Labour for replacement of self priming mono block pump with motor 1 HP with in-built thermal overload protector complete all as specified & installation in repair of centrifugal pump having discharge not less than 80 Ltr per minute,Head-not less than 10 mtr m,1400/1500, single phase, 230 volt including all connection and testing complete all as specified & directed (Make- Crompton/ CRI/ Kirloskar/ KSB/ Beacon/ Havells) |
| 139 | S&F in repair of good quality tyre rubber couplingsuitable for 5 to 10HP pump set (Make-Unique/Form-Flex/HIC/Mahalaxmi/Metro) |
| 140 | S &F in repair of good quality tyre rubber coupling suitable for 15 to 20 HP pump set (Make-Unique/Form-Flex/HIC/Mahalaxmi/Metro) |
| 141 | Dismanltingand disconnection from motor and water connection of thepumpand transport to work shop & opening carefully and servicing complete with replacing of bushes, gland packing, ball bearing, rubber gasket, nut and bolt and re-fixing it in original position and making out all electrical and water connection incl painting to two coats with synthetic enamell paint after necessary prepartion incl testing & commissioning complete for following capacity :- (Note: Replacement of impellor rewinding of motor shall be measured and paid separately) |
| 142 | 7.5 to 10 HP |
| 143 | 15 to 20 HP |
| 144 | Taking out submersible pump set 3 to 10 HP including column pipe and electric cable from borewell (depth upto 50 mtr) complete by chainpully or other method and lowering the same in existing borewell after repair work all as specified. Note: The rate of T&P shall be included inquoted rate. |
| 145 | Dismanltingand disconnection from motor and water connection of submersiblepumpand transport to work shop & opening carefully and servicing complete with replacing of unsv parts such as bushes/ ball bearing, rubber gasket,stop ring,washer shaft sleeve,stop plate nut and bolt and re-fixing it in original position and making out all electrical and water connection incl painting to two coats with synthetic enamell paint after necessary prepartion incl testing & commissioning complete for following capacity :- (Note:- Replacement of impellor/shaft and rewinding of motor shall be measured and paid separately) for following capacity:- |
| 146 | 3 to 10HP |
| 147 | 11 to 20 HP |
| 148 | Dismanltingand disconnection from sumersible pump and electric connection of submersible motorand transport to work shop & Material & Labour for rewinding of submersible motor with PVC insulated copper winding wire of existing gauge and size to get original/proper speedand testingincludingreassebling of motor with submersible pumpcomplete for following capacity:- |
| 149 | 3 to 10HP |
| 150 | 11 to 20 HP |
| 151 | Material & Labour for spray painting of complete water pumpset of cap 3 to 10 HP with two coats of synthetic enamelled paint of specified colour after preparation of surface. |
| 152 | Material & Labour for spray painting of complete water pumpset of cap 15 to 25 HP with two coats of synthetic enamelled paint of specified colour after preparation of surface. |
| 153 | Supply ony handy medi kit first aid plastic box having medicine /first aid items asfirst Aid Leaflet, Scissor S.S, Savion 50 ml,Cotton, Bandaid (Adhesive strip), thermometer, Burn Ointment, Nitrofurazone Creame U.S.P/Neomycin , Cotton Crepe Bandage. Paracetamole Tab. I.P, Merbromin Solution (20 ml), Sterile Guage swab (5cmx5cmx12 ply), Paper Adhesive Tape, Rolled Guage(6cmx2.5mtr), Rolled Guage(7.5cmx2.5mtr), Eye wash cup (plastic), Measuring cup(plastic), Disposable Glove, Dropper Plastic, Set of safety pine, Triangular Bandage, Blade. |
| 154 | Material & Labour for painting of water supply pipes networks of 80 to 200 mm dia consisting of valves any type/ size at various pump houses inlcuding duly scrapping thoroughly the existing corroded paint / dirt/ dust/ rust and preparing the surface and applyingtwo coats of syntheticenamel paint over a coat of red oxide primer asper the colour code and marking the water flow directions on pipe lines as directed. |
| 155 | Collecting water sample in clean bottle from borewell/ UG sump/service tank and getting Chemical, Boilogical, Potability Testing of water sample (as per IS 10500:2012) at Govt recognised/approved institute/ Lab for potability and chemical analysis complete all as specified & directed. |
| 156 | Material & Labour in repair auxiliary contactor 415 Volt, 18/20 amps, coil voltage 230 Volt including auxiliary block (1 NO + 1 NC) and over load relay complete. |
| 157 | Supply only in repair of MS nut bolt of any size with washer completeall as specified and as directed. |
| 158 | Supply only in replacement GI Elbowfor 15 mm bore pipe. |
| 159 | Supply only in replacement GI Elbowfor 20 mm bore pipe. |
| 160 | Supply only in replacementGI Elbowfor 25 mm bore pipe. |
| 161 | Supply only in replacement GI Elbowfor 40 mm bore pipe. |
| 162 | Supply only in replacementGI Elbowfor 50 mm bore pipe. |
| 163 | Supply only in replacementGI Unoinfor 15 mm bore pipe. |
| 164 | Supply only in replacement GI Union for 20 mm bore pipe. |
| 165 | Supply only in replacement GI Unionfor 25 mm bore pipe. |
| 166 | Supply only in replacement GI Unoinfor 40 mm bore pipe. |
| 167 | Supply only in replacement GI Unoinfor 50 mm bore pipe. |
| 168 | Supply only in replacement GI EqualTee for 15 mm bore pipe. |
| 169 | Supply only in replacement GI EqualTee for 20 mm bore pipe. |
| 170 | Supply only in replacement GI EqualTee for 25 mm bore pipe. |
| 171 | Supply only in replacement GI EqualTee for 40 mm bore pipe. |
| 172 | Supply only in replacement GI EqualTee for 50 mm bore pipe. |
| 173 | Supply only in replacement GI Reducerfor50x40 mm bore pipe. |
| 174 | Supply only in replacement GI Reducer for 40x25 mm bore pipe. |
| 175 | Supply only in replacement GI Reducer for 25x20 mm bore pipe. |
| 176 | Supply only in replacement GI Reducer for 20x15mm bore pipe. |
| 177 | Supply only in replacement GI socketfor 15 mm bore pipe. |
| 178 | Supply only in replacement GI socketfor 20 mm bore pipe. |
| 179 | Supply only in replacement GI socketfor 25 mm bore pipe. |
| 180 | Supply only in replacement GI socketfor 40 mm bore pipe. |
| 181 | Supply only in replacement GI socketfor 50 mm bore pipe. |
| 182 | Supply only in replacement GI Nipple 15 mm bore dia x 100 mm long made out of medium grade pipe. |
| 183 | Supply only in replacement GI Nipple 20 mmbore dia x 100 mm long made out of medium grade pipe. |
| 184 | Supply only in replacement GI Nipple 25 mmbore dia x 100 mm long made out of medium grade pipe. |
| 185 | Supply only in replacement GI Nipple 25 mm bore dia x 150 mm long made out of medium grade pipe. |
| 186 | Supply only in replacement GI Nipple 40 mmbore dia x 150 mm long made out of medium grade pipe. |
| 187 | Supply only in replacement GI Nipple 50 mmbore dia x 150 mm long made out of medium grade pipe. |
| 188 | Supplyand replacement GI Plug 15 mm dia, externally threaded. |
| 189 | Supply andreplacement GI Plug 20 mm dia, externally threaded. |
| 190 | Supply and replacement GI Plug 25 mm dia, externally threaded. |
| 191 | Supply, laying, jointing & testing for replacement of GI Pipe, medium grade, including all fittings in old/new position, laid in trenches/ wallincluding taking down the old/unsv pipe line complete all as specified & directed of following sizes:- (Note:Excavation and earth work shall be measured and paid separately under respective items of schedule) |
| 192 | All as per item No. 139 above but 80 mm dia |
| 193 | All as per item No. 139 above but 50 mm dia |
| 194 | All as per item No. 139 above but 40 mm dia |
| 195 | All as per item No. 139 above but 25 mm dia |
| 196 | All as per item No. 139 above but 20 mm dia |
| 197 | All as per item No. 139 above but 15 mm dia |
| 198 | Excavation in trenches n.exc 1.5 m wide and not exc 1.5 m depth and getting out in soft and loose soil complete all as specified and directed. |
| 199 | Returning, filling in, of excavated material any type including spreading,levelling,watering and well ramming in layers not exceeding 25cm in soft/ loose soil complete all as specified and directed. |
| 200 | Removal of surplus excavated material of any type not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point in soil complete all as specified and directed. |
| 201 | Attending breakdown/ inspection of 3000 LPH Capacity RO Plant (Make: Eukawa) by Sevice Engineer of OEM to check the serviceability and repalcement of any parts related to breakdown complete all as specified and directed.Note: (a) Spares for replacement shall be measured and paid separately.(b) A sum of Rs. 1000/- will be recovered in case of not attending breakdown by service engineer within 24 hrs. |
| 202 | Supply only in replacement of Big blue spun candle 20\"\" as per existing make & model complete all as specified and direced. |
| 203 | Supply only antiscalent chemical as per existing make complete all as specified and directed. |
| 204 | Supply only in replacement of multimedia sand as per existing make complete all as specified and directed. |
| 205 | Supply only in replacement of activated carbon as per existing make complete all as specifed and directed. |
| 206 | Supply and fixing, testing adjustable Crown Jet nozzle ½’’thread size water discharge 10mm as per existing make complete all as specifed and directed. |
| 207 | Supply and fixing, testing Programmable color changing Power LED based spot lights 18W 12 V IP 68 Model : Body S.S304 Top 18 R-S.L as per existing make complete all as specifed and directed. |
| 208 | Supply and fixing, testing D.C. Controller for LED Light With Remote control as per existing make complete all as specifed and directed. |
| 209 | Supply and fixing, testing Sump cover S,S 304 as per existing make complete all as specifed and directed. |
| 210 | Cleaning of fountain sump by taking out all sludge, silt from bottom and cleaning all inside walls with wire brush and brooming the walls and top ceiling/roof including washing the walls with fresh water mixed with bleaching powder and draining out complete sludge, silt etc from bottom of the sump and applying one coat of lime wash for the fountain sump complete all as directed. |
| 211 | Dismantling and taking out corroded/worn out/unserviceable GI pipe from surface/wall/under ground trenches of size 80/50/40/25 mm bore and setting aside. (Note:- The excavation/earth work for replacement of pipe from underground trenches shall be measured and paid separately under respective items below) |
| 212 | Taking up or down 40/50 mm steel tubing and connections, including cleaning for refixing or removal to store. |
| 213 | Refixing old steel tubing and connections in new or old position (Walls, ceiling, floors, etc.) |
| 214 | M & L forGun metal, glob or gate valve, with iron wheel head, screwed on both e nds suitable for 50 mm dia GI Pipe. |
| 215 | M & L forGun metal, glob or gate valve, with iron wheel head, screwed on both e nds suitable for 40 mm dia GI Pipe. |
| 216 | M & L forGun metal, glob or gate valve, with iron wheel head, screwed on both ends suitable for 25 mm dia GI Pipe. |
| 217 | Supplying and laying of 40 mm CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings complete in trenches/Wall/surface complete all as specified and directed. |
| 218 | Supplying and laying of 32 mm CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings complete in trenches /Wall/ surface complete all as specified and directed. |
| 219 | Cutting the existing 80 mm GI tubing for inserting tee 50X50X25 mm including supply and fixing GI reducer 80x80x50 mm with all fittings all as directed including earth work. |
| 220 | Cutting the existing 50 mm GI tubing for inserting tee 50X50X25 mm including supply and fixing GI reducer 50x50x40 mm with all fittings all as directed including earth work. |
| 221 | M&L for making good the disturbed surfaces with PCC BO 1:2:4(12.5 mm graded agreegate) in surface channel and pavement. |