| 1 | Taking down carefully, after noting meter reading, by disconnecting and unscrewing from boards /outlets boxes, TPN Boxes electric meters of any size, rating, of any locations and depositing and handover to E & M storesas per bldg inventory and making good the disturbed surfaces after installation of new meters complete all as directed. |
| 2 | Design, installation, testing and commissioning, integrate and maintain the Advanced Metering infrastructure (AMI) comprising of folowing:-(a) Supply, installation, testing and commissioning of Smart Meters of different makes (not more than 33 % of a particular make to ensure interchangeability at a later date as per BIS 16444 with communication technology including GPRS/RF/Hybrid (RF+GPRS)/ Any other advanced technology as per CEA/ TRAI regulations alongwith polycarbonate meter box.(i) Single phase 3541 Nos.(ii) Three phase 121 Nos(b) Supply/ Planning/ Setup/ Turining of RF Communication infrastructure inclidng Network Management (NMS) & Head End System (HES) for the project area AMI software and associated equipments should be capable of handling at least 5162 Numbers of Meters of different makes as per BIS 16444 with 25 % expansion without any additional infrastructure and cost implication to MES.(c) Supply and set up of Meter Data Management (MDM) system.Contd.. |
| 3 | (d) Integration of different devices of different makes/ equipment/ software covered in scope of this project with each other as per functional requirements, including water charges, furnitrue and license fees.(e) Integration/ Interfaces of the AMI system with application system like metering/ billing/ collection. Interface has to be provided in the proposed solution to upload and process meter data from these systems.(f) Hosting the system to Government community could server for hosting and management of supplied software application with standby server.(g) Planning, deployment & tuning of communication system incliding cellular network (if required) to meet the performance requirements.(h) Business intelligence, Analytics and Reporting.(j) Return of Dismantled materials to MES store.(k) Training and knowledge transfer.(l) All expenditure including periodoc charges of telecom operator form installation till completion. |
| 4 | Note :(i) The defect liability period will be 2 years from the date of completion.(ii) Any variaiton in quantity of Smart Prepaid Meter (AMI) will be paid/ deducted as per pro- rate basis of serial item No-02(iii) The rent and water supply bills and any other charges or levy will be included in software\"s as decided by GE.Note: Supplementary rate for single and three phase smart meter beyond the quantity mentioned here-in-before are as under:-(a) single phase meter installed as per above mentioned in intem No 02 - Rs 8000/- per meter(b) three phase meter installed as per above mentioned item No 02 - Rs 9000/- per meter |
| 5 | Supply, installation three broadband connections for Bareilly , Hempur and Shajahanpur station with high speed internet connection for two years complete all as directed.(One connection in the name of Garrison Engineer (West)Bareilly and another Two coneection in the name of Garrison Engineer (East)Bareilly) |
| 6 | M&L for integration of additional single/ three phase smart electric meters (as per IS- 16444) in the AMI being provided in this conrtract complete all as specified and directed by Engr in charge |
| 7 | Provision of wireless Report Printer with 12 pages per minute capacity, 600 x 600 dpi with HP, REt, 1200 dpi effective output quality (600 x 600 x 2 dpi with REt, with duty cycle 3,000 single-sided pages per month for report printing complete as required, |
| 8 | Provision of computer PCdesktop with processor i-7- 12700 , 9 Generation, 8-GB RAM, hard disk 1TB, 4-USB Port including 18.5\" monitor of same make, keyboard, mouse,with licensed Operating system (Windows 10), along with 1KVA capacity online UPS all as specified. |
| 9 | Supply and install hi wall five star rated split units indoor/outdoor complete with cordless remote control unit and with in built Heating and Cooling arrangement and Digital Inverter twin rotary of capacity 2 TR complete all as directed. |
| 10 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA |
| 11 | Supply and fix LT Meter box wall mounted made out of CRCA sheet of 2 mm thick indoor type totally enclosed weather ,dust and vermin proof with front opening hinged door and locking arrangement mounted on MS flat iron with clamp welded to suitable size of angle iron frame around panel body duly grouted on wall, 415 Volt, 3 Phase, 4 Wire AC 50 Hz hving 3 phase with neutral aluminium Bas Bar suitable for connection of 12/14 meter, insulated with PVC sleeves, space for fixing three/ single phase smart prepaid meter of suitable capacity 12/14 Nose meter with transparent toughen Glass not less than 4 mm thick for each meter, copper lugs, spacers, Mouting Channel, rubber gasket, locking knobs. Hylam sheets pieces, PVC shrinkable connections, sutiable compartment for each prepaid meter and epoxy powder spray pained with one coat primer complete including taking down old type meter box:-(i) Incoing MCCB 100 Amps 16 KA, 415 V, 4 pole-01 No. (ii) R-Y-B phase LED indicating lamp-03 Nos. (iii) 200 Amps TPN main aluminium bus bar. (vi) Space for mounting three/ single phase smart prepaid meter-12 Nos. (v) All connection with wiring with 10/6 sqmm PVC insulated single core multistranded copper conductor drawing copper thimbles. Sub main wire will be paid separately. |
| 12 | Supply and fix LT Meter box wall mounted made out of CRCA sheet of 2 mm thick indoor type totally enclosed weather ,dust and vermin proof with front opening hinged door and locking arrangement mounted on MS flat iron with clamp welded to suitable size of angle iron frame around panel body duly grouted on wall, 415 Volt, 3 Phase, 4 wire AC 50 Hz having 3 phase with neutral aluminium Bas Barsuitable for connection of 4 meter, insulated with PVC sleeves, spacefor fixing three/singlephase smart prepaid meter of suitable capacity 4 Nos meter with transparent toughen Glass not less than 4mm thick for each meter , Copper lugs, spacers, Mounting Channel, rubber gasket, locking knobs, Hylam sheets pieces, PVC shrinkable connections, suitable compartments for each prepaid meters and epoxy powder spray painted with one coat primer complete includingtaking down old type meter box:-(i) Incoming MCCB 63 Amps 16 KA, 415 V, 4 pole--01 No.(ii) R-Y-B phase LED indicating lamp-03 Nos(iii) 200 Amps TPN main aluminium bus bar(v) Space for mounting three/single phase smartprepaid meter -04 Nos(vi) All connection with wiring with 10/6 sqmm PVC insulated single core multistranded copper conductor drawing through PVC flexible conduitand connected with appropriate size copper thimbles. (Sub main wire will be paid separately). |
| 13 | Supply and fix LT Meter box wall mounted made out of CRCA sheet of 2 mm thick indoor type totally enclosed weather ,dust and vermin proof with front opening hinged door and locking arrangement mounted on MS flat iron with clamp welded to suitable size of angle iron frame around panel body duly grouted on wall, 415 Volt, 3 Phase, 4 wire AC 50 Hz having 3 phase with neutral aluminium Bas Barsuitable for connection of 1 meter,insulated with PVC sleeves, spacefor fixing three/singlephase smart prepaid meter of suitable capacity 1 Nose meter with transparent toughen Glass not less than 4mm thick for each meter , Copper lugs, spacers, Mounting Channel, rubber gasket, locking knobs, Hylam sheets pieces, PVC shrinkable connections, suitable compartments for each prepaid meters and epoxy powder spray painted with one coat primer complete includingtaking down old type meter box:-(i) Incoming MCCB 63 Amps 16 KA, 415 V, 4 pole--01 No(ii) R-Y-B phase LED indicating lamp-03 Nos(iii) 200 Amps TPN main aluminium bus bar(v) Space for mounting three/single phase smartprepaid meter -01 Nos(vi) All connection with wiring with 10/6 sqmm PVC insulated single core multistranded copper conductor drawing through PVC flexible conduitand connected with appropriate size copper thimbles. Sub main wire will be paid separately. |
| 14 | S&F in replacement sheet metal enclosure DB\"s 415 Volts, IP-42, vertical suitable for mounting MCCB\"s, TPN,4 way with 200 Amps rated copper bus bar complete all as directed by Engineer-in-charge. |
| 15 | Supply and Fixingin repairsMCCB TPN 63 Amps, 415V, 16kA ,Thermal Magnetic Release. |
| 16 | Material & labour for sub main wiring with 1100 volt grade two single core PVC insulated and unsheathed cable with stranded copper conductor (FRLS) of following sizes drawn into and including electrical grade PVC conduit not less than 25 mm diawith all accessories fixed concealed including chase cutting in brick/ stone masonry for fixing conduit and making good the disturb surfaces of wall as per existing including multi - stranded copper conductor as earth wire in green colour complete all as specified and directed.Contd... |
| 17 | (a) 2 run of 2.5 Sqmm cable and 1 run of 2.5 sqmm cable connected to common earth dollyNote: Two run of 2.5 sqmm copper cable and one run of 2.5 sqmm copper earth wire and one run of PVC non metallic condure shall be measured as one unit length. |
| 18 | (b) 2 run of 4.0 Sqmm cable and 1 run of 4.0 sqmm cable connected to common earth dollyNote: Two run of 4.0 sqmm copper cable and one run of 4.0 sqmm copper earth wire and one run of PVC non metallic condure shall be measured as one unit length. |
| 19 | (c) 2 run of 6.0 Sqmm cable and 1 run of 6.0 sqmm cable connected to common earth dollyNote: Two run of 6.0 sqmm copper cable and one run of 6.0 sqmm copper earth wire and one run of PVC non metallic condure shall be measured as one unit length. |
| 20 | (d) 4 run of 6.0 Sqmm cable and 2 run of 6.0 sqmm cable connected to common earth dollyNote: Four run of 6.0 sqmm copper cable and Two run of 6.0 sqmm copper earth wire and one run of PVC non metallic condure shall be measured as one unit length. |
| 21 | (e) 2 run of 10.0 Sqmm cable and 1 run of 10.0 sqmm cable connected to common earth dollyNote: Two run of 10.00 sqmm copper cable and one run of 10.00 sqmm copper earth wire and one run of PVC non metallic condure shall be measured as one unit length. |
| 22 | Supply and fix flush sheet metal enclosure SPN DB 8 way with double door IP-42 protection detachable gland plates, flush mounting for MCB fitted with bus bar , earth bar and neutral links all as specified and directed including taking out existing DB complete all as specified and directed. |
| 23 | Supply and fixing 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of single poles and neutral current carrying capacity 40 AMP, in the MCB DB Complete with connection testing and commissioning including taking out existing MCB complete all as specified and directed. |
| 24 | Supply and fixing 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning including Taking out existing MCB complete all as specified and directed. |
| 25 | Supply and install polycarbonate meter box as per IS:14772 with IP-55 ,weather proof and temper proof fire returdant suitable for three phase/ single phase smart prepaid meter , including suitable capacity of MCB TPN(for three phase)/SPN (for single phase) for protection of smart prepaid meters with cable glands for incoming and outgoing cables and locking arrangement for top cover of the box complete all as specified and as directed by Engr-in-charge |
| 26 | Provision for comprehensive operation including periodic charges of telecom operator, smart meter billing from completion of work till the completion of defect liability period of 2 years complete all as specified and directed. |
| 27 | Comprehensive operation and maintenance of system including Project implementation & management, all expenditure including periodic charges of telecom operator, smart meter billing and maintenance, after completion of defect liability period till completion for 08 years extendable to further 2 years after manual agreement complete all as specified and directed.\" |
| 28 | Note for Sl No. 26 & 27:-Penalty Clause:-(a) Any defect/ malfunctioning in meter will have to be resolved within 24 hours failing which payment for that particular meter for concerned month shall not be made to the contractor.(b) In case issue is not resolved for 48 hours, penal recovery double rate quoted shall be made from contractor\"s due. |