| 1 | A. PANEL BOARDSM.V Panel:(OSR) Indoor type M.V. Switch gear panel 440V. 400 AMP busbar, four wire system, cubical type, front operated complete powered coat finish comprising the following switches confirming to I.E. specification Make of MCCB Siemens /L&T with identification tags and indication lamp with metering arrangement. (Panel sheet thickness 2 mm) |
| 2 | OSR - 400A 4P MCCB |
| 3 | OSR - 200A TPN MCCB |
| 4 | OSR - 125A TPN MCCB |
| 5 | OSR - 63A TPN MCCB |
| 6 | OSR - Energy Meter |
| 7 | OSR - 16/18 SWG CR Sheet |
| 8 | EB Metering: (OSR) 200A TPN Aluminium Bus Bar Powder Coating with Epoxy Paint with Sheet Steel Enclosure Indoor type panel 440V cubical type, front operated complete powered coat finish comprising the following switches confirming to I.E. specification make Siemens/L&T with identification tags and indication lamp with metering arrangement. |
| 9 | OSR - 200A TPN MCCB |
| 10 | OSR - 63A TPN MCCB |
| 11 | OSR - 32A TPN MCCB |
| 12 | OSR - Energy Meter |
| 13 | OSR - 16/18 SWG CR Sheet |
| 14 | Light Point Wiring |
| 15 | OSR - Recessed wiring to light point/Fan point/ Exhaust fan point/Call bell point with 1.5 sg.mm FR PVC insulated single core multistrand copper conductor of ISI marked with 20 mm dia non-metallic PVC flexible conduit with 6Amp, 250V Modular switch(Legrand mylinc/Schneider clipsai/Hager insysta/Anchor Dural or equivalent) ISI marked and ceiling rose ISI marked mounted on metal box having front Modular cover of suitable size, metal box with 1.5 sq.mm FR PVC insulated single core multistrand copper conductor as earth wire including all accessories and connection.(Make of wire L&T/Anchor Havells/V-Guard/Great White/HPL) (Group-B) |
| 16 | Circuit Mains |
| 17 | OSR -Recessed wiring for light / power plug with 2 x 2.5 sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked with 20rnm dia non-metallic PVC flexible conduit along with 1 x 1.5 sq.mm FR PVC insulated single core multistrand copper conductor for loop earthing as required (Make of wire-Finolex/L&T/ Anchor Polycab/Havells/Great white/ RR/ V-Guard/ HPL) |
| 18 | OSR - Recessed wiring tor light / power plug with 2 x 4 sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked with 20mm dia non-metallic PVC flex1ble conduit along with 1 x 2.5 sq.mm FR PVC insulated single core multistrand copper conductor for loop earthing as required. Finolex L&T/Anchor/Polycab/Havells/Great white/RR/V-Guard/HPL) |
| 19 | Light Fittings |
| 20 | OSR - Supply, Installation, Testing and Commissioning of integrated LED Batten Light fitting of extruded aluminium/CRCA housing with high quality polycarbonate diffuser, 1200mm long, having nominal colour temperature not less than 6500K, system lumen output 2000 (nominal) and system wattage not more than 20W including connections with 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block and 1.5 sq. mm FRLS, PVC insulated, copper conductor, single core cable and earthing etc., as required. |
| 21 | OSR - Supply, installation, testing and commissioning of 20W LED Outdoor light fittinghaving die cast aluminium housing IP 65/ 66 body, with builtin surge protection device of 5KV, constant current driver complete with all accessories on the existing street light pole/bracket including connectionetc. as required. |
| 22 | LMR - Supply, Installation, Testing and Commissioning of LED Bulb with Reflector of thermal plastic heat dissipating body with opal lens,having nominal colour temperature not less than 2700K, system lumen output 806 (nominal) and system wattage not more than 50W including connections with 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block and 1.5 sq. mm FRLS, PVC insulated, copper conductor, single core cable and earthing etc., as required. |
| 23 | Fan / Exhaust Fan |
| 24 | OSR - Supply, Installation, Testing and Commissioning of 1200 mm sweep, ceiling fan class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos canopies, shackle kit, copper winding, Air delivery minimum 210 CMM,380 RPM suitable to work on existing electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 25 | OSR - Supply, Installation, testing and commissioning ofIndustrial type Exhaust fan of size300mm sweep, body made of Engineering plastic, plastic bladesin the existing opening on the existing wall on existing hole to suit to the size of the above fan with Connection accessories of 3 pin, 5 amp ceiling rose on the existing junction box/wooden block including connection etc as required. |
| 26 | Accessories |
| 27 | OSR - Supply of fixing of 40 mm GI Bracket with 2 nos GI clamp & 4 nos 3\" Anchor fasteners for fixing of street light. |
| 28 | OSR - Supply and fixing of Electronics step type Modular fan regulator. (Legrand mylinc/ Schneider clipsal/Hager insysta/Anchor Dura or equivalent) |
| 29 | Sockets |
| 30 | OSR - Supply and fixing of Modular metal box on surface or in recess with suitable size of Modular cover in front including providing and fixing of 6pin 6amp, 16Amp socket outlet and 16Amp Modular switches connection ( Legrand mylinc / Schneider clipsal / Hager insysta / Anchor Dural or equivalent) |
| 31 | OSR - S/F of Ac Point with 20A Plug and socket with provision for mounting of 20A DP MCB for flush mounting and surface mounting including DP MCB (Legrand / Schneider / Hager / Anchor Dural or equivalent) |
| 32 | LMR - Supply and Fixing of 240V Single Phase water proof Industrial socket with plug (Insulated Plug and Socket IP67) Surface Mounting Outlet with MCBProvision, 16/20A , Including 2Pole 20A MCB etc. as required. |
| 33 | Air Conditioner Unit |
| 34 | OSR - Supply, Erection, Testing and Commissioning of 1.5 Ton Split Type Room Air Conditioner with Stand and copper tubing arrangement |
| 35 | OSR - Supply, Erection, Testing and Commissioning of 130 to 280 volt 4 KVA Stabilizer including all the accessories. |
| 36 | Lighting Power Distribution Board : (OSR) Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 37 | OSR - 4 way (4+12), Double door |
| 38 | OSR - Supplying and fixing following amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 39 | OSR - 63A Triple pole and neutral MCB |
| 40 | OSR - 32A Triple pole and neutral MCB |
| 41 | LMR - 40A, Double Pole RCCB |
| 42 | LMR - 25A, Double Pole RCCB |
| 43 | OSR - 6A Single pole MCB |
| 44 | OSR - 20A Single pole MCB |
| 45 | OSR - Single pole, Blanking Plate |
| 46 | POWER CABLE - (OSR) Supplying of following sizes of PVC insulated and PVC sheathed/ XLPE aluminium/Copper conductor Multi-strand UG armoured cable of 1.1 KV grade confirming to IS:7098 (Part-I) 1988 with upto date amendments duly ISI marked complete as required. |
| 47 | OSR - 3.5C x 150Sq.mm Cable(Al) |
| 48 | OSR - 3.5C x 120Sq.mm Cable(Al) |
| 49 | OSR - 3.5C x 50Sq.mm Cable(Al) |
| 50 | OSR - 3.5C x 35Sq.mm Cable(Al) |
| 51 | OSR - 3.5C x 25Sq.mm Cable(Al) |
| 52 | OSR - 4C x 16Sq.mm Cable(Al) |
| 53 | CABLE LAYING - (OSR 5.1) Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 54 | OSR 5.1.3 - 3.5C x 150Sq.mm Cable(Al) |
| 55 | OSR 5.1.2 - 3.5C x 120Sq.mm Cable(Al) |
| 56 | OSR 5.1.2 - 3.5C x 50Sq.mm Cable(Al) |
| 57 | OSR 5.1.2 - 3.5C x 35Sq.mm Cable(Al) |
| 58 | OSR 5.1.1 - 3.5C x 25Sq.mm Cable(Al) |
| 59 | OSR 5.1.1 - 4C x 16Sq.mm Cable(Al) |
| 60 | END TERMINATION - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 61 | LMR - 3.5C x 150Sq.mm(50mm) |
| 62 | LMR - 3.5C x 120Sq.mm(45mm) |
| 63 | LMR - 3.5C x 50Sq.mm(32mm) |
| 64 | LMR - 3.5C x 35Sq.mm(28mm) |
| 65 | LMR - 3.5C x 25Sq.mm(25mm) |
| 66 | LMR - 4C x 16Sq.mm(25mm) |
| 67 | CABLE TRAY - Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. |
| 68 | LMR - 150 mm width X 50 mm depth X 1.6 mm thickness |
| 69 | LMR - 300 mm width X 50 mm depth X 1.6 mm thickness |
| 70 | EARTH FLAT |
| 71 | OSR - Supply and fixing of G.I Earthing with G.l earth pipe 3mtr. Long 40mm dia ISI marked including accessories and providing masonry with charcoal and salt as required. |
| 72 | OSR 3.16 - Supplying and laying 25mm X 5mm G.l strip on surface or in recess for connection etc as required. |
| 73 | OSR 3.20 - Providing and fixing 8 SWG (4 mm) dia copper wire on surface or in recess for loop earthing along with existing surface / recessed conduit as required. |
| 74 | MISCELLANEOUS ITEMS - (OSR) Laying of G.I pipe for Cable Support (Motors and Starters, Fan and Light Fittings 40mm, 50mm) Including Fabrication Bolt, Nut, etc. |
| 75 | OSR 40mm G.I Pipe |
| 76 | OSR 50mm G.I Pipe |
| 77 | OSR Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 78 | SAFETY EQUIPMENTS |
| 79 | LMR - 1.1 KV Class 20mm Thick900x1800mm rubber mat. |
| 80 | LMR - Safety Instruction chart in English and Local Language |
| 81 | LMR - Shock treatment chart in English and Local Language |
| 82 | LMR - Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side as required. |
| 83 | LMR - First aid box complete with all standard first aid materials |
| 84 | LMR - CO2 Fire Extinguisher |
| 85 | LMR - 1 set - Fire buckets filled with sand and water, necessary bracket for hangingCO2 Fire Extinguisher with bracket etc., as required. |
| 86 | PLUMBING WORKSKitchen Sink: (OSR 3.4.14.B) - Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required Kitchen sink without drain board 610x510 mm bowl depth 200 mm. |
| 87 | Tap: [OSR 3.2.14 (vi)]- Fixing of Brass Screw-down Bib Cocks (Taps) polished bright conforming to IS:781-1995 of the following nominal sizes as per specification complete. |
| 88 | Nahini Trap: (LMR) Providing and fixing 10 cm rigid PVC Nahani trap including bend,connecting piece of PVC pipe up to the outside face of wall ,making the good damaged surface and testing etc. complete ( Prior approval of sample and brand by Ex. Engr. is necessary before use) |
| 89 | Supply Pipe (10kgf/cm2): (OSR 3.2.4) Providing and fixing Polyvinyl Chloride (PVC) pipes, having thermal stability for water supply including all PVC fittings .This includes jointing of pipes & fittings with one step PVC solvent & testing of joints complete as per direction of Engineer in Charge. |
| 90 | OSR 3.2.4 (ii) 20mm |
| 91 | OSR 3.2.4 (iii) 25mm |
| 92 | OSR 3.2.4 (iv) 32mm |
| 93 | OSR 3.2.4 (vi) 50mm |
| 94 | Ball Valve : (OSR 3.2.18) Providing and fixing Polyvinyl Chloride (PVC) Ball Valve,This includes jointingwith one step PVC solventas per direction of Engineer in Charge. |
| 95 | 25mm |
| 96 | 32mm |
| 97 | 50mm |
| 98 | 90mm |
| 99 | Drain Pipes ( 6Kg/cm2 ) : (OSR 3.1.4) Providing and fixing Polyvinyl Chloride (PVC) pipes, having thermal stability for drain water including all PVC fittings. This includes jointing of pipes & fittings with one step PVC solvent & testing of joints complete as per direction of Engineer in Charge. |
| 100 | 90mm |
| 101 | 160mm |
| 102 | 200mm |
| 103 | PVC Fittings( 10 Kg/cm2 ) : (OSR 3.2.18) Providing and fixing Polyvinyl Chloride (PVC) Coupler,This includes jointingwith one step PVC solventas per direction of Engineer in Charge. |
| 104 | 160mm Dia Coupler |
| 105 | 200mm Dia Coupler |