| 1 | Supply and fix in replacement of unserviceable one with new cast iron sluice valve IS 14846 -200 PN1.6 both flanged heavy duty drilled and installed with brass spindle gun metal face rings rubber gasket 3mm thickMS bolts nuts and washers graphite rope complete for the following bore :- |
| 2 | 150 mm bore |
| 3 | 100 mm bore |
| 4 | Dismantling the defective electric driven centrifugal pump setof capacity 100 HP from foundation by opening of coupling and foundation bolts and transporting to workshop for repairing and reassembling after servicing and overhauling complete with oiling/greasing, lubricating the parts including repair / replacement of worn out parts and spray paintng with one coat of existing colour paint and writing SM / MES No with white paint and installation commissioning and testing on full load complete all as specified and directed by Engineer-in-Charge. |
| 5 | Dismantling the defective electric driven centrifugal pump setof capacity 50 HP from foundation by opening of coupling and foundation bolts and transporting to workshop for repairing and reassembling after servicing and overhauling complete with oiling/greasing, lubricating the parts including repair / replacement of worn out parts and spray paintng with one coat of existing colour paint and writing SM / MES No with white paint and installation commissioning and testing on full load complete all as specified and directed by Engineer-in-Charge. |
| 6 | Dismantling the defective electric driven centrifugal jockey pump setof capacity 10-15HP from foundation by opening of coupling and foundation bolts and transporting to workshop for repairing and reassembling after servicing and overhauling complete with oiling/greasing, lubricating the parts including repair / replacement of worn out parts and spray paintng with one coat of existing colour paint and writing SM / MES No with white paint and installation commissioning and testing on full load complete all as specified and directed by Engineer-in-Charge.Note for item Nos 2,3&4:- (i) The rate quoted for this item shall includes labour charge /maint repair and replacement of defective/unserviceable spares/accessories.(ii) Cost of other minor items/spares such as nut, bolts washers, gaskets, paints etc shall be deemed to be included in this item. Major spares such as impellar, ball bearing, motor coupling, foundation bolts, nuts & washer shall be measured and paid separately. |
| 7 | Supply only spare parts of monoblock / centrifugal pumpsets complete all as specified and as directed. |
| 8 | CI impeller for Jockey pump |
| 9 | Ball bearing for Jockey pump |
| 10 | Motor coupling assembly with tyre for Jockey pump |
| 11 | CI impeller for centrifugal pump set |
| 12 | Ball bearing for centrifugal pump set |
| 13 | Motor coupling assembly with tyre for centrifugal pump setof capacity |
| 14 | Foundation bolts with nuts, washers etc |
| 15 | Material and labour for servicingDiesel Engine driven Fire pump complete oil servicing, necessary replacement of below mentioned spares and servicing work for 112BHP fire pump(a) Diesel Filter (Pre+micro) - 2Nos, (b) Engine Oil filter (Spain-on type) - 2 Nos, (c) Engine Oilas required,(d) Radiator Coolant - 1 Liter. |
| 16 | Material and labour for servicingDiesel Engine driven Fire pump complete oil servicing, necessary replacement of below mentioned spares and servicing work for 50BHP fire pump (a) Diesel Filter (Pre+micro) - 2Nos, (b) Engine Oil filter (Spain-on type) - 2 Nos, (c) Engine Oilas required,(d) Radiator Coolant - 1 Liter. |
| 17 | Dismantling self starter ofdiesel engine driven fire pump of any make, opening up, overhauling / servicing including replacement of armature coils bushes carbon brushes, springs, screws, etc., assembling back, re-fixing and testing for diesel engine model 50-112BHP KVA capacity. |
| 18 | Removing the old unserviceable canvas hose pipe and supply, install, connect, test and commission new canvas hose pipe 63mm dia proof pressure Kg.f/cm2 21.4 Burst pressure Kg.f/cm2 35.7 fabric lined 15m long for housing in the fire boxes near hydrants as well as near landing valves |
| 19 | Removing the old unserviceable pressure gauge and Supply, installation, testing and commissioning of new pressure guagesofrange 20 Kg/cm2 for pumpset complete with ball valves for isolation, siphon, fittings |
| 20 | Removing the old unserviceable manual call point and Supply installing testing commissioning of double actionpull push typemanual call point glass break system, housed in MS enclosure with mounting accessories , complete in all respect and all as specified and directed. |
| 21 | Removing the old unserviceable nozzle and supply, install, connect, test and commission of branch pipe, short, GM with 63mm dia male instantaneous inlet and threaded outlet fitted with 15 mm bore nozzle confirming to IS-903 all as specified and directed. |
| 22 | Removing the old unserviceable gunmetal landing valves and taken as credit ,supply, install, connect, test and commissioning of new Hydrants gunmetal landing valves double outlets 63mm dia female outlets. |
| 23 | Removing the old unserviceable rubber hose reel lined hose , supply, install, connect, test and commission new rubber hose reel lined hose 20mm dia fabric lined 30 mtr long with 5mm outlet brass nozzle. |
| 24 | Replacement in repair of unserviceable fire hose cabinet box of size as per requirment of size 800x600x250 mm, made out from 16 gauge MS sheet duly painted with two coats of red colour synthetic enamel paint over a coat of red oxide primer with double leafed glazed shutters ( glaged with 4 mm thick glass ) suitable for housing of two length of canvas hose ,branch pipe, fire hose and nozzle, fireman axe, first aid hose and single outlet landing valve. |
| 25 | Taking up or down U/S MS fire fighting pipe line 150mm including disconnecting the flanged joints including removal from site for sch of credit all as specified |
| 26 | Supplying, fixing, jointing, testing and commissioning, ISI marked, heavy grade, GI pipe, class \"C\" conforming to IS:1239-1982 ISI marked, including fittings such as couplings, bends, elbows and tees, screwed /flanged joints packing rubbers, nuts & bolts laid into trenches /on wall /in ducts below ground, over the floor as per the site requirment in long/short pieces for 150 mm bore all as specified and directed. |
| 27 | Supply lay and connect MS Pipe ERW steel pipe 6.0 mm thickness and fitting shall be all weldingconstruction complete including two coats of synthic ennamel paint over the coat of red oxide with approved colour allnominal dia 150mm. |
| 28 | M & L for preparation of old painted surface of any description of 150mm dia pipe line of fire fighting installation including bends, flanges, valves, etc n. exc 10 cm in width or girth and applying one coat of heat resisting paint first quality of approved colour with colour code all as specified and directed. |
| 29 | Supply and fix in replacement of unserviceable Sounder with new sounder strobe flame proof of 85 DB @ 3 M for audible automatic alarm annunciation and 75 cd flashing at 1 Hz for visual indication with control module. The sounder with strobe with control module shall be flush or surface mountable type with all accessories etc complete and as per technical specification UL listed and all as specified and directed. |
| 30 | Taking down unserviceable wiring and Supply, Laying, Testing, Commissioning of 1100 volts grade, 3 runs of 1.5 sqmm 2 core, FRLSH, multistranded copper cable, armoured with steel strip/wire ISI marked including MS, ERW, Medium grade, 20mm, ISI Marked pipe for laying of cable fixed over the wall/roof, over the surface through saddles /spacers etc for making connections to fire detectors / MCP / SIREN / to control panels etc all as specified and directed. |
| 31 | Supply and fix in replacement ofOld unserviceable wiring and complete checking & repairing of automatic fire pump starting system including replacement of air vessel and pressure switches and control wiring complete from starter to pumps /control connectionsto control panels etc all as specified and directed. |
| 32 | Supply and fix in replacement of old unserviceable fire alarm panel andsupply, Install, testing, commissioning of intelligent addressible fire alarm panel, 5 loop capacity expandable upto 10 loops, with minimum 250 address on every loop, minimum 640 charactors LCD display, battery charger and power supply complete with all mounting accessories furnished with SMF type lead acid battery in above panel for 24 hours backup in case of power failure and 30 minutes in alarm condition . |
| 33 | Lifting & re- assembling of hangar doors leaf of size 15m height & any size in width apprx weight of 6 Ton per leaf for repair and replacement of damaged parts dismantling including provision of necessary hydraulic jacks 3 ton capacity with necessary scaffolding complete for repair/ replacement of unserviceable spares testing commissioning for smooth function of complete hangar door manually/ motorisedNote: All spare like bearing, wheels & shaft/ locking pins will be measured and paid separately as \"Supply only\". Contactor has to give on year garruantee for smoothe operation of hangar doors as directed |
| 34 | Supply & fix unserviceable top & bottom ball bearing of door leaf with new ball bearing fixed as per directed. |
| 35 | Supply & fix of hangar wheel heavy duty double flange steel track wheels of required dia as per sample to match with existed wheel incl taking down as per direction of engr-in-charge. |
| 36 | M&L replacement of gear box cover made out of 1.6mm thick MS sheet with locking arrangement all as per existing six complete all as specified and as directed |
| 37 | Cleaning of iron top/bottom rail in hangar doors leaf slids on that cleaning with sand paper and oil suitable material side surface of rial and making free to move oiling/ greasing in top and side of rial complete of door as directed |
| 38 | Dismantling of motors of any make any capcity of 2/3/4/5 HP, Rewinding of motor completely incl proper varnishin, and refixing of the same at existing site, connection testing & commissioning etc complete all as specified and as directed. |
| 39 | Material and labour for dismantling of unserviceable old gear box of hangar door and supply and fix new worm gear with coupling as per existing all as specified and directed. |
| 40 | Material and labour for dismantling of unserviceable foot mounted motor of hangar door and supply and fix in replacement of foor mounted motor of cap 01 to 03 HP 415 Volt all as specified and directed. |
| 41 | Material and labour for dismantling of unserviceable rotary limit switch and supply and fix new rotary limit swithc all as specefied and directed,. |
| 42 | M & L for dismantling of unserviceable burnt copper conductor cable and supply and fix in replacement of multicore copper conductor FRLSH round cable size 1.5 sqmm 2 core all as specified and directed. |
| 43 | M & L for dismantling of unserviceable burnt copper conductor cable and supply and fix in replacement of multicore copper conductor FRLSH round cable of size of 4 sqmm 4 core all as specified and directed. |
| 44 | Supply and fix in replacement of contactor with coil 32 Amp 4 pole suitable for existing door hangar all as specified and directed. |
| 45 | Taking down fire alarm panel and checking completely with system including all fire alarm detectors check for any fault fixed at any height in the ceiling all as specified and directed by Engineer-in-Charge. |
| 46 | S&F in replacement of Addressable manual call point all as directed |
| 47 | S&F in replacement of Addressable multi sensor heat and smoke all as directed |
| 48 | S&F in replacement of 12x7 AH Battery all as directed |
| 49 | S&F in replacement of Responds idicator all as directed |
| 50 | S&F in replacement of Addressable Smoke detectors all as directed |
| 51 | S&F in replacement of flame detectors point all as directed |
| 52 | Removing of old earthing including earth plate and M&L for Earthing complete with GI earth plate electrode 600 mm x 600mm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 Mtr below ground level with the top edge of earth plate at depth not less than 1.5 Mtr below ground level connected to galvanised iron earth strip 25x4 mmby means of bolts, washers ,watering pipe 20mm dia, medium gradeGI pipe,with welded funnel and wire mesh and 40mm dia medium grade GI pipe with fittingas protection pipe for strip from plate electrode to test point /plant/machineries etc. including necessary excavation and earth work in any type of soil, salt, charcoal dust, concrete pit in PCC (1:3:6) type C-I having outer dimension 60cmx60cmx60cm and internal dimension 30cmx30cmx30cm, pre-caste RCC 1:2:4 type B-1 cover slab of size 350x350x50mm reinforced with 8mm dia deformed bares @15 cm centre to centre both direction and 10 mm dia MS handle of suitable size charcoal or coke and salt in alternative layers,necessary earth work in soft/loose soil all as shown in electrical plate No 3 of MES Schedule Part I and testing complete all as specified and as directed. |