| 1 | Laying (Relaying)of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. (i)Upto 35 sq. mm |
| 2 | Laying (Relaying)of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. (i)Above 95 sq. mm and upto 185 sq. mm |
| 3 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 4 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. i) 3½ X 25 sq. mm (28mm) |
| 5 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. i) 3½ X 70 sq. mm (38mm) |
| 6 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. i) 3½ X 95 sq. mm (28mm) |
| 7 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. i) 3½ X 185 sq. mm (57mm) |
| 8 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (i) 3½ X 35 sq. mm |
| 9 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (i) 3½ X 70 sq. mm |
| 10 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (i) 3½ X 150 sq. mm |
| 11 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (i) 3½ X 185 sq. mm |
| 12 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 13 | Earthing with G.I. earthing Electrodes 2 metre long, 25 mm dia including accessories, and providing connection with GI/MS poleby existing 25mm X 6 mm GI strip as required. |
| 14 | Supplying ,installation,testing and commissioning ofcubical type padestal mounted outdoor Junction Feeder Pillar of size 500mmX500mmX400mm made out of 1.6 mm. thickMS sheet and mounted on 35mm x 35mm x 5mm thickangle iron frame i/c same size of angle 04 nos. legs 500mm lenght erected in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) foundation including excavation & refilling,hinged front & back doors with locking arrangements,with provision of fixing of glands at the bottom, antirust design, air ventilation grooves, water drop proofing arrangement ,insluators,earthing studs & connection with 25mm x 5 mm 2 mtr GI strip,nuts bolts etc.as required including connections,interconnetions , painting with primer & finish paint with synthetic enamel paint , 04 nos aluminium bus bar strip suitable for 160 A,415 V capacity with suitable insulated support for aluminium bus bar complete as required. |
| 15 | Supplying and laying of 3.5 X 70 Sqmm one number PVC insulated and PVC sheathed / XLPE armoured Aluminium cable of 1.1 KV grade toIS :1554 (p-1)/ IS: 7098(P-1) of above size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering etc. as required. |