Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 17-02-2025 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 24-02-2025 |
| Sl. No. | Item Description |
| 1 | Dismantling and taking down UNSV LED street light/security/flood lights upto 90 watt after disconnection electric supply and fix again after repairing of unsv AC/DC drivers incl proper connections complete all as specified and directed.Note : (i) Cost of repair and driver is incl in quoted rate.(ii) If repair is not possible then replacement of street/security light will be measured and paid seperately under relevent items. |
| 2 | Dismantling and taking downUNSV LED street light/security/flood lights upto 200 watt after disconnection electric supply and fix again after repairing of unsv AC/DC drivers incl proper connections complete all as specified and directed.Note : (i) Cost of repair and driver is incl in quoted rate.(ii)Ifrepair is not possible then replacement of street/security light will be measured and paid seperately under relevent items. |
| 3 | Taking down old unsv street/security lights and Material and labour for new LED street light fittings of 45 watt system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, TOP opening separate driver compartment with frame, IP 66 protection suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy>120lm/W and system efficacy 90 lm/w 240 volts AC, 50 Hz CRI>70% operating voltage range 160 V-270 V, power factor>0.95, working temperature range -20 degree C to 60 degree C, built in surge protection of more than 5kv with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting, welding, drilling holes, nut bolts, washer complete all as specified and directed.Make:- Havells/Bajaj/Crompton/Wipro |
| 4 | All as per Srl Item No 3.00 here in before but for 60 Watt LED street light. |
| 5 | All as per Srl Item No 3.00 here in before but for 72/75 Watt LED street light. |
| 6 | Supply and fix in replacement or passing through pipe, 1100 volts grade heavy dutyPVC insulated flat twin core cable of size 4 sqmm nominal cross section with connection in sintex box flood light complete all as specified and directed.Note: PVC pipe will be measured and paid seperately under relevent items. |
| 7 | Supply and fixin replacement of rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. Note : PVC pipe will be clamed at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates complete all as specified and directed. |
| 8 | Material & Labour for fixingin replacement of new street light bracket made out of GI pipe medium grade 25 mm bore suitable to fit with LED street light approx length not less than 120cm bent to shape including new clamps made of MS flat of size 30x4 mm thick including cutting, welding holes, nut, bolts washers etc including two coat of aluminium paint over one coat of red oxide primer on MS work complete all as specified and directed. |
| 9 | Supply, fixing and testing in replacementof auto day/ night on and off photocell. LDR sensor switch 6amps for lighting on and off photocell, LDR sensor switch 6amps for lighting on and off water proof 220volt 50HZ, AC supply, model No Quick Sense QS-301 complete with all accessories internally pre-wired including connection with 1.5Sqmm copper conductor from main supply to sensor, sensor to fittings complete all as specified and directed. |
| 10 | Excavation in trenches n.exc 1.5 Mtr wide and n,exc 1.5 Mtr in depth in loose/soft soil and getting out for underground cable/erection of poles, stays etc complete all as specified and directed. |
| 11 | Earth work in excavation by mechanical means (Hydraulic excavator) means over areas (exceeding 30 cm in depth,1.5 m in width as well as 10 sqm on plan) in any type of soil including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5m complete all as specified and directed. |
| 12 | All as per Srl Item No 11.00 here in before but exceeding 1.5 mtr deep but not exc 3.0 mtr deep. |
| 13 | Material & Labour for sand cushioning for cables with river washed sand and punning to provide required cover as per SSR part I complete all as specified and directed. |
| 14 | Supply and laying bricks common burnt clay sub classs \"B\" old size for cable protection complete all as specified and directed. |
| 15 | All as per Srl Item No 14.00 here in before here in before here in before but except bricksNote : Old bricks retrieved from item No 31 here in after shall be used. |
| 16 | Material & labour for cement concrete in foundations, filling and mass concrete PCC as foundation to poles, type D2, 1:4:8 using 40 mm graded stone agregate as foundations to poles complete all as specified and directed. |
| 17 | Material & labour for Cement concrete, filling and mass concrete, PCC type C2, 1:3:6 using 20 mm graded aggregate complete all as specified and directed. |
| 18 | Material & labour for cement concrete as coping to poles, PCC type B1, 1:2:4 using 20 mm graded stone aggregate complete all as specified and directed. |
| 19 | Returning, filling in (Soil) including spreading, levelling, watering and well ramming in layers not exc 25CM thicklayers complete all as specified and directed. |
| 20 | Removal of excavated material n,exc50 Mtr away and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 21 | Supply & erection in replacement of Prestressed Concrete Pole 9.0 mtr long in true vertical position 102x172 mm at top 102x279 mm at bottom class-10 incl providing black and white radium tape strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip complete all as specified and directed.Note: Earth work and PCC shall be measured and paid seperately(ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost. |
| 22 | Supply & erection in replacement (in true vertical position) Steel tubular swaged poles complete with cast iron base plate, finial taper plug bolts, nuts & screws all as specified of type 410 SP-31 ( 9.0 mtr length)complete all as specified in IS 2713 (Part-II) 1980 including one coat of red oxide primer and two coats of aluminium paint to exposed surfaces incl providing of two coats of black and white radium tape strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip and with black bituminus paint for embedded portion of pole complete all as specified and directed. Note: Earth work and PCC shall be measured and paid seperately(ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost. |
| 23 | Supply and fixing in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4.0 x 10-50 Sqmm complete all as specified and directed. |
| 24 | Supply and fixing in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as specified and directed. |
| 25 | Supply and fixing in replacementindoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-300 Sqmm complete all as specified and directed. |
| 26 | Supply and fixing in replacementindoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.50 x 400 Sqmm complete all as specified and directed. |
| 27 | Supply and fixing in replacementstraight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4 x 25-50 Sqmm complete all as specified and directed. Note:- Earth work will be measured and paid seperately. |
| 28 | Supply and fixing in replacementstraight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as specified and directed. Note: Earth work will be measured and paid seperately. |
| 29 | Supply and fixing in replacementstraight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-400 Sqmm complete all as specified and directed. Note: Earth work will be measured and paid seperately. |
| 30 | Material & Labourfor drilling hole of any size manully as per site requirement, drilling for laying pipes under the road for crossing electrical cables complete all as specified and directed.Note : Pipe will be measured and paid for seperately. |
| 31 | Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, watt etc complete all as specified and directed. |
| 32 | Supply, laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 16 sqmm 4.0 core laid in trenches/ on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall etc complete all as specified and directed.Note : (i) Earth work, sand , bricks removing , returning filling Aluminium thimbles/lugs will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates(iii)All equiments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost. |
| 33 | All as per Srl Item No 32.00 here in before but for 3.5 core 25 Sqmm. |
| 34 | All as per Srl Item No 32.00 here in before but for 3.5 core 35 Sqmm. |
| 35 | All as per Srl Item No 32.00 here in before but for 3.5 core 50 Sqmm. |
| 36 | All as per Srl Item No 32.00 here in before but for 3.5 core 70 Sqmm. |
| 37 | All as per Srl Item No 32.00 here in before but for 3.5 core 95 Sqmm. |
| 38 | All as per Srl Item No 32.00 here in before but for 3.5 core120 Sqmm. |
| 39 | All as per Srl Item No 32.00 here in before but for 3.5 core 150 Sqmm. |
| 40 | All as per Srl Item No 32.00 here in before but for 3.5 core 185 Sqmm. |
| 41 | All as per Srl Item No 32.00 here in before but for 3.5 core 240 Sqmm. |
| 42 | All as per Srl Item No 32.00 here in before but for 3.5 core 300 Sqmm. |
| 43 | All as per Srl Item No 32.00 here in before but for 3.5 core 400 Sqmm. |
| 44 | Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, will etc and locate the fault, rectify, the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminium conductor heavy duty 1100 volts including and testing for any size complete all as specified and directed.Note:- Excavation/earth work & sand cushioning, brick and joint shall be measured & paid for seprately. |
| 45 | Supply and fixing in replacement ofstay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 complete all as specified and directed.Note- The quoted rate shall include the cost of loop type insulator, stay clamps, excavation, PCC, stay wire, stay bow, turn buckle, nuts etc complete all as specified and directed. |
| 46 | Material & Labour in replacement for cross arms,bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape of size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed. |
| 47 | Material & Labour in replacement for shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mm complete all as specified and directed. |
| 48 | Material & Labour in replacement for pintype insulator porcelain vitreous white or brown 1100 volts grade100 mm hight and 65 mm dia with GI spindle two washer and one GI nut complete all as specified and directed. |
| 49 | Dismantling and taking down old unserviceable ACSR conductor incl cutting, welding complete all as specified and directed. |
| 50 | Material & Labour for aluminium conductor steel reinforced (ACSR) including fixing, stretching on poles and proper noseling with binding wire with insulator of any size as required at site complete all as specified and directed. |
| 51 | Material & Labour in replacement for 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as specified and directed. |
| 52 | Dismantling and taking down old u/s earthing and material & labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick buried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth strip of size 25x4 mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, cover 50mm thick RCC 1:2:4 type B-1 using 8mm for steel bars @ 10 cm C/C both ways, 20 mm bore medium grade GI protection pipe, watering pipe 20 mm bore nedium grade , funnel, wire mesh, also including earth work, common salt, charcol dust complete all as specified and directed.Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way.(ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with standgrouted in PCC.(iii) On testing after completion if the desired earth resistanceis more than 2Ώthe earthing will be redone at no extra cost |
| 53 | Dismantling and taking down old u/s earthing and material & labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick buried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth wire of size 4mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, cover 50mm thick RCC 1:2:4 type B-1 using 8mm for steel bars @ 10 cm C/C both ways, 20 mm bore medium grade GI protection pipe, watering pipe 20 mm bore nedium grade , funnel, wire mesh, also including earth work, common salt, charcol dust complete all as specified and directed.Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way.(ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with standgrouted in PCC.(iii) On testing after completion if the desired earth resistanceis more than 2Ώthe earthing will be redone at no extra cost |
| 54 | Material & Labour for fixing in replacement GI tubing 50 mm bore light grade, on poles, on walls, under floors, road crossing as reqd at site complete all as specified and directed.Note : Clamps, Nut bolts, saddle etc will be measured and paid seperately. |
| 55 | All as per Srl Item No 54.00 here in before but 80 mm dia. |
| 56 | Supply and fixing in replacement MCCB TPN 400 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection complete all as specified and directed. |
| 57 | Supply and fixing in replacement MCCB TPN 630 Amps, 415 Volts, 50 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection complete all as specified and directed. |
| 58 | Supply and fixing in replacement MCCB TPN 250 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete all as specified and directed. |
| 59 | Supply and fixing in replacement MCCB TPN 160 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete all as specified and directed. |
| 60 | Supply and fixing in replacement MCCB TPN 100 Amps, 415 Volts, 16/18 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete all as specified and directed. |
| 61 | Detecting of fault in cable HT/LT with fault locator equipment which is capable to supply as per cable of HT/LT (11 KV/430 Volts) serviceable to cable with Straight throughjoint complete all as specified and directed.Note :-(a)The fault which is detected through cable fault locater will only be paid under this item (b)Charges of Cable fault locator and DG set including transportation charges deemed to be included in the quoted rate.(c)Earth fault locator will be provided by the contractor for even single fault delay on this account will be acceptable otherwise penalty will levied Rs 500/- per day. (d)Necessary testing of cable after making jointdeemed to be included in the cost of relevent item.However necessary earth work ,cable cutting, joint making will be paid under relevant item. |
| 62 | Supply and fixing in replacementLT line separators 1100 V grade PVC spacer to separate LT conductor from each other 5 line as per IS complete all as specified and directed. |
| 63 | Supply and fixing in replacementLT line separators 1100 V grade PVC spacer to separate LT conductor from each other 4 line as per IS complete all as specified and directed. |
| 64 | Re-streteching existing/retrieved ACSR conductor on LT pole and building conductor on insulator properly using new binding wire/jumper wire complete all as specified and directed.Note : (i) Each Run of line conductor shall be measured & paid for separetly. |
| 65 | Material and labour in replacementfor fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 50 sqmm incl dismantling old thimbles of any type complete all as specified and directed. |
| 66 | Material and labour in replacement for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-185sqmm incl dismantling old thimbles of any type complete all as specified and directed. |
| 67 | Material and labour in replacement for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400 sqmm incl dismantling old thimbles of any type complete all as specified and directed. |
| 68 | Material & Labour forshifting oftransformers/ RMUs/ Stabilizers/ VCBs/ LT panels/ HT/LT poles / ACBs/ other mterials from one to another site/Power house/ store by providing crane/hydra/JCB as required at site complete all as specified and directed. |
| 69 | Material & Labour for painting cleaning and repair of LT panel size upto 0.6 x 0.6 x0.6 mtr after cleaning of surface including removing rusted particles removing dust tightening nut, bolts welding and painting on complete panel two coats of synthetic enamel aluminium paint over a coat of red oxide primer including stand complete all as specified and directed.Note : (i)Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate (ii)Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates. |
| 70 | Material & Labour for painting cleaning and repair of LT panel size upto 1.2 x 1.2 x0.6 mtr after cleaning of surface including removing rusted particles removing dust tightening nut, bolts welding and painting on complete panel two coats of synthetic enamel aluminium paint over a coat of red oxide primer including stand complete all as specified and directed.Note : (i)Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate (ii)Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates. |
| 71 | Material & Labour for surface cleaning of steel tubular poles LT 9 mtrs long including removing rusted particles , painting withtwo coats of synthetic enamelaluminium paint over a coat of red oxide primer including stand cross arms, bracing, supports,clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl reparing and painting on coping with cement base white paint complete all as specified and directed.Note : (i)The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge.(ii)The quoted rates shall including the reparing of coping with cement / PCC |
| 72 | Material & Labour for cement base paint for Prestressed Concrete Pole 9 mtr includingblack & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide primer including cross arms bracing supports, clamps, eye hooks, security light bracket, clamp etc inclincl reparing and painting on coping with cement base white paint complete all as specified and directed.Note : (i)The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge.(ii)The quoted rates shall including the reparing of coping with cement / PCC |
| 73 | Material & Labour for spraying chemical (Round up) on area to remove unwanted vegitation/grass at various locations complete all as specified and directed. |
| 74 | Supply and fixing in replacement of old unsv, new On load change over switch with sheet steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed. |
| 75 | Supply and fix inreplacementof Lithium based Energy Efficient Integrated Solar Street Light of 25 Watt” in Single FRP body with duly Polyurethane coating (Camouflage color) , encases with Monocrystalline Solar PV Panel of 64/66Wp , Lithium Battery 11.1/12.8V, 33.0AH with inbuilt BMS, IP 65, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700°K - 6500°K, Microcontroller based charge controller cum driver, automatic dimming function (first four hours at full brightness & rest of the time at lower light level with PIR Motion Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10°C to (+)55°C, weight not more than 16-18kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections. Firm should provide Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS compliant including tubular pole 4-6 mtr height with bottom base plate 200x200x12 mm , outdoor dia not less than 65 mm with heavy duty GI pipe or steel thickness 3mm and suitable arrangement to mount solar light as directed on pole including foundation PCC 1:3:6 type C-1using 20mm graded crushed stone aggregate and erection as per manufacturer drawing, providing synthetic enamel aluminium paint over one coat of red oxide complete all as specified and directed. Make:-Surya/ Halonix/Phillips/Bajaj/wipro/havells |
| 76 | Taking down old unsv switches and Supply & fix of Automatic street light control with infrared sensor based NATURE SWITCH and VOLTAGE MONITORING SYSTEM (VMS) . Three phase loadof 8 KW for automatic switching of street lights.Nature switch operation should be based on Natural light Lux level . Required illuminance level for switching ON is < 30 Lux and for switching OFF < 10 Lux. The sensor should also have part night operation facility of min, 4 hrs to max 12 hrs, VMS should have adjustable over & under voltage trip level and protection against phase loss, Beutral loss & phase reverse incl power contractors (63Amos) and incoming-outgoing MCB rating of 63 Amps& main load circuit wiring (Copper) of minimum 16 sqmm.The sensor, VSM power contractor, MCBs incl connected items should be enclosed in a pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade SMC junction box conforming to IP54. The circuit should also have provision for manual operation (i.e sensor & VMS by pass option) complete all as specified and directed.Model-Schneider/Havells/Legrand./Crompton/IndoAsianMake:(i) Nature switch : Kakatiya Energy Systems/Healer/Bajaj(ii)Power contractor - L&T / BCH/Schneider(iii)Voltage Controlling Device - L&T (IV) MCB- Hager/Schneider/L&T/Legrand, (v)Enclosure & circuit sheet - Sintex (shock proof , rust proof, termite proof, FR rade) (v)Circuit wiring-Polycab/FinolexNote:-(i) S S Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii)The sensor must have the warranty of min of 2 years. (iii)The test certificate and warranty cirtificate must be provided by supplier.(iv)Cost of marking description on the box is incl quoted rate. |
| 77 | Material & Labour for chemical spray (DC>2.26) in sealed container having container 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisum cleanese etc complete all as specified and directed. Make-WD40 |
| 78 | Material & Labour for rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 finished even and fair without using extra cement complete all as specified and directed. |
| 79 | Material & Labour for three coat of white cement base paint on new plastered surfaces of walls complete all as specified and directed. |
| 80 | Material & Labour for 18-20 mm thick Machine cut Kota stone slab in flooring on treads, landing laid over including 20 mm thick screed bed 1:4 jointed with grey cement slurry mixed with pigment to match the shade of slab including rubbing and polishing & demolition of existing complete all as specified and directed. |
| 81 | Material and labour for vibratory compactive,precast cement concrete rubber moulded, coloured ( except grey colour), interlocking designer paver blocksin dumble shape, comfirming to IS-15658-2006 of 60 mm thickness, M-35 grade, as in path, hardingstanding, etc laid over and including 25 mm compacted sand cushioning, including 75 mm thick PCC 1:4:8 type D-2 using 40mm graded crushed stone aggregate including surface excavationover area n. exc. 30 cm deep and averaging 15 cm deep and getting out in soft/loose soil and removing excavated soil exc. 50 mtr but n. exc. 250 mtr including demolition of existing paver blocks complete all as specified and directed. |
| 82 | Material & Labour for preparing oldplastered wall surfaces complete all as specified and directed. |
| 83 | Material & Labour for 3 coats of white cement base paint on old decorated wall surfaces complete all as specified and directed. |
| 84 | Comprehensive maint and servicing ofDG SET from 200 KVA to 400 KVA complete including draining out diesel from tank, cleaning the tank thoroughly and refilling the drained out diesel, drain out engine oil from the sump, flushing the sump thoroughly and filling the batteries with electrolite to maintain the required specific gravity of the batteries, applying the petroleum jelly on battery terminal polesand chargingup to required amperage, cleaning the entire DG set including all accessories as prescribed by Engr-in charge andchecking voltage, frequency,ampere, fuel, oil, coolantleveland exhuast leakage etc.Tightening all the bolts & nuts to the required torque etc. and testing as directed by Engineer In Charge and recording the test result complete all as specified and directed.Make : Cummins/ Kirloskar / Ashok Leyland etc, installed at MH powerhouses, MH Dental, AMN Depot Naraingarh, signal centre, Raina auditorium, butchery, Allenby PH etc. Notes:- (a)Contractor will carry out comprehensive maint and servicing through technically qualified staff having an experience of ten years atleast (b) Cost of spare parts replaced shall be measured and paid separately. (c) Engine oil shall be measured and paid separately- |
| 85 | All as per Srl Item No 84.00 here in before but for DG set upto 125 KVA |
| 86 | Draining out water from the radiator from DG set from 200 KVA to 400 KVA, Dismantling opening and taking out radiator from the foundation , Maintenance and Servicing of Radiator and cleanning the radiator thoroughly with cleaning agent to improve the efficiency of the radiator, welding / soldering / brazing of radiator for the undermentioned DG sets complete all as specified and directed.Notes:- (a) Contractor will carry out comrehensive maint and servicing listed in respective items through qualified tecnical staff only. (b) Contractor will gaurantee for one year from the certified date of completion for the repair work carried out. (c) Any fault occured during gaurantee period shall be rectfied by the contractor with out any extra cost to the department.(d) Coolant for radiator shall be measured and paid separately- |
| 87 | All as per Srl Item No 86.00 here in before but for DG set upto 125 KVA |
| 88 | Dismantling opening and taking down unserviceable fuel injection pump from DG set of cap 200 KVA to 400 KVA and transportation to civil wksp for repair, maintenance andservicing offuel injection pump (FIP) including phasing & caliberation of Fuel injection pump, replacement of injectors, nozzles etc if any found defective,and refitting the same in position for smooth and efficient functioning of FIP for the under mentioned DG sets complete all as specified and directed.Note : - (a) Repairs will be carried out from authorised workshop of manufacturer of DG set.(b) Contractor will give gaurantee for one year from the date of completion of the repair work carried out. Any fault occured during gaurantee period shall be rectified by the contractor with out any extra cost to the department. |
| 89 | All as per Srl Item No 88.00 here in before but for DG set upto 125 KVA |
| 90 | Maintenance and servicing of self starter 12/24Volt of DG setof capacity 200 KVA to 400 KVAinstalled at various installations and servicing/overhauling including replacing of worn out parts like solenoid switch, bearing, clutch, synchromesh gear, carbon brush, drive end plunger, rewinding the starter motor winding wth suitale size super enamelled copper wire including varnishing complete etc. and refitting the self starter in position for smooth functioning of DG sets and testing complete in all respect complete all as specified and directed.Note:- (a) Contractor will carry out comprehensive maint and servicing listed in respective itms through qualified technical staff only. (b) Any extra Spare except as mentioned will be measured and paid separately under relevant items of the schedule. |
| 91 | All as per Srl Item No 90.00 here in before but for DG set upto 125 KVA |
| 92 | Disconnecting & Removing the unserviceable fan belt from DG set upto 400 KVA & Supply & fixing new fan belt of same size as per sample and capacity complete all as specified and directed.Make :Fenner/LUCAS/TVS |
| 93 | Supply and filling engine oil 15W40 suitable for Kirloskar/Cummins engine including taking out existing oil complete all as specified and directed.Make: Castrol / Shell / Bosch / Kirloskar KOEL |
| 94 | Supply and filling coolantsuitable for Kirloskar/Cummins engine complete all as specified and directed. |
| 95 | Taking down unserviceable speed control unit supply and fixing new electronic speed control unit with necessary connection terminal suitable for up to 400 KVA DG sets complete all as specified and directed. Make Kirloskar /Greaves |
| 96 | Removing of defective engine oil control pressure switch supply & fix new engine oil control pressure switch suitable upto 400 KVA DG set of make Kirloskar / Cummins complete all as specified and directed. |
| 97 | Supply and fixing in replacementfuel filter element set suitable for 200 KVA to 400 KVA Kirloskar/Cummins as per existing engine complete all as specified and directed. |
| 98 | Supply and fixing in replacementfuel filter element set suitable for 100 KVA to 125KVA Kirloskar/Cummins engine complete all as specified and directed. |
| 99 | Supply and fixing in replacementoil filter element suitable for 200 KVA to 400 KVA Kirloskar/Cummins engine complete all as specified and directed. |
| 100 | Supply and fixing in replacementoil filter element suitable for 100 KVA to 125KVA Kirloskar/Cummins engine complete all as specified and directed. |
| 101 | Supply and fixing in replacementdiesel pipe from tank to diesel filter suitable dia both side factory fitted union/elbow heavy duty each 5 mtr in length complete all as specified and directed. |
| 102 | Supply and fixing in replacementdiesel pipe from filter to fuel pump suitable dia both side factory fitted union/elbow heavy duty each1.5 mtr in length complete all as specified and directed. |
| 103 | Supply and fixing in replacement diesel return pipe from pump to diesel tank suitable dia both side factory fitted union/elbow heavy duty each 5 mtr in length complete all as specified and directed. |
| 104 | Supply and fixing in replacement rubber hose pipe set suitable for 200KVA to 400 KVA Kirloskar/Cummins DG sets complete all as specified and directed. |
| 105 | Supply and fixing in replacement rubber hose pipe set suitable for 100KVA to 125KVA Kirloskar/Cummins DG sets complete all as specified and directed. |
| 106 | Supply and fixing in replacementair cleaner filter element suitable for 200KVA to 400 KVA Kirloskar/Cummins engine complete all as specified and directed. |
| 107 | Supply and fixing in replacement air cleaner filter element suitable for 100KVA to 125KVA Kirloskar/Cummins engine complete all as specified and directed. |
| 108 | Supply and fixing in replacementmaintenance free battery 12 volt 180 AH sealed in MS container by manufacturing unit, having inbuilt charge indicators for indicating the Main input, bty charging, bty full including three metre charging lead with three pin top complete all as specified and directed. Make: Exide / Ameron / Luminous |
| 109 | All as per Srl Item No 108.00 here in before as above but capacity 12 volt 65 AH. (Pulse lite) |
| 110 | Supply and fixingin replacement On load change over switch415 V, 4 pole, 630 Amps with sheet steel enclosure capacity fixed on DG Set incl necessary connection of cables from LT panels to change over switch complete all as specified and directed. |
| 111 | Supply and fixing in replacement On load change over switch415 V, 4 pole, 250 Amps capacity with sheet steel enclosure fixed on DG Set incl necessary connection of cables from LT panels to change over switch complete all as specified and directed. |
| 112 | Supply & fix in replacement Voltmeter analog type for voltage range of ( 0-500 V) complete with all accessories and wiring complete all as specified and directed. |
| 113 | Supply & fix in replacement Ammeter analog type for current range of ( 0-1000 Amps) as per matching to exixtingwith all accessories and wiring complete all as specified and directed. |
| 114 | Supply & fix in replacement Electronic timer suitable for AMF panel of DG Set 100KVA to 400 KVA as per matching to existing 230 V AC 50 Hz complete all as specified and directed. |
| 115 | Supply & fix in replacementcontrol relay contactors of MXO type operatable at AC/DC supplies with NO/NC add ON as per the existing site requirement complete all as specified and directed. |
| 116 | Supply & fix in replacement power contactor 400 Amps capacity suitable for AMF panel of DG sets as per matching to existing complete all as specified and directed. |
| 117 | Supply & fix in replacement of under voltage relay suitable for DG set of capacity 7.5 KVA to 75 KVA DG Sets complete all as specified and directed. |
| 118 | All as per Srl Item No 117.00 here in before but for 100 KVA to 280 KVA DG Sets. |
| 119 | All as per Srl Item No 117.00 here in before but for 400 KVA DG Sets. |
| 120 | Supply & fix in replacement of 3 Phase digital multi function meter with suitable accessories and fixing arrangement complete all as specified and directed. Make- L&T/ABB/Siemens/Legrand/C&S electricals. |
| 121 | Supply and fixing in replacement digital fuel flow meter upto 400 KVA DG sets incl all accessories complete all as specified and directed. |
| 122 | Supply and fixing in replacement of Megnetic pickup Sensor suitable for 32.5 to 400 KVA DG set connecting with panel circuit, starting and testing on load complete all as specified and directed. |
| 123 | Supply and fixing in replacement of Oil Pressure Sensor suitable for 32.5-400 KVA DG set connecting with panel circuit, starting and testing on load complete all as specified and directed. |
| 124 | Supply and fixing in replacement of Coolant TempetarureSensor suitable for 32.5 -400 KVA DG set connecting with panel circuit, starting and testing on load complete all as specified and directed. |
| 125 | Excavating in post holes each n.exc 0.5 cum getting out, in soft/loose soil complete all as specified and directed. |
| 126 | Supply & fix in replacementMild; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe 290 Gde E-165. complete all as specified and directed. |
| 127 | Supply only in replacementChain link Fencing MS galvanised fencing, any size or type complete all as specified and directed. |
| 128 | Fixing only in replacementchain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provision of binding wire complete all as specified and directed. |
| 129 | Supply & fix in replacementMild steel rounded bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed. |
| 130 | Material & Labour two coats of synthetic enamel paints on newsteel Surfaces exc 10cm girth over a coat of red oxide when unconnected with other painting or when painted in a different tint complete all as specified and directed. |
| 131 | Material & Labour for Brick work with sub class \"B\" bricks, straight or curved on plan exc 6m mean radius built in CM 1:6. including demolition of existing complete all as specified as directed. |
| 132 | Material & Labour in replacement of steel nuts, bolts, washers of any size required at site complete all as specified and directed. |
| 133 | Supply and fixing in replacement of rolled mild steel plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk)forming holes, with riveted, bolted or welded attachmentFe-290 (Gde E- 165)for existing LT panel doors/gates complete all as specified and directed. |
| 134 | Material & Labour for disconnecting and connecting of LT service wires and XLPE cables of any type and anysizefromLT panel, MCCBs, DBs, over head conductor, LT poles, street light timerincluding replacement of old unsv items such as nuts, bolts, thimbles, insulating seleaves and existing misc items etc, andafter cleaningand removing of corbon on cables end surface including removing rested particles removing dust tightening nut, bolts complete all as specified and directed.Note : (i)Cost ofall tools and ladder required for maintenanne of LT service wires and XLPE cable end connection and disconnection is incl in quoted rate (ii)Cost of misc items like nuts, bolts, thimbles, insulating sleaves etc if required are included in quoted rates. |
| 135 | Supply and fixing in replacement of contactor 3 pole 18 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed Make- BCH/L&T or equivalent as approved by GE |
| 136 | Supply and fixing in replacement of contactor two pole 25/40 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed Make- L&T/BCH or equivalent as approved by GE |
| 137 | Supply and fixing in replacement ofcontactor coil (230V)for MU series 25/40 Amps 2 pole contactorscomplete all as specified and directed Make- L&T (Cat No CS90793) or equivalent as approved by GE |
| 138 | Supply and fixing in replacement ofcontactor coil (240V)for freedom series 18 Amps 3 pole contactorscomplete all as specified and directed Make- BCH, Cat No CE15D1N-K or equivalent as approved by GE |
| 139 | Supply and fixing in replacement ofVMS (voltage monitoring series) in street light timer box, including all salient features such as selectabe under/over voltage trip levels, protection against phase loss & natural loss, protecotion against phase reversal and phase to phase unbalance (10%), voltage sensing principle and LED indications for power and fault conditions complete all as specified and directed. Make- L&T, Cat No SM500 or equivalent of GIC |
| 140 | Supply and fix in replacement of danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled red, with letters, figures and conventional skull and bones in signal white colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed |
| 141 | Supplying and laying in replacement of synthetic rubber insulated mats 25 mm thick for voltage upto 11 kv forlectrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 10m x 1m complete all as specified and directed. |
| 142 | Supply and fix in replacement of cradles, hexagonal/rectangular, earth continuity wire for GOD/LAfabricated with galvanised steel wire 3.15/4 mm dia complete all as specified and directed. |
| 143 | Material and labour in replacement for cable route indicator showing \"MES LT UG 1.1KV\" and route of cable with arrow (should be embossed or engraved) made of RCC in suitable shape and fixed in PCC block 1:3:6 type C-2 using 40mm graded aggregate including bricks works and excavation, size of route indicator 60cm x 30cm, 30cm below ground level and 30cm above ground level to show clear indication of cable including painting the complete slab with red paint and making the engraved/embossed letters/arrow with white paint complete all as specified and directed. |
| 144 | Supply and fixing in replacement of cable route indicator or cable joint mark for 1100 volts made out of mild steel 100mm dia 6mm thick plate welded to 40 x 40 x 6mm angle iron 60 cm long embeded in PCC 1:3:6 type C-2 (using 20mm graded stone aggregate) block of size of 150mm x 200mm x 200mm including applying two coats of synthetic enamel paint over a coat of redoxide primer on steel surfaces complete all as specified and directed. |
| 145 | Supply & fix in replacement of extended spreaders link should be installed both side with exisitng/new MCCBs 4P/3P of any capacity with existing LT panelscomplete all as specified and directed. |
| 146 | Dismantling and taking down rusted old UNSV LT Panel inner/outer covers and Material & Labour for outer covers of LT panel board of existing size, outer shell made out of 3.15 mm thich for outer panel and MS sheet with front openable having 60 % area with perspex sheet of minimum 5 mm thicness and back bolt openable lockable, powder coated painting having thickness not less than 100 microns complete all as specified and directed. |
| 147 | Supply and fixing in replacement of old unserviceable , new garden LED 8W bollard lightsmade in 3 parts (a) Spun aluminiumdome shaped top cover (b) Cylindrical opal acrylic diffuser (c ) GI pipe bottom housing the control gear for 8/9 W LEDs, Maintenance done by removing die cast aluminium housing, warm white luminaire,luminaire is wired with inbuilt driver with 4.5kV surge protection,Luminaire is provided with a base plate and fixing holes for directly mounting on the concrete pedestal, Finish in graphite grey powder coated IP65 complete all as specified and directed. Make-Havells/orient |
| 148 | Supply anf fixing in replacement of old unserviceable, new Aluminium Grill/diffuser for ICU of size as per ground and complete all as specified and directed. |
| 149 | Supply and fixing in replacement of fabrication of Kiosk box made out of fibre material complete with TPN ,aluminium bus and suitable for one number MCB (SP) including one No MCB (SP) 6 Amps 240 volts with glands for incoming & out going cable including fixing of flat iron clamps of size 20x4mm on PCC/Steel tubular polecomplete all as specified and directed.Make: Havells/Sintex. |
| 150 | Supply & fix Pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with selftapping screws incl taking down oldsheets complete all as specified and directed. Make : Tata/ Jindal/ JSW Steel |
| 151 | Supply, Install, Test and Commissioning of LT feeder piller box outdoor type in replacement of old unsv , fabricated ofsize 0.6x0.6x0.5M,out of 3.00 mm thick CRCA sheet, CPRI approved complete with powder coating with seven tank process mounted on MS angle frame of size 40x40x5mm, duly grounted with PCC using concrete 1:2:4 type B-1 reqd with the following:-(a) On load change over switch 4 pole, 415 volts 250 Amps in open execution - 01No |
| 152 | Supply, Install, Test and Commissioning of LT feeder piller box outdoor type in replacement of old unsv , fabricated ofsize 0.6x0.6x0.5M,out of 3.00 mm thick CRCA sheet, CPRI approved complete with powder coating with seven tank process mounted on MS angle frame of size 40x40x5mm, duly grounted with PCC using concrete 1:2:4 type B-1 reqd with the following:-(a) Copper bus bar 270 Amp, having four number hole of dia 11mm in each phase incl neutral ,with coloured heat shrinkable insulated sleeve 415 volts as per IS of suitable size mounted on DMC/epoxy insulator (not less than 50mmx50mm conicle type at a maximum interval of 500 mm - 01 Set.(b) MCCB FP 125 Amps 16 KA- 01 No For Main incoming(c)RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos(d)kWH multifunction meter - 01 No |
| 153 | Supply, installation, Test and Commissioning outdoor type LT feeder panel size 1.2Mx1.0Mx50Cm with out door type cubical feeder pillar box in replacement of old unsv , outer shell made out of 3.15 mm thick MS sheet inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm on PCC 1:2:4 type B-1 platform 45cm above the ground level and 30 cm below the ground level, frame factory fabricated with front and backopen able double door system complete suitable for 3 phase 4 wire 415 Volt, 50 Hz.a) TPN, Copper bus bar 600 Amps insulated with colour coded heat shrinkable sleeve.b) Incoming MCCB 4 pole 400 Amp 36 KAAdjustable type-01 Noc) Out going MCCB 4P 200 Amps 25 KA- 02 Nosd) Outgoing MCCB 4P 160 Amps 16 kA- 02 Nos (e) Indicator lamps RYB –01 Set(f) Multifunction KWh meter - 01 No(g) On load change over switch 4 pole, 415 volts 320 Amps in open execution. -01No |
| 154 | Note for item No 151.00 to 153.00:-(i)The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.(ii)Panel drawing shall be got approved before placing of order from GE.(iii) The bus bar connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated.(iv)Cost of making description on the front door as per direction of Engr-in-Charge is encl in quoted rate. (v) Cable will be entered in panles through gland.(vi) Cost of marking descreption on the front door as per direction of Engr-in-Charge |
| 155 | Note:-Amount of credit ofRs.160869.08 for retrieved materials is mentioned in Schedule of Credit of tender documents in pdf form which will be deducted offline while acceptance of tender. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail