| 1 | Requirement of electrical wiring for new computer systems in Simulation lab (EED) and Requirement of electrical connections and earthing for FESEM instrument in CIR Lab. |
| 2 | Supplying and fixing of suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. Complete in all respect.Make- Anchor Roma, Havells crabtree,C&S. |
| 3 | Supplying and fixing of suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. Complete in all respect.Make- Anchor Roma, Havells crabtree,C&S. |
| 4 | Wiring forfollowing circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Complete in all respect.Make- KEI,R.R Kable, Kalinga Premium. HPL, Havells, Rallison, V-Marc 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 5 | Wiring forfollowing circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Complete in all respect.Make- KEI,R.R Kable, Kalinga Premium. HPL, Havells, Rallison, V-Marc 2 X10 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, “C”curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DBcomplete with connections,testing and commissioning etc. as required.complete in all respect.Make- L&T, Havells, Legrand, HPL, C&S. Single pole |
| 7 | Supplying and fixing 63amps rating, FP , 415 volts, miniature circuit breaker (10kA), C curve, suitable for inductive load of followingpoles in the existing MCB DBcomplete with connections,testing and commissioning etc. as required.complete in all respect.Make- L&T, Havells , Legrand, HPL,C&S,ABB, Schnieder, Simens.CAT-B |
| 8 | Supplying and fixing 40 amps rating, DP , 220 volts, miniature circuit breaker (10kA), C curve, suitable for inductive load of followingpoles in the existing MCB DBcomplete with connections,testing and commissioning etc. as required.complete in all respect.Make- L&T, Havells , Legrand, HPL,C&S,ABB, Schnieder, Simens.CAT-B |
| 9 | Supplying and fixing following way, single pole and neutral sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. Complete in all respect. (But without MCB/ RCCB/ Isolator). Make- L&T, Havells , Legrand, HPL,C&S,ABB, Schnieder, Simens. 8 way , Double door |
| 10 | Supplying and fixing following way, single pole and neutral sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. Complete in all respect. (But without MCB/ RCCB/ Isolator). Make- L&T, Havells , Legrand, HPL,C&S,ABB, Schnieder, Simens. 6 way , Double door |
| 11 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, “C”curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DBcomplete with connections,testing and commissioning etc. as required.complete in all respect.Make- L&T, Havells, Legrand, HPL, C&S. Single pole and Neutral |
| 12 | Supplying & fixing DP Sheet steel enclouser on surface/recess along with 32 amps to 40 amp 240 volt\"C\" curve DP MCB complete with all connection, testing commissioning etc as required.complete in all respect.Make- L&T, Havells, Legrand, HPL, C&S. |
| 13 | Supply and burring of Safe Earthing Electrode T-39 Cu CopperCoated,Lengthupto3000mm,outerpipe 76.3mm x 3.2 inner pipe 42.4mm x 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductivemixture(CCM)havinganti corrosive& conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonry housing. (From electrode terminal to switch board, cost of 25 x 3 Copper Strip will be extra). The specification of grounding terminal is 100 Ohm or less and Neutral to earth voltage should be less than 2V AC. |
| 14 | Supply and fixing of two number 8 SWG copper wire in 15 dia G.I. pipe for earthing, laid in ground or in wall duly concealed including the post of cement, sand, labour, T&P other material required for proper completion of the work with2 Nos.8 SWG copper wire. complete in all respect. |