| 1 | Supply, erection, testingand commissioning of CPCB IV +30 kVA DG Set,415V,3 phase, 4 wire, 50Hzat 0.8p.f< &% dBA prime duty diesel generatorincluding with acoustic enclosure andsuitable for Controller, with radiator cooled engine, alternator, 12V batteries charger with battery leads and Residential Silencer with accessories, common base plate, anti vibration mounts, first fill of Lube oil, drip trays etc. as required. The DG set should meet the requirement of CPCB- IV + [Load trials should be planned at the manufacturers / suppliers premises at their expenses] The DG accoustic enclosure shall have inbuilt fuel tank bed. The system shall comply with the norms of the statutory bodiescomplete with connections ,testing and commissioning etc as required. |
| 2 | Supply, Erection, installation, testing & commissioning of Inbuilt AMF control panel for auto change over in line with specifications of 2Nos. 4 Pole Power Contactor & 2Nos. 4 Pole MCCB complete with necessaryaccessories .etc as required. |
| 3 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.(DSR2022 Item no.5.6) |
| 4 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. (DSR 2022 Item no.5.10) |
| 5 | Supply of PVC insulated and PVC sheathed XPLE power cable of 1.1 KV grade armoured UG aluminium conductor cable conforming to IS 7098 part 1 with up-to-date amendment of the following size as required. |
| 6 | 3.5 X 50 sq.mm |
| 7 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulatedand PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 8 | 3½ X 50 sq. mm (35mm) (DSR 2022 -Item no.9.1.22) |
| 9 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 10 | Above 35 sq. mm and upto 95 sq. mm (DSR 2022 -Item no.7.3.2) |
| 11 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.up to 35 sq.mm. |
| 12 | Above 35 sq. mm and upto 95 sq. mm (DSR 2022 -Item no.7.5.2) |
| 13 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 14 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) (DSR 2022 -Item no.7.7.2) |
| 15 | Supply & installation of Safety Items with First Aid Kit, short Treatment Chart, DCP Type Fire Extinguisher of 2Kgs., Rubber mat , Fire Bucket of 2nos. With Stand etc as required |
| 16 | Supply and Fixing of 4 pole On load Change-Over switch having Rated Current of 100A and Rated Voltage of 415V along with sheet steel enclosure on wall surface or existing panel board along with connecting existing cables to change-over switch including testing, commissioning etc., at site of work as required |
| 17 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m inwidth or 10 sqm on plan), including dressing of sides and ramming ofbottoms, lift upto 1.5 m, including getting out the excavated soil anddisposal of surplus excavated soil as directed, within a lead of 50 m. |
| 18 | All kinds of Soil |
| 19 | Carriage of Materials by By Mechanical Transport including loading,unloading and stacking Earth for all leadsfor 1 Km within the depot premises. |
| 20 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinthlevel : |
| 21 | 1:5:10 (1 cement : 5 coarse sand (zone-III) derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 22 | Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto plinth level. |
| 23 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 24 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : |
| 25 | 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 26 | Steel work in built up tubular (round, square or rectangular hollow tubesetc.) trusses etc., including cutting, hoisting, fixing in position andapplying a priming coat of approved steel primer, including welding andbolted with special shaped washers etc. complete. |
| 27 | Hot finished seamless type tubes |
| 28 | Providing and fixing mild steel round holding down bolts with nuts and washer plates complete |
| 29 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade |
| 30 | Two or more coatson new work over an undercoat of suitable shade withordinary paint of approved brand and manufacture. |
| 31 | Providing and fixing precoated galvanised iron profile sheets (size,shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 micronsepoxy primer on both side of the sheet and polyester top coat 15-18microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost ofpurlins, rafters and trusses and including cutting to size and shape wherever required. |
| 32 | Centering and shuttering including strutting, propping etc. and removal of form for |
| 33 | Foundations, footings, bases of columns, etc. for massconcrete |
| 34 | 6 mm cement plaster of mix :commissioning etc., at site of work as required |
| 35 | 1:3 (1 cement : 3 fine sand) |
| 36 | Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5- microns epoxy primer on both side of the sheet and polyester topcoat 15-18 microns using self drilling/ self tapping screws complete : |
| 37 | Ridges plain (500 - 600mm) |
| 38 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with sealring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. |
| 39 | Ridges plain (500 - 600mm) |
| 40 | Flashings/ Aprons.( Upto 600 mm) |
| 41 | Gutter (600 mm over all girth) |
| 42 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes. |
| 43 | 75 mm diameter |
| 44 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conformingto IS : 13592 Type A, including jointing with seal ring conforming toIS : 5382, leaving 10 mm gap for thermal expansion. |
| 45 | 75 mm diameter |
| 46 | Clearing jungle including uprooting of rank vegetation, grass, brush wood,trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. |
| 47 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: |
| 48 | New work (Two or more coats applied @ 1.43 ltr/10 sqmover and including priming coat of exterior primer applied@ 2.20 kg/10 sqm) |