| 1 | Excavation in trenches not exc. 1.50 m wide and not exc. 1.50 m in depth for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exc. 10 Sqm on plan and getting out in soft / loose soil complete all as specified and directed. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick in each layer as in soil complete all as specified and directed. |
| 3 | M&L for sand coushioning to UG cables (8cm deep before laying of cables and 15 cm over the cable) including spreading, levelling, well ramming in layers complete all as specified and directed. NOTE:- punned thickness of 18cm only will be considered for measurement and payment. |
| 4 | Removing Excavated soils not exc 50 Mand depositing where directed at a level not exc1.5 M above the starting pointcomplete all as specified and directed. |
| 5 | M&L PCC 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed. |
| 6 | M&L PCC 1:2:4 type B-1 (using 12.5 mm graded crushed stone aggregate) as in copings, bed plates, bed block for holdfasts, filling in pressed steel door frames, benching, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles and throating and including necessary formwork complete all as specified and directed. |
| 7 | M&L for Precast Reinforced Cement concrete 1:2:4 type B0 (Using 12.5 mm graded stone aggregate) in 25 mm thick (measured solid) Jallies or louvers including all mouldings set jointed in CM 1:4 but excluding frame including demolition of existing cement concrete complete all as specified and directed. |
| 8 | M&L for brick protection cover of size 230x115x75 mm to LT underground cables with sub class ‘B’ over burnt brick, (locally available best quality), laid dry and flat abutting each other with gaps not exceeding 10 mm complete all as specified and directed. |
| 9 | Taking down chowkhats or frames area not exc. 1.50 Sqm each with shutters (without taking off shutters from the frames) including dismantling of PCC bed blocks for hold fast etc complete all as specified and directed. |
| 10 | Taking down chowkhats or frames area exc. 1.50 Sqm but not exc. 4.00 Sqm each with shutters (without taking off shutters from the frames) including dismantling of PCC bed blocks for hold fast etc complete all as specified and directed. |
| 11 | S & F 30 mm thick (style thickness) factory made solid panel PVC shutter consisting of frame made out of mild steel tubes for top and bottom rails, mild steel frame shall be covered with heat moulded plain colour PVC \"C\" channel having a PVC sheet strip of 20 mm width stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail and bottom rail on either side & as gap insert for top rail and bottom rail, panelling of plain colour PVC sheet to be fitted in the MS frame welded / sealed to the stiles and rails with suitable PVC sheets beading and joined together with solvent cement as per specification and drawinggiven on MES schedule Part – II (2010) complete all as specified and directed. |
| 12 | S & F factory made Solid PVC door frame of size 50 mm X 47 mm made out of 5 mm plain coloured PVC sheet reinforced with mild steel square tube as per specification and drawing given on MES schedule Part – II (2010) complete all as specified and directed. |
| 13 | S&F 5 mm thick PVC insulation panel with EPS stuck to 1 mm plain PVC sheet suitably placed in false ceiling including GI frame work for seamless ceiling comprising of GI perimeter channel 0.55 mm thick with two unequal flanges of 20 and 30 mm and web of 27 mm fixed to surrounding wall using nylon sleeves and screws at 450 mm centre to centre/intermediate channel 0.9mm thick having equal flanges of 15mm each and web of 45 mm suspended from soffit at approx 900 mm centre to centre with GI cleat and steel expansion fasteners with and including ceiling section (n. exc. 1.2 m length) of 0.55 mm thickness having kurled web of 50 mm and flange of 26 mm each with lips of 10.5 mm fixed to the intermediate channel at 457 mm centre to centre and necessary hangers 6 mm dia GI fixed to roof complete all as specified anddirected. |
| 14 | S&F 150 mm long aluminium anodized barrel tower bolts of extruded section complete all as specified and directed. |
| 15 | S&F 100 mm butt hinges, extruded aluminium alloy with galvanized mild steel hinge pin, anodised and fixed, type B-21 complete all as specified and directed. |
| 16 | S & F 150 mm long Extruded Aluminium alloy handles, fabricated type, anodised complete all as specified and directed. |
| 17 | S&F Stainless steel wire cloth 0.36 mm nominal dia of wire and average width of aperture 1.40 mm and fixed with tinned tacks or galvanised wire staples complete all as specified and as directed. |
| 18 | S&F in repair 20 mm curtain harrison rails, mild steel, chromium plated with fixing brackets, stops, rollers etc with two nos of scoket end caps and brakets (decorative type) for doors/window opening complete all as specified and directed. |
| 19 | M&L for mild steel work as in bands, straps, supports or stays for rainwater, ventilating pipes, including bolts, if required: hooks (stay), heavy, for large gates; hook and pintle hinges: large hasps and staples; chains; handmade sliding bolts; clamps; hold fasts; wall ties; hooks for hanging fans; plain angle cleats for securing purlins to wood trusses or rafters; knee piece inserts; two way and three way straps, plate washers and similar small articles conforming to Fe-290 Gde-E-165 complete all as specified and directed. |
| 20 | S & F Steel windows with side hung shutters including box type hinges with steel handle and steel peg stay, complete with glazing bars, dovetailed or welded complete all as specified and directed. |
| 21 | S&F Steel windows with side hung shutters including box type hinges with steel handle, and steel peg stay, complete without glazing bars, dove-tailed or welded complete all as specified and directed. |
| 22 | S&F Steel Door including projecting type hinges with steel handle, and steel peg stay, complete with glazing bars, dove-tailed or welded complete all as specified and directed. |
| 23 | S&F steel ventilator with top hung shutter and including hinges steel peg stay complete all as specified and directed. |
| 24 | S&F pre-painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50 mm TCT (total coated thickness) of any colour having tensile strength of 550 Mpa as in roof covering cladding to wall etc, fixed with self tapping screws complete all as specified and directed. |
| 25 | S&F 4 mm thick E-board (designer pattern) celing of size 60x60 cm, fixed or laid / inserted to aluminium framework with screws in false ceiling (flat or sloping) of grid size 605 x 605 mm and including anodised aluminium snap grid frame work for false ceiling hanging from structural steel / scantling with 6 mm GI wire complete all as specified and directed. |
| 26 | M&L 75 mm thick, PCC 1:4:8, type D-2 (using 40 mm graded crushed stone aggregate) as in sub floor, sub base of floor, etc complete all as specified and directed. |
| 27 | M&L for providing and laying 60mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved colour, design & pattern as in footparth, parks, lawns, drive ways or light traffic parking etc., of required strength, thickness & size / shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50 mm thick compacted bed of fine sand, compacting and proper embedding / laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand complete all as specified and directed. |
| 28 | S & F Sheet glass 3.0 mm thick, ordinary quality and glazing with oil putty or wooden beads not exceeding 0.5 Sqm in each pane glazed with putty or fixed with beads complete all as specified and directed. |
| 29 | S&F 4 mm thick frosted / pin headed glass in ventilator shutters complete all as specified and directed. |
| 30 | Demolition of cement concrete (un-reinforced) of any description and in any position not otherwise specifically provided including padding concrete on roof all as specified and directed. |
| 31 | Dismantling of corrugated or semi corrugated Asbestos Cement (AC) sheets in roof covering complete all as specified and directed. |
| 32 | Dismantling wall and ceiling boards, partitions of any description or in any position (fibre, pulp, insulation etc.) any thickness, or insulation boards/ slabs/ blankets of any thickness including cover fillets complete all as specified and directed. |
| 33 | M&L for roof treatment in order of precedence as given below complete all as specified and as directed:- (i) Taking out of existing water proofing treatment and including padding, cleaning the surface using wire brush, brooming down and washing down with water to remove dust etc, and brushing with neat cement slurry @ 3.00 kg of cement per Sqm. (ii) 15 mm thick screed bed in CM 1:4 on surface. (iii) Cleaning of plastered surface and applying one coat of bituminous primer @ 0.40 Ltr / Sqm. (iv) Supply and laying 3 mm (Minimum) thick APP based polymeric membrane of approved manufacturer with weight not less than 3.60 Kg per Sqm, reinforced with non-woven polyester fabric weight not less than 150 gms per Sqm. Polymeric membrane shall be taken to a height of 30 cm (minimum) and then inserted inside the groove of parapet wall and shall be finished by a membrane flashing. (Cont.) |
| 34 | (v) Applying one coat of water proofing paint with aluminium finish over APP as per manufacturer\"s instruction. Note :- (a) Bituminous primer shall be \"ShaliTex Primer\" manufactured by M/s STP Ltd or equivalent in M/s Sika India Pvt Ltd or M/s Fosroc Chemicals or M/s Hindcon chemicals limited or M/s IWL India Limited (b) Laying APP based polymeric membrane shall be done by torch on method as per manufactures instructions.(c) A minimum overlap of 100 mm and 75 mm should be made at the end and sides of the polymeric membrane respectively and all overlaps and joints shall be sealed as per manufacturers instruction. |
| 35 | S&F MCCB 4P 200 Amps 415V ,50 Hz ,breaking capacity 36 KA, type DU 250 C, Including dismantling/taking down unsvericeable one complete all as specified and directed. |
| 36 | S&F MCCB 4P 250 Amps 415V ,50 Hz ,breaking capacity 36 KA, type DU 250 C, Including dismantling/taking down unsvericeable one complete all as specified and directed. |
| 37 | S&F MCCB 4P 400 Amps 415V ,50 Hz ,breaking capacity 36 KA, type DU 250 C, Including dismantling/taking down unsvericeable one complete all as specified and directed. |
| 38 | M&L earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised earth lead of GI strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate No. 3 connected to earthing test point and including dismantling complete all as specified and directed. Note :- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:1.5:3, type A1 cover slab, 50 mm thick reinforced with 8 mm dia TMT bar @ 140 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, 20 mm bore medium grade GI watering pipe, 15 mm bore GI light grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc. |
| 39 | Supply and fixing earthing continuty conductor or main earthing lead fixed to pole or burried in ground or at any other situation for loop earthing extra as requiredof GI strip 25x4 mm complete all as specified and directed |
| 40 | S & F of Pole mounted Junction box with terminals of size 182 x 180 x 111 mm, made of high quality thermoplasticpolycarbonate, dust & jet water proof, chemical, acid corrision, impact IK-09, insulated & shock proof IP 66, grey RAL 7035 color with internaly embedded gasket (PUR) , along with coverand metric knockout all sides including back of the base must including terminals 4Nosincluding fixing arrangement with MS flat of size40X4mm , nuts , bolt and washers and MCB SP 6-32 Amps 01 No including taking down old unsv complete all as specified and as directed.Make :- Cape Cat Part No CJB008PS / Hensel / Emitter. |
| 41 | S&F in replacements Nature switch smart sensor based automatic street light control panel with suitable enough to take 3-phase load of 12 KW with 03 Nos I/O MCBs of 32 Amps & 03 Nos contactors of 32 Amps & circuit wiring (copper) of 10 sqmm. The infrared sensing should be maintenance free in design and its operation should be based on natural light lux level ( switching on less than 60 lux & switching off more than 10 lux). The sensor along with suitable power contactors and I/O MCBs should be enclosed in a pole / wall mountable rust proof, electric shock proof, termite proof and FR grade thermoplastic enclosure ( with HINGED LED) conforming to IP66 protection class 2 complete all as specified and directed. Make :- SWADEEP SUGAM 66 12kW3P or its equivalent in legrand / Havells. |
| 42 | S&F in repair of Street Light Timer switch with 24 Hour daily setting, protected with IP-53 box, 230 volt,50Hz AC,ON-AUTO-OFF on front panel, one segment of 15 Min with accuracy of +/- 5 mins, complete all as specified and directed. Make :- Legrand Cat Part No 412790 / Schneider / Havells. |
| 43 | M&L for painting steel tubular poles 9 mtr height with one coat of aluminium paint from bottom to topincluding cross arms, GI brackets etc after cleaning and preparing the surface and marking alternate yellow and black strips 30 cm height total 5 Nos with two coats of synthetic enamel point over a coat of primer complete all as specified and as directed. |
| 44 | M&L for painting of PCC poles 9 mtr height with one coat of aluminium paint from bottom to topincluding cross arms,GI brackets etc after cleaning and preparing the surface and marking alternate yellow and black strips 30 cm height total 5 Nos with two coats of synthetic enamel point over a coat of primer complete all as specified and as directed. |
| 45 | Boring/Drilling (horizontally) manually under 2m deep in soil below existing road suitable for passing GI tubing of 40 to 80 mm bore complete all as specified and directed. |
| 46 | Supply and fixing of GI tubing light grade 40mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor / wall including taking down old unsv complete all as specified and directed. |
| 47 | Supply and fixing of GI tubing light grade 50mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor / wall including taking down old unsv complete all as specified and directed. |
| 48 | Supply and fixing of GI tubing light grade 80mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor / wall including taking down old unsv complete all as specified and directed. |
| 49 | Supply, laying testing and commissoning in replacement of cable XLPE insulated screened PVC bedded galvanised steel strip armoured electric power cables (heavy duty) LT Cable with stranded aluminium conductor 1100 volts grade of size 16 sqmm 4 core laid through duct / pipe / in trench etc connected to LT panel / poles with cable glands & lugs complete all as specified and directed. |
| 50 | All as per Sl. item No. 49.00 above but for 25 sqmm 4 core. |
| 51 | All as per Sl. item No. 49.00 above but for 50 sqmm 3.5 core. |
| 52 | All as per Sl. item No. 49.00 above but for 70 sqmm 3.5 core. |
| 53 | All as per Sl. item No. 49.00 above but for 120 sqmm 3.5 core. |
| 54 | All as per Sl. item No. 49.00 above but for 150 sqmm 3.5 core. |
| 55 | Matrerial & Labour for Painting of Transformer complete with conservator & fins of capacity 100 to 400 KVA, 11/.433 KV out door / in door type with two coats of synthetic enamelled gray spray painting including preparation of old surfaces and writing SM/MES No complete all as specified and directed by Engr -in charge. |
| 56 | Matrerial & Labour for Painting of Transformer complete with conservator & fins of capacity 500 to 750 KVA, 11/.433 KV out door / in door type with two coats of synthetic enamelled gray spray painting including preparation of old surfaces and writing SM/MES No complete all as specified and directed by Engr -in charge. |
| 57 | M& L for on site repair of front and rear doors LT Panel of size 500mmx 500mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 58 | M& L for on site repair of front and rear doors LT Panel of size 1000mmx 800mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 59 | M& L for on site repair of front and rear doors LT Panel of size 1200mmx 800mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 60 | M& L for on site repair of front and rear doors LT Panel of size 1500mmx 1000mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 61 | M& L for on site repair of front and rear doors LT Panel of size 2000mmx 1000mmx500mm including welding of butt hinges 06 Nos on front side and as per requirement on back side, aldrop latches on front and rear side,spray painting with synthetic enamel paint (one coat) complete all as specified and as directed |
| 62 | Supply and fixing in repair of Manual Changeover switch 200 Amps, 4 Pole ,I-O-II operation supplied with bridging bars,extended shaft and IP65 pistol type handle to be fixed in existing slot of the panel and make electric connection complete all as specified and as directed. Make :- ABB Cat No OT200E04CP/Legrand/Havells |
| 63 | Supply and fixing in repair of Manual Changeover switch 400 Amps, 4 Pole ,I-O-II operation supplied with bridging bars,extended shaft and IP65 pistol type handle to be fixed in existing slot of the panel and make electric connection complete all as specified and as directed. Make :- ABB Cat No OT200E04CP/Legrand/Havells |
| 64 | Dismantling and taking down old unserviceable LT panel board and Supply, installation, testing and commissioningof Panel board not less than 1.5m x 1.2 m x0.60 m , outdoor cubical type factory made (CPRI approved) ,double door , front& back both side openable type fixed with Butt Hinges and locking arrangement with Aldrop latches , fabricated of CRCA sheet , inner sheet 2.0 mm thick hinged type door for individual MCCBs and outer door 3.15 mm thick,rubberised gasket, supported on 50x 50 x 6 mm angle iron and Tee section frame dust and vermin proof complete with aluminium bus bar 4 Nos, 600 Amps rated capacitymounted on porcelain insulators totally enclosed chamber for protection 3 phase 415 volt with suitable capacity aluminium bus bar /PVC insulated copper cable control wiring duly mounted on PCC foundation with suitable size of bolts, nuts & wahsers and connecting all I/C & O/G existing cables. Panel boardshall be powder coated and angle iron frame painted with black synthetic enamel paint over a coat of red oxide primer complete, connecting existing cables with suitable size glands and lugs to accommodate and includingthe following as per SI No. 64.01. |
| 65 | INCOMING :- (a) Aluminium busbar 600 Amps rated capacity-04 Nos. (b) MCCB 400 Amps, 4 pole, 415 volt, 36 KA thermal &magnetic release adjestable type - 01 No (c) Spreader Link -02 Sets OUTGOING :- (a) MCCB 250 Amps,4 pole,415 volt 25 kA thermal &magnetic release adjestable type - 02 Nos (b) MCCB 200 Amps, 4 pole,415 volt 25 kA thermal &magnetic release adjestable type - 01 No(c) MCCB 160 Amps, 4 pole,415 volt 16 kA thermal &magnetic release adjestable type - 01 No(d) Spreader Link -06 Sets (e) MCB TPN 63 Amps,415 Volt \"B\" curve -02 Nos(f) MCB 6 Amps, 415 Volt, \"B\" curve -03 Nos(g) Indication lamp Neon/ LED type (set of three) - 01 Set(h) Danger Notice plate - 01 No. (i) Panel control wiring with 16 sqmm s/c copper wire complete- 01 Job. |
| 66 | Dismantling and taking down old unserviceable LT panel board and Supply, installation, testing and commissioningof Panel board not less than 1.0m x 0.8 m x0.50 m , outdoor cubical type factory made (CPRI approved) ,double door , front& back both side openable type fixed with Butt Hinges and locking arrangement with Aldrop latches , fabricated of CRCA sheet , inner sheet 2.0 mm thick hinged type door for individual MCCBs and outer door 3.15 mm thick,rubberised gasket, supported on 50x 50 x 6 mm angle iron and Tee section frame dust and vermin proof complete with aluminium bus bar 4 Nos, 400 Amps rated capacitymounted on porcelain insulators totally enclosed chamber for protection 3 phase 415 volt with suitable capacity aluminium bus bar /PVC insulated copper cable control wiring duly mounted on PCC foundation with suitable size of bolts, nuts & wahsers and connecting all I/C & O/G existing cables. Panel boardshall be powder coated and angle iron frame painted with black synthetic enamel paint over a coat of red oxide primer complete, connecting existing cables with suitable size glands and lugs to accommodate and includingthe following as per SI No. 65.01. |
| 67 | (a) Aluminium busbar 400 Amps rated capacity-04 Nos. (b) MCCB 250 Amps, 4 pole, 415 volt, 25 KA thermal & magnetic release adjestable type – 01 No (for incoming). (c) Spreader Link for MCCB – 02 sets(d) Indication lamp Neon / LED type (set of three) -01 set. (e) Danger Notice plate – 01 No.(f) Panel control wiring with 10 sqmm s/c copper wire complete – 01 job. |
| 68 | Dismantling and taking down old unserviceable LT panel board and Supply, installation, testing and commissioningof Panel board not less than 1.8m x 1.5 m x0.60 m , outdoor cubical type factory made (CPRI approved) ,double door , front& back both side openable type fixed with Butt Hinges and locking arrangement with Aldrop latches , fabricated of CRCA sheet , inner sheet 2.0 mm thick hinged type door for individual MCCBs and outer door 3.15 mm thick,rubberised gasket, supported on 50x 50 x 6 mm angle iron and Tee section frame dust and vermin proof complete with aluminium bus bar 4 Nos, 400 Amps rated capacitymounted on porcelain insulators totally enclosed chamber for protection 3 phase 415 volt with suitable capacity aluminium bus bar /PVC insulated copper cable control wiring duly mounted on PCC foundation with suitable size of bolts, nuts & wahsers and connecting all I/C & O/G existing cables. Panel boardshall be powder coated and angle iron frame painted with black synthetic enamel paint over a coat of red oxide primer complete, connecting existing cables with suitable size glands and lugs to accommodate and includingthe following as per SI No. 66.01. (Loc : TOI) |
| 69 | INCOMING :- (a) Aluminium busbar 400 Amps rated capacity-04 Nos.(b) MCCB250 Amps, 4 pole, 415 volt, 36 KA thermal &magnetic release adjestable type - 01 No (c) Spreader Link -02 Sets OUTGOING :-(a) MCCB 160 Amps, 4 pole,415 volt 16 kA thermal &magnetic release adjestable type - 01 No (b) MCCB 100 Amps, 4 pole,415 volt 16 kA thermal &magnetic release adjestable type -03 Nos (c) Spreader Link -06 Sets (d) Manual Changeover Switches,I-O-IIoperation supplied with bridging bars, extended shaft and IP-65 protection with pistol type handle of rating 200 Amps 4 pole . Make : ABB Cat No OT200E04CP/Havells/Legrand - - 02 Nos (01 for operation & 01 Standby)(e) MCB TPN 63 Amps,415 Volt \"B\" curve -08 Nos (f) MCB 6 Amps, 415 Volt, \"B\" curve -03 Nos (g) Indication lamp Neon/ LED type (set of three) - 01 Set (h) Danger Notice plate - 01 No. (i) Panel control wiring with 16 sqmm s/c copper wire complete- 01 Job. |
| 70 | Dismantling & taking down old unsv existing LT capacitor panel board and Supply, installation, testing and commissioningof APFC Capacitor panel board cubical type of size (1.2x1.5x0.6)m depth not less than 0.60 M fatory made (CPRI approved), outdoor use single door , back side& front both sideopenable in totwo halve,inner door for individualcontrols, MCCBs & Capacitor, contactor etcwith locking arrangement made out of 3.15 mm thick CRCA Sheet supported on ,50 x 50 x 6 mm angle iron and Tee section frame dust and vermin proof,well ventelated with exhaust fan of suitable size complete, powder coatedwith aluminium bus bar 4 Nos, 400 Amps capacity duly PVC sleaved with colour coadingmounted on porcelain insulatorswith suitable size of PVC insulated copper cable control wiring duly pedestal mounted to match the existing feeder pillar complete to accommodate and including the following as per SI No. 67.01. (150KVAR=5*2+10*1+15*2+25*2+50*1) |
| 71 | (a) Ultra Heavy duty capacitor box oil filled type of capacity 5 KVAr,440 volt 3 phase -02 Nos (b) Ultra Heavy duty capacitor box oil filled type of capacity 10 KVAr,440 volt 3 phase -01 No (c) Ultra Heavy duty capacitor box oil filled type of capacity 15 KVAr,440 volt 3 phase -02 Nos(d) Ultra Heavy duty capacitor box oil filled type of capacity 25 KVAr,440 volt 3 phase -02 Nos(e) Ultra Heavy duty capacitor box oil filled type of capacity 50 KVAr,440 volt 3 phase -01 No(f) APFC RELAYModel No- etaCON L12, 5 Amps ,415 Volts, AC 12 Steps with RS 485 communication port for Modbus Data transfer complete.:01 No (g) MCB three pole 16 Amp ,415 Volt ,10 KA :18 Nos (h) Digital meter for digital parameter such asVoltage,Ampere,Power Factor ,Frequency, KWH , 3 Phase ,Class 1, 5A,with RS 485communication port for MODBUSS Data transfer complete.:01 No(i) MCCB Four pole 200 Amp 25 kA adjustablethermal magnetic release with threshold and Adjustable Over Load setting. : 01 No(j) Capacitor Duty MO C type contactor(1 NO+1NC), low operating losses high widhstand capacity as per capacitor capacity .(5x2+10x1+15x2+25x2+50x1) KVAr: 01 Set for all Capacitor Banks (k) Indicating lamp LED type 220vac(red and green in colour):18 Nos (l) Push button with NO/NC220vac:18 Nos (m) Copper Lugs 16sq mm:24 Nos (n) Suitable capacity CT\"s. -04 Nos. (o)Painting as per CPRI (p) Danger notice plate.-01 No. (q) Panel control wiring with 16 sqmm s/c copper wire complete- 01 Job. |
| 72 | Supply and fixing in repair of ACB 4 pole, 415V, 50KA with thermal magnetic release (manual drawout type) of capacity 630 Amps including taking down old unsv complete all as specified and directed. |
| 73 | Supply and fixing in repair of ACB 4 pole, 415V, 50KA with thermal magnetic release (manual drawout type) of capacity 800 Amps including taking down old unsv complete all as specified and directed. |
| 74 | Supply and fixing in repair of Ultra Heavy duty capacitor box oil filled type of capacity 10 KVAr, 440 volt 3 phase incl making connection to existing MCCB/Contactors incl taking down old unsv complete all as specified & as diretced. Make :- L&T LTXL LTBCU/Legrand/Schneider |
| 75 | Supply and fixing in repair of Ultra Heavy duty capacitor box oil filled type of capacity 15 KVAr, 440 volt 3 phase incl making connection to existing MCCB/Contactors incl taking down old unsv complete all as specified & as diretced.Make :- L&T LTXL LTBCU/Legrand/Schneider |