Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 12-02-2025 | Corrigendum for BOQ and Tenderdoc | BOQ | 19-02-2025 |
| Sl. No. | Item Description |
| 1 | Surface excavation not exceeding 30 cm deep and averaging 15 cm deep andgetting out in Soft/ Loose soil complete all as specified and directed. |
| 2 | Excavation in trenches not exc. 1.50 m wide and not exc. 1.50 m in depth for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exc. 10 Sqm on plan and getting out in soft / loose soil complete all as specified and directed. |
| 3 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick in each layer as in soil complete all as specified and directed. |
| 4 | M & L for Sand filling under floors or in foundations including watering and consolidation complete all as specified and directed. |
| 5 | M&L for sand coushioning to UG cables (8cm deep before laying of cables and 15 cm over the cable) including spreading, levelling, well ramming in layers complete all as specified and directed. NOTE:- punned thickness of 18cm only will be considered for measurement and payment. |
| 6 | Removing Excavated soils not exc 50 Mand depositing where directed at a level not exc1.5 M above the starting pointcomplete all as specified and directed. |
| 7 | M & L for Hardcore of gauge not exc. 63 mm, deposited, spread and leveled in layers not exc. 15 cm thick, watered and rammed to a true surface using broken stone or boulders complete all as specified and directed. |
| 8 | M&L PCC 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed. |
| 9 | M&L for Plain Cement Concrete Type C2 1:3:6 (using 40 mm gradedstone aggregate) in surface channels and drains complete all as specified and directed. |
| 10 | M & L for plain Cement Concrete Type B0 1:2:4 (using 12.5 mm gradedstone aggregate) in roof kerbs, rounded or chamfered on haunching in chajjas to prevent water seepage into brick walls, including necessory formwork rounded or chamfered on edges complete all as specified and directed. |
| 11 | M&L for repair to broken/damaged RCC chajjas by making good with PCC 1:2:4 type B1 or rendering 15 mm thick in cement mortar 1:4 mixed with water proofing compound to top and sides and rendering 5 mm thick to soffits in cement mortar 1:3 including necessary formwork complete all as specified and directed. Note:- Rate shall be included for necessary scaffolding and safety arrangement. |
| 12 | M&L PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) as in copings, bed plates, bed block for holdfasts, similar bands, plinth coarses, string coarses, lacing coarces, parapets nad railings upto 60 cm in height, filling in pressed steel door complete all as specified and directed. |
| 13 | M&L cement concrete 1:2:4 type B1, (using 20 mm graded crushed stone aggregate) as in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, benching, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles and throating and including necessary formwork & demoliton complete all as specified and directed. |
| 14 | M&L RCC nominal mix 1:2:4 type B1 as in slab supported on walls ,beams and coloumns in floors,roofs,landings, kitchen slabs etc complete all as specified (Reinforcement shall be measured and paid seperately) including demolition of old concrete complete all as specified and directed. |
| 15 | M&L for Precast reinforced cement concrete 1:2:4, type B1 (Using 20 mm gradedstone aggregate) in landings, cover slabs (for Manholes etc.) shelves and similar articles with plain faces and set in cement mortar 1:4 and including demolition complete all as specified |
| 16 | M&L Extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using extra cement, including forms, moulds, mitred/stopped ends etc complete all as specified and directed. |
| 17 | Supply only integral water proofing compound complete all as specified. |
| 18 | M & L for brick work with sub class ‘B’ old size bricks straight or curved on plan n.exc. 6.00 m mean radius built in cement mortar 1:6 complete all as specified and directed. |
| 19 | M&L for Burnt Brick work with sub-class `B\" bricks, straight or curved on plan to any radius in half brick thick wallbuilt in cement mortar 1:6 complete all as specified and directed. |
| 20 | M&L for brick protection cover of size 230x115x75 mm to LT underground cables with sub class ‘B’ over burnt brick, (locally available best quality), laid dry and flat abutting each other with gaps not exceeding 10 mm complete all as specified and directed. |
| 21 | Use and Waste of formwork to faces of walls, retaining walls, abutments, parapets and staircase railings and similar work including attached pillasters, buttresses, etc.; vertical or to batter for rough finished flat surfaces of concrete complete all as specified and directed. |
| 22 | M & L for use & waste of formwork to sides and soffits of floor or roof beams, beam haunchings, girders, bressummers, lintels, cantilevers, shelves including supports, overhangs etc. also splayes between floors and beams in rough finished flat surface of concrete complete all as specified and directed. |
| 23 | M&L for Mild steel TMT bars 10 mm dia., and over cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with mild steel wire (annealed) not less than 0.9 mm dia., or securing with clips complete all as specified and directed. |
| 24 | M&L 75 mm thick, PCC 1:3:6, type C-2 (using 40 mm graded crushed stone aggregate) as in sub base, floors etc complete all as specified and directed. |
| 25 | M&L 60 mm thick machine pressed precast concrete interlocking coloured paver block of any shape and size confirming to IS 15658-2006, M-35 grade, set with grey cement and pigment complete all as specified and directed. |
| 26 | M&L for rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:6 finished the surface even and smooth without using extra cement complete all as specified and directed. |
| 27 | M&L for rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 finished even and smooth without using extra cement using WPC compound complete all as specified and directed. Note:- WPC shall be measured and paid separatley. |
| 28 | Taking down cement plaster on brick or stone walls, etc., including raking out joints, hacking for key, scrubbing down with water, etc complete all as specified and directed. |
| 29 | M&L preparation of old decorated wall surfaces by brooming down or steel wire brushing scraping down smoke spot, moulds, moss and efflorescent salts and trading oil and greasy spots etc and applying one coat of white wash complete all as specified and directed. |
| 30 | M & L for preparation of newly plastered or previously untreated surfaces of walls and applying two coats of oil bound distemper over a coat of primer and over a thin layer of wall care putty to obtain smooth finish complete all as specified and directed. |
| 31 | M&L for preparation of new plastered wall surfaces and including applying two coats of cement base paint over a coat of cement primer complete all as specified and directed. |
| 32 | M&L for preparation of old painted wood and wood based surfaces of any description, not otherwise described, over 10 cm width or girth and applying one coat of Synthetic enamel paint (Ordinary tint) complete all as specified and directed. |
| 33 | M&L preparation of old decorated steel surfaces of any description, not otherwise described over 10 cm width or girth and including applying one coat of synthetic enamel paint complete all as specified and directed. |
| 34 | M&L preparation of new steel surfaces of any description, not otherwise described over 10 cm width or girth and including applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 35 | Demolition of brick work or stone/ boulder masonry, built in cement mortar including all quoins, pillars etc. complete all as specified and directed. |
| 36 | Demolition of cement concrete (un-reinforced) in ground floor and paving not exc. 15 cm thick (Below or above ground level) complete all as specified and directed. |
| 37 | S&F MCCB 4P 100 Amps 415V ,50 Hz ,breaking capacity 16 KA Including taking down unsvericeable one complete all as specified and directed. |
| 38 | S&F MCCB 4P 160 Amps 415V ,50 Hz ,breaking capacity 25 KA, type DU 250 C, Including dismantling/taking down unsvericeable one complete all as specified and directed. |
| 39 | S&F MCCB 4P 200 Amps 415V ,50 Hz ,breaking capacity 36 KA, type DU 250 C, Including dismantling/taking down unsvericeable one complete all as specified and directed. |
| 40 | S&F MCCB 4P 250 Amps 415V ,50 Hz ,breaking capacity 36 KA, type DU 250 C, Including dismantling/taking down unsvericeable one complete all as specified and directed. |
| 41 | S&F MCCB 4P 400 Amps 415V ,50 Hz ,breaking capacity 36 KA, type DU 250 C, Including dismantling/taking down unsvericeable one complete all as specified and directed. |
| 42 | Supply & fixing of copper strip 20x3.15 mm with saddles and fixing screws etc. for roofconductors and down conductors above ground complete all as specified and directed. |
| 43 | M &L ofEarthingwith galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm thick, buried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below ground level connected using galvanised iron earth lead wire 4 Sqmm as earthing electrode by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe (medium grade) and other end connected to earthing test point as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C both ways andsuitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth up to a distance not exceeding 50 Mtr etc all as shown on electrical plate No. 5 of MES Schedule Part-I complete including testing on completion. On testing after completion if the desired earth resistance is not obtained the earthing will be made again by the contractor at no additional cost and including dimantling complete all as specified and directed. |
| 44 | M&L earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised earth lead of GI strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate No. 3 connected to earthing test point and including dismantling complete all as specified and directed. Note :- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:1.5:3, type A1 cover slab, 50 mm thick reinforced with 8 mm dia TMT bar @ 140 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, 20 mm bore medium grade GI watering pipe, 15 mm bore GI light grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc. |
| 45 | M&L for Earthing complete with copper earth plate electrode 60cm x 60cmx 3.15 mm thick electrode buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the earth plate not less than 1.5 meter below normal ground level connected to copper strip 20 x 3 mm as earthing lead by means of bolt and nut, check nuts and washers of brass material all as shown in electrical plate No 3 of MES Schedule part I with and including excavation & earth work in any type of soil, providing charcoal dust and common salt upto 15 cm above top edge of earth plate, construction of PCC pit in cement concrete 1:3:6 type C-1 with 40 mm thick RCC 1:2:4 type B-1 reinforced with 8 mm dia MS deformed bars @ 100mm center to center both ways watering arrangement with funnel and wire mesh and watering pipe of 20mm dia GI light grade and 40mm dia medium grade pipe for earth lead protection and testing on completion complete all as specified and directed. |
| 46 | Supply and fixing earthing continuty conductor or main earthing lead fixed to pole or burried in ground or at any other situation for loop earthing extra as requiredof GI wire 4 sqmm complete all as specified and directed |
| 47 | Supply and fixing earthing continuty conductor or main earthing lead fixed to pole or burried in ground or at any other situation for loop earthing extra as requiredof GI strip 25x4 mm complete all as specified and directed |
| 48 | M&L test point terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25 mm drilled and screwed including 3 nos. 8 mm dia 25 mm long hex. head screw complete all as specified and directed. |
| 49 | S & F of Pole mounted Junction box with terminals of size 182 x 180 x 111 mm, made of high quality thermoplasticpolycarbonate, dust & jet water proof, chemical, acid corrision, impact IK-09, insulated & shock proof IP 66, grey RAL 7035 color with internaly embedded gasket (PUR) , along with coverand metric knockout all sides including back of the base must including terminals 4Nosincluding fixing arrangement with MS flat of size40X4mm , nuts , bolt and washers and MCB SP 6-32 Amps 01 No including taking down old unsv complete all as specified and as directed. |
| 50 | M&L for painting steel tubular poles 9 mtr height with one coat of aluminium paint from bottom to topincluding cross arms, GI brackets etc after cleaning and preparing the surface and marking alternate yellow and black strips 30 cm height total 5 Nos with two coats of synthetic enamel point over a coat of primer complete all as specified and as directed. |
| 51 | M&L for painting of PCC poles 9 mtr height with one coat of aluminium paint from bottom to topincluding cross arms,GI brackets etc after cleaning and preparing the surface and marking alternate yellow and black strips 30 cm height total 5 Nos with two coats of synthetic enamel point over a coat of primer complete all as specified and as directed. |
| 52 | Boring/Drilling (horizontally) manually under 2m deep in soil below existing road suitable for passing GI tubing of 40 to 80 mm bore complete all as specified and directed. |
| 53 | Supply and fixing of GI tubing light grade 40mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor / wall including taking down old unsv complete all as specified and directed. |
| 54 | Supply and fixing of GI tubing light grade 50mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor / wall including taking down old unsv complete all as specified and directed. |
| 55 | Supply and fixing of GI tubing light grade 80mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor / wall including taking down old unsv complete all as specified and directed. |
| 56 | Supply and fixing of GI tubing light grade 100mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor / wall including taking down old unsv complete all as specified and directed. |
| 57 | Supply, laying testing and commissoning in replacement of cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) LT Cable with stranded aluminium conductor 1100 volts grade of size 16 sqmm 4 core including taking down old unsv complete all as specified and directed. |
| 58 | Supply, laying testing and commissoning in replacement of cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) LT Cable with stranded aluminium conductor 1100 volts grade of size 25 sqmm 4 core including taking down old unsv complete all as specified and directed. |
| 59 | Supply, laying testing and commissoning in replacement of cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) LT Cable with stranded aluminium conductor 1100 volts grade of size 50 sqmm 3.5 core including taking down old unsv complete all as specified and directed. |
| 60 | Supply, laying testing and commissoning in replacement of cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) LT Cable with stranded aluminium conductor 1100 volts grade of size 95 sqmm 3.50 core including taking down old unsv complete all as specified and directed. |
| 61 | Supply, laying testing and commissoning in replacement of cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) LT Cable with stranded aluminium conductor 1100 volts grade of size 150 sqmm 3.50 core including taking down old unsv complete all as specified and directed. |
| 62 | Supply, laying testing and commissoning in replacement of cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) LT Cable with stranded aluminium conductor 1100 volts grade of size 240 sqmm 3.50 core including taking down old unsv complete all as specified and directed. |
| 63 | Supply and fixingin replacement of energy saving LED flood light 150 watt 230 V AC outdoor type, thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant,die cast aluminium housing ,lumen efficacy of minimum 120 Lm/W,min surge protection of 10 kV including taking down old unsv complete all as specified and as directed. |
| 64 | Supply and fixingin replacement of energy saving LED flood light 200 watt 230 V AC outdoor type, thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant,die cast aluminium housing ,lumen efficacy of minimum 120 Lm/W,min surge protection of 10 kV including taking down old unsv complete all as specified and as directed. |
| 65 | S&F of LT 1100 Volt heat shrinkable straight through jointing kit for XLPE cable with jointing material and accessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 25 to 50 sqmm including taking down old unsv complete all as specified and as directed. |
| 66 | All as per item No. 72.00 above but for aluminium conductor cable of size 70 to 120 sqmm including taking down old unsv complete all as specified and as directed. |
| 67 | All as per item No. 72.00 above but for aluminium conductor cable of size 150 to 185 sqmm including taking down old unsv complete all as specified and as directed. |
| 68 | All as per item No. 72.00 above but for aluminium conductor cable of size 240 to 300 sqmm including taking down old unsv complete all as specified and as directed. |
| 69 | Supply and fixing in repair Switch air break, gang operated triple pole mechanically operated mounted on with 9 insulator and steel frame with operating mechanism working from ground level current rating upto 400A, 11000 V grade having nine insulators, vertical type including dismantling of existing air break gang operated switch and removalthe same from site complete all as specified and directed. |
| 70 | Supply and fixing in repair expulsion drop out fuse carrier assembly outdoor type 400 Amps capacity including fuse elementup to 60 Amps and insulator suitable for HT 11 KV completeand dismantling of existing fuse carrier assembly and removalthe same from site completeall as specified and as directed. |
| 71 | M& L for on site repair of front and rear doors LT Panel of size 500mmx 500mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 72 | M& L for on site repair of front and rear doors LT Panel of size 1000mmx 800mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 73 | M& L for on site repair of front and rear doors LT Panel of size 1200mmx 800mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 74 | M& L for on site repair of front and rear doors LT Panel of size 1500mmx 1000mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 75 | M& L for on site repair of front and rear doors LT Panel of size 2000mmx 1000mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 76 | S&F in repairs of glow sign board printed on flex sheet, size of board not less than 2.0 mtr x 1.0x 0.20 mtr with contents written as details of power house in and the size of the letter not less than 20mm height, on 6mm thick polysheet on front and GI sheet backing on rear, sides top and bottom including fabrication with necessary clamps and necessary arrangement including providing 10 nos 20 watt LED tubes with necessary wiring with copper wire, duly fixed on GI pipe of 40 mm dia (04 legs) with PCCfor fixing on ground complete all as specified and directed. |
| 77 | Supply and installation of advance encapsulated compound based CPRI tested maintenance free,pipe-in-pipe technology upgrade (zinc & alloy coated),zinc coated (80-100) microns with pure zinc (99.9%) & alloy coating (200-250) microns and this system confirming to IS 3034.The outer and inner pipe of model ASEEL 19 should be 48.3 mm & 26.4 mm dia,3 mtrs length ,zinc coated with additional special alloy coating 300 mm on the topside for additional protection of the terminal.The annular space between the pipes being filled up with compact crystalline conductive compound.The compact fill (CF) mixture which is machine pressed in the pipes should not disintegrate or collapse when outer pipe corrodes.The inner pipe should be extended with terminals for connectivity the job includes digging the pits and refilling the same by Electrodite back fill compound (ground enhancer),the BFC should be eco friendly it should not contain environmentally hazardous material/metal having ROHS certification from NAB accredited lab.The earth pit should be provided with a FRP earth pit cover for protection and safe guard of terminals.In areas where soil condition is bad ,good earth is to be arranged to fill the excavated pits by mixing the same with BFC 2 or 4 bags (as per soil condition) extra per pit/unit.As the earth electrode is the main component of the earthing system which is in direct contact with the ground and thus provides a means of releasing or collecting earth leakage currents.The material should have good electrical conductivity & anti corrosion property in wide range of soil conditions.(All the above given dimensions may vary +/- 1 mm) .Make :- ASHLOK MODEL-ASEEL-19,3 mtr length (ZC & AC) or equivalent |
| 78 | Supply and fixing in repair of busbar chamber 4 way of current rating 200 Amps, wall mounted made of ETP grade copper incl cable connection with suitable aluminum lugs & glands complete all as specified & as directed.Make :- Havells Cat No IHBC020004/Legrand/ABB |
| 79 | Supply and fixing in repair of busbar chamber 4 way of current rating 400 Amps, wall mounted made of ETP grade copper incl cable connection with suitable aluminum lugs & glands complete all as specified & as directed.Make :- Havells Cat No IHBC020004/Legrand/ABB |
| 80 | Supply and fixing in repair of Manual Changeover switch 200 Amps ,4 Pole ,I-O-II operation supplied with bridging bars,extended shaft and IP65 pistol type handle to be fixed in existing slot of the panel and make electric connection complete all as specified and as directed.Make :- ABB Cat No OT200E04CP/Legrand/Havells |
| 81 | Dismantling and taking down old unserviceable LT busbar panel and Supply, installation, testing and commissioningof LT busbar Panel board not less than 0.5m x 0.6 m x0.50 m , outdoor cubical type factory made (CPRI approved) with canopy,double door , front& back both side openable type fixed with Hinges and locking arrangement with Aldrop latches , fabricated of CRCA sheet , inner sheet 2.0 mm thick hinged type door for individual MCCBs and outer door 3.15 mm thick,rubberised gasket, supported on 50x 50 x 6 mm angle iron and Tee section frame dust and vermin proof complete with aluminium bus bar 4 Nos, 400 Amps rated capacitymounted on porcelain insulators totally enclosed chamber for protection 3 phase 415 volt with suitable capacity aluminium bus bar /PVC insulated copper cable control wiring duly mounted on PCC foundation with suitable size of bolts, nuts & wahsers with danger notice plate. Panel boardshall be powder coated and angle iron frame painted with black synthetic enamel paint over a coat of red oxide primer complete, connecting existing cables with suitable size glands and lugs to accommodate complete all as specified & as directed. |
| 82 | Dismantling and taking down old unserviceable LT panel board and Supply, installation, testing and commissioningof Panel board not less than 1.5m x 1.2 m x0.60 m , outdoor cubical type factory made (CPRI approved) ,double door , front& back both side openable type fixed with Butt Hinges and locking arrangement with Aldrop latches , fabricated of CRCA sheet , inner sheet 2.0 mm thick hinged type door for individual MCCBs and outer door 3.15 mm thick,rubberised gasket, supported on 50x 50 x 6 mm angle iron and Tee section frame dust and vermin proof complete with aluminium bus bar 4 Nos, 600 Amps rated capacitymounted on porcelain insulators totally enclosed chamber for protection 3 phase 415 volt with suitable capacity aluminium bus bar /PVC insulated copper cable control wiring duly mounted on PCC foundation with suitable size of bolts, nuts & wahsers and connecting all I/C & O/G existing cables. Panel boardshall be powder coated and angle iron frame painted with black synthetic enamel paint over a coat of red oxide primer complete, connecting existing cables with suitable size glands and lugs to accommodate and includingthe following :- |
| 83 | INCOMING :-(a) Aluminium busbar 600 Amps rated capacity-04 Nos.(b) MCCB 400 Amps, 4 pole, 415 volt, 36 KA thermal &magnetic release adjestable type - 01 No (c) Spreader Link -02 SetsOUTGOING :-(a) MCCB 250 Amps,4 pole,415 volt 25 kA thermal &magnetic release adjestable type - 02 Nos (b) MCCB 200 Amps, 4 pole,415 volt 25 kA thermal &magnetic release adjestable type - 01 No(c) MCCB 160 Amps, 4 pole,415 volt 16 kA thermal &magnetic release adjestable type - 01 No(d) Spreader Link -06 Sets(e) MCB TPN 63 Amps,415 Volt \"B\" curve -02 Nos(f) MCB 6 Amps, 415 Volt, \"B\" curve -03 Nos(g) Indication lamp Neon/ LED type (set of three) - 01 Set(h) Danger Notice plate - 01 No.(i) Panel control wiring with 16 sqmm s/c copper wire complete- 01 Job. |
| 84 | Dismantling and taking down old unserviceable LT busbar panel and Supply, installation, testing and commissioningof LT busbar Panel board not less than 0.5m x 0.6 m x0.50 m , outdoor cubical type factory made (CPRI approved) with canopy,double door , front& back both side openable type fixed with Hinges and locking arrangement with Aldrop latches , fabricated of CRCA sheet , inner sheet 2.0 mm thick hinged type door for individual MCCBs and outer door 3.15 mm thick,rubberised gasket, supported on 50x 50 x 6 mm angle iron and Tee section frame dust and vermin proof complete with aluminium bus bar 4 Nos, 600 Amps rated capacitymounted on porcelain insulators totally enclosed chamber for protection 3 phase 415 volt with suitable capacity aluminium bus bar /PVC insulated copper cable control wiring duly mounted on PCC foundation with suitable size of bolts, nuts & wahsers with danger notice plate. Panel boardshall be powder coated and angle iron frame painted with black synthetic enamel paint over a coat of red oxide primer complete, connecting existing cables with suitable size glands and lugs to accommodate complete all as specified & as directed. |