| 1 | Supply, installation, testing and commissioning of multistage centrifugal pump set with cast iron impellerof capacity 26 ltr/sec at2970 RPM, 160 mtr delivery head and with suitable dia of suction and delivery (80 mm x 65 mm) coupled with squirrel cage induction motor of suitable capacity, 415 Volt, three phase including necessary PCCfoundation complete all as specified and directed.Note:(i) The quoted rate shall be inclusive of pump set and motor.(ii) The quoted rate shall be inclusive of making of Platform of PCC (1:2:4)(20 mm aggregate. The platform shall be 20 cm below GL and 45 cm above GL. The PCC platform shall be constructed over rammed hard core. Necessary excavation and shuttering shall be considered in quoted rate. The platform shall be painted with two coat of white synthetic enamel paint. The necessary working space of 30cm all around the platform shall be made in PCC and quoted rate shall be inclusive of the same.(iii) The suitable size of MS base frame, foundation bolts and nuts, anti-vibration pad (mim thickness 3mm), coupling and coupling guard including connection of suction and discharge pipe lines, all electrical cable connectionto the pump shall deemed to be included in quoted rate. The base frame shall be painted with two coat of Synthetic enamel paint over one coat red oxide primer.(iv) The testing of pump shall be carried out by Engr-in-Charge in presence of AGE(I) and rep of contractor. The testing report shall be fwd to this HQ for record.(v) Any other requirement arising during installation of pumpset (which is necessary for installation of pump set) shall be included in quoted rate. (vi) The pump will be installed at the location all as specified and directed by Engr-in-Charge.(vii) The contractor shall submit original warrantee from manufacture to Engr-in-Charge. . Make:Pump : Model Horizontal pump 4 Stage, RKB 65-19L coupled with CGL make 75 KW, 2P, IE2 TEFC motor of make Kirloskar or equivalent in KSB/Crompton Greaves) |
| 2 | Supply, installation, testing and commissioning of multistage vertical turbine pump set with cast iron impellerof capacity 25.2 ltr/sec at2900 RPM, 150 mtr delivery head with suitable dia of suction and delivery (150 mm x 150 mm) coupled with squirrel cage solid shaft induction motor of suitable capacity, 415 Volt, three phase including necessary RCCfoundation complete all as specified and directedNote:(i)The quoted rate shall be inclusive of pump set and motor.(ii) The pump shall be mounted over RCC foundation. The base frame of pump shall be 45 cm above ground level. The platform shall be 20 cm below GL and 45 cm above GL. The PCC of platform shall be laid over hard core . The RCC shall have thickness of 200mm with 10 mm dia TMT with spacing @ 100mm C/C in both directions. Suitable and necessary all around working space i.e. clear 30 cm shall be made. The platform shall be painted with two coat of white synthetic enamel paint. The quoted rate shall be inclusive of such provisions.(iii) The suitable size of MS base frame, foundation bolts and nuts, coupling and coupling guard including connection of suction and discharge pipe lines, anti vibration pad (Mim 3 mm thick), all electrical cable connection including testing the pump shall deemed to be included in quoted rate. (iv) Provn of 150mm dia column pipe flanged/ screwed type as required at site with pump shaft as per manufacturer recommendation of 13 mtr long and fixing the multistage pump at the bottom of column pipe. The quoted rate shall be inclusive of the same.(v) Any other requirement arising during installation of pumpset is also deemed to be incl in the item rate. The pump will be installed at the locationall as specified and directed by Engr-in-Charge.(vi) The contractor shall submit original warrantee from manufacture to Engr-in-Charge. .Make:Pump : Model Multistage vertical turbine pump 5 Stage, VT 250 HL coupled with CGL make 75 KW, 2P, IE2 TEFC motor of make Kirloskar or equivalent in KSB/Crompton Greaves) |
| 3 | M&L for making header 4 mtr length with 300 mm dia 10mm thick MS pipes both end closed by welding MS plate with two inlet and one outlet connections. The size of the inlet is 100 mm dia and outlet is of 150 mm dia. The rates of 300 mm dia MS pipe incl required welding / cutting of MS pipes / plates for making header with branch connections incl the required flanges is deemed to be incl in the item rate. The proper anchoring of header with RCC wall with suitable clamps and nuts to withstand vibration caused by the working pressure of water from pumps is also deemed to be incl in the item rate incl making the disturbed surfaces good complete all as specified and as directed by Engr-in-Charge. |
| 4 | M&L for cutting CI/DI/GI pipes and reduction to required length before laying including insertion of new Tees, branches etc of size upto 150 mm dia all complete. |
| 5 | Supply onlyMS ERW water pipe of 100 mm dia complete all as specified and directed. |
| 6 | M & L for cast non return valve of 100 mm dia ISI Marked, confIrming to IS14846 both ends flanged class PN1.6 and necessary new MS nuts, bolts, washer, gasket and making good etc complete all as specified and directed. |
| 7 | M & L for cast iron sluice valve of 100 mm dia ISI Marked, confIrming to IS14846 both ends flanged with ss spindle, class PN1.6 and necessary new MS nuts, bolts, washer, gasketand making good etc complete all as specified and directed. |
| 8 | M & L in replacementfor DI/CI special fitings like bends, tapers, tee, tail pieces,collars etc suitable upto 100 mm dia pipesincluding necessary welding works at site requirement . |
| 9 | M & L in replacementfor DI/CI special fitings like bends, tapers, tee, tail pieces,collars etc suitable upto 200 mm dia pipesincluding necessary welding works at site requirement . |
| 10 | M&L for Ductile Iron pipes 150 mm, spigot & socket end, centrifugally cast (spun), Class K-9, confirming to IS-8329/ 2000 or latest revision, in any length, laid in trenches/PCC base /RCC columuns, with & including EPDM rubber gasket confirming to IS:9523/2000 or latest revision, connecting & testing complete all as specified & directed . |
| 11 | M & L for cast iron sluice valve of 150 mm dia ISI Marked, confIrming to IS14846 both ends flanged with ss spindle, class PN1.6 and necessary new MS nuts, bolts, washer and gasket, including making good etc complete all as specified and directed by Engr-in-Charge. |
| 12 | M & L forJoint with rubber or fibre board gasket for bore upto 200 mm dia size complete all as specified and as directed. |
| 13 | M&L for PCC type B-2 1:2:4 (40mm graded aggregate) Cement concretefoundations, filling and massconcrete all complete all as directed |
| 14 | M&L for Reinforced cement concrete (nominal mix) Type B 1:1.5:3 (20 mm graded stone aggregate) Foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concrete all complete all as directed |
| 15 | M&L for Formwork to sides of concrete rough finished surface flat for foundations, footings, bases of columns, raft and raft beams,sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batteall complete all as directed |
| 16 | M&L for Mild steel TMT bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips all complete |
| 17 | M&L for Joist, channel, angle, or tee sections,fixed independently, without connecting plates, etc. Fe 410 -W (GdeE- 250) qualityA (cut to ordinary lengths all complete all as directed . |
| 18 | M&L for new steel Surfaces of any description, over 10cm in width or girth with two coats of black japan paint over and including with red oxide primer all complete all as directed |
| 19 | M&L for SS flexible pipe of dia 100 mm, single braided with both side flanges all as specified and as directed . |
| 20 | M&L for HDPE pipe of dia 100 mm, welded with 2 stud ends and 2 MS slip flange inserted UV stabilized raw materialall complete all as specified and as directed . |
| 21 | M&L for pipe floater for pipe size 100 mm dia, high impact polyethylene PU foam filled UV stabilized raw material bolts, nuts, rubber pads and belts, colour orangeall complete all as specified and as directed . |
| 22 | M&L foranchoring and mooring as the floating platform with necessary bollards, RCC anchors with suitable weight and size, chain with suitable size, diameter and length all complete all as specified by OEMand as directed by Engr-in-Charge.Make : Vari Pontoons or equivalent |
| 23 | M&L forfloating platform made of HDPE High Density Polyethylene block buyos interlocking in nature of dimension of each block 50cm x 50cm x 40 cm cubical in shape and modular in nature that enable easy assembly and dismantling the required size all complete with load capacity 350 kgs/m2 and complete with railingto bear load ofsuction line of HDPE pipe of dia 100 mm with stainer and foot valve of size all complete all as specified by OEM and as directed. Note:(i) The floating block must have proper interlocking arrangements.(ii) The weight carrying capacity of block shall be 360kg/Sqm or more.(iii) The Floating Pontoons to be made up of 100 % Virgin high density polyethylene (HDPE) and should be 100% recyclable & Non-Polluting.(iii) The module to comply with following Technical parameters:Material: HDPE, Density: min.0.952 g/cc,IZOD Impact Strength: 25 KJ/m2, Tensile Strength at Break: min. 20 MPa,Tensile Strength at Yield: min. 25MPa, Melt Flow Index (21.6kg, 190°C): less than 10,Filler Content: Less than 2%. |
| 24 | M & L forPVC insulated,heavy duty,industrial copper cables of 35 sqmm,single coreunsheathed 1100 volts grade conforming to IS : 694 for connection of motors etc with copper lugs for suitable size complete all as specified and as directed. |
| 25 | Supply and fixing of powder coated MS peforated cable tray of size 100 x 50x 1.6 mm with cover C type for cable dressing including coupler, junction boxes, screws, fastner etc all complete and fixing charges as directed . |
| 26 | Excavation in trenches in soft/loose soil n.exc 1.5 mtr wide and n.exc 1.5 mtr deep getting out of soil for taking out/laying of pipe line etc.complete all as specified & directed . |
| 27 | Returning, filling in, including spreading, levelling watering and well ramming in layers not exc 25 cm.complete all as specified & directed. |
| 28 | Removing excavated mateials n.exc 50 mtr & depositing where directed at a level n.exc 1.5 mtr above the starting point.complete all as specified & directed . |
| 29 | M & L for Foot Valve stainer brass end 100 mm Dia ISI Marked brass made complete all as specified and directed. |
| 30 | M&L for earthing complete with galvanised steel earth plate electrode 600x600x 6mm thick burried in ground (earth pit not less than 2.25 m deep below ground level0with top edge of the plate not less than 1.5 m below normal ground level, connected to earth lead wire 4.0mm dia as earthing lead by means of bolts, nuts, check nuts, and washers of GI or steel, GI strip protected by 40 mm bore medium grade GI pipe and other end connected to earth test point as directed including funnel with watering pipe 20 mm bore light grade GI, wire mesh charcoal or coke common salt laid in altrnative layer of 15 cm (complete thickness) all round the earth electrode, concrete earth pit in PCC(1:3:6) type C-1, 50 mm thick pre-cast RCC(1:2:4) type B-1 normally mix cover slab reinforced with in 8 mm dia TMT bar 10 cm C/C both ways and single handle of 10 mm dia round bar including necessary excavation, earth work etc. in soft/loose/hard soil and disposal of soil to a distance n.exc 50 m and necessry testing on completion all as shown in electrical plate No 3 MES schedule part-I complete all as specified and as directed. |
| 31 | All as Sl item No. 30 above but using galvanised iron strip 25×4mm as earthing lead |
| 32 | Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sq. mm, 3.5 core complete all as specified and as directed. |
| 33 | Supply and laying new dry riversand laidintrenches 8 cm below the cable and 15cm above the cable and punned to 18 cmascablecushioningandcoveringall asdirected. |
| 34 | Supply and layingin replacement of brickwell burntlocallyavailablesubclass \"B\" laid over sand cushioningfor cableprotectionintrencheswidthofbrickperpendicullar to the length of cable complete all as specified and directed by Engr-in-Charge. |
| 35 | M&L for 20 mm dia galvanized steel tubing (medium grade), with all fitting laid in trenches complete all as specified and as directed. |
| 36 | S & F for 20 mm gun metal gate valve with iron wheel head, screwed both ends for iron pipe complete all as specified and as directed. |
| 37 | S & F for pressure gauge 100mm dial, 0-14 Kgs ratingwith fittings as per site requirementcomplete all as specified and directed. |
| 38 | S&F LT Panel board with copper loop bus bar of capacity 600A ,made out of CRCA sheet 3.15 mm thick otdoor pedestal type totally enclosed with front and rear opening, hinged doors of size 1.0 m x 1.2m x 0.5 m, with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, danger notice plate, strickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 copper bus bar (incoming and ougoing side) mounted on insulators as per IS with heat proof colour code, insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 500 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following:Incoming:a) LT 440 volts3 phase, 4 wire 50 cycles, 20kA, Adjustable type MCCB of 300 Amp rated 4 pole complete as per IEC: 60947-II, adjustable thermal and fixed magnetic , Ics=100% Icu . Make:Havells, Cat Part No: IHD2HTBF0250/Indoasian / Schnieder/ Siemens - 1No. Outgoing:a) LT 440 volts3 phase, 4 wire 50 cycles, 20kA, Adjustable type MCCB of 200 Amp rated 4 pole complete as per IEC: 60947-II, adjustable thermal and fixed magnetic , Ics=100% Icu . Make:Havells, Cat Part No: IHD2HTBF0160/Indoasian / Schnieder/ Siemens2 Nos.(b) Fully Automatic star delta starter complete with under voltage and over voltage relays, contactor etc suitable for 75 HP pump motor ac 415 voltthree phase-02 nos. (c) Supply and fixing MCCB C-Curve, 32 Amp TPN, 50 Hz, 240/415 Volts complete all as directed.Make:Panasonic, Cat Part No:BBD4633CHH /Indoasian /Schnieder - 01 No(d) LED Indicating Lamps for ech phase with colour coed Red Yellow Blue for R, Y and B Phases-01 Set(e) Multifunctional Intelligent Panel Meter digital type for measuring Volts, Current, Hz, pf, power, energy, THD along with connected CTs Make: Schinder / L&T-01 No |
| 39 | Repair/Maintenance/Cleaning of jack well including taking out of sludge / desilting from jack well water and depositing upto 150 mtr to 200 mtr distance and lifting from 12 to 15 meter depth from Jack well pump room flooring level including repairs and cleaning / clearing the blockage of 3 Nos on the jack well for smooth inlet of water inside the well and making it in serviceable condition including required dewatering / welding/ greasing/oiling if necessary repairs required complete including any type of materials required for the joball complete all as specified and as directed . |
| 40 | M&L for Micro Concrete ready to use dry powder mix form that only needs clean water added at site consisting of cement, river sand, quartz sand, lime, water based resin, additives, mineral pigments and polymers in the specified ratio all complete to be applied in thin layers of around 2 to 4 mm on concrete surfaces to refurbish them all complete all as specified. |
| 41 | M & L for pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified compete all as specified and as directed by Engineer-in-Charge. |