| 1 | Dis-connecting the ACB ( Air Circuit Breaker) panel capacity ranging from 600 to 2000 Amp of Make : CG/ABB /L&T /Simens /Schnider, Over hauling of complete bearker panel by taking out the trolley of the breaker, opening the total mechanism of breaker checking its contact, baffle plates and other minor parts, cleaning the complete accessories carefully. Minor repairs shall be rectified, Parts/accessories shall be cleaned, the tank, baffle plates, rotating contact, upper supports, lower supports, drive assembiesand all other spare parts all as directed by Engineer-in-Charge. Reassembled Breaker after repair/ replacement of the faulty parts, testing and calibration of ACB realy settings complete. 1. This item is considereded for repair and maintanace of LT infrastucture of Bikaner Mil station and different ASCON nodes located at 200 KMs away from Bikaner City. No extra cost for fault finding at ASCON nodes will be given to contractor.2. LT fault / reapir and maintanace intimated to the contractor or his rep at any time day or night, through complaint slip or telephonically must be rectified by the contractor within 8 Hrs. If contractor fails to rectify the fault with in 8 Hrs a panelty of Rs 500 per day per complaint will be deducted till the fault/complaint is rectified.3. All Material required for the repair and matainance work considered in the CA will be made available by the contractor with in 3 Hr.4. Item fixing only will be issued from MES store (AGE E/M yard) based on complaints on daily basis and cost of transportation from mes store to site will be responsibility of the contractor. |
| 2 | Material and labour for replacement of spring charging motor 220 V AC/DC supply. |
| 3 | Material and labour for replacement of Shunt Release EA1 415V AC |
| 4 | Material and labour for replacement of Under-voltage Release 415V AC |
| 5 | Material and labour for replacement of Closing Preventer 415V AC |
| 6 | Material and labour for replacement of Supply only Jaw contact Assy. 630/1000A S1 |
| 7 | Material and labour for replacement of Jaw contact Assy. 800/1000A C/H & 1250A S1 |
| 8 | Material and labour for replacement of Jaw contact Assy. 1250/1600A C/H, 1600/2000A S1 |
| 9 | Material and labour for replacement of Pole Assy. 630-1250 S1 D/O |
| 10 | Material and labour for replacement of Pole Assy. 1250/1600 C & 1600 S1 D/O |
| 11 | Excavation in trenches not exceeding 1.5 mtr wide, and not exceeding 1.5 mtr in depth; for laying of cables, pipes in soft/loose soil etc and not exceeding 10 Sqmon plan and getting out including trimming of sides complete all as specified and directed by Engineer-in-Charge |
| 12 | Returning filling in, including spreading , levelling, watering and well ramming in layers each not exceeding 25cm in soft/loose soil complete all as specified. |
| 13 | Removing surplus spoil to distance not exceeding 50metre and depositing where directed at level not exceeding 1.5metre above the starting point complete all as specified. |
| 14 | Supply and laying un-reinforce precast concrete cable cover, class LV type-1 size 250 mmX150 mmx 40mm for protection of cablecomplete all as specified and directed by Engineer-in-Charge |
| 15 | Local tibba dry sand cushioning and cover (8 cmthick layer of sand before laying of cable and 15 cm thick layer of sand after laying of cable)for protection of cable, material and labour complete all as specified and as directed by Engineer-in-Charge. |
| 16 | Material and labour forCable indoor/outdoor end terminal jointing kit for LV/LT 1100 V cable heat shrinkable type joint kit complete with jointing material, 04 Nos coloured sleeves(Red, Blue, Yellow and black) each 45 cm long and accessories thimbles etc suitable for 25 sqmm to 50 sqmm 3.5 core XLPE armoured aluminium conductor cable including testing after jointing fixing in replcement complete all as specified and as directed by Engineer- in - charge. |
| 17 | Ditto All as per Srl Item No.07 Here in above but 70 Sqmm to 150 sqmm 3.5 corecomplete all as specified and directed by Engineer-in-Charge |
| 18 | Ditto All as per Srl Item No.07 Here in above but 185 Sqmm to 300 sqmm 3.5 corecomplete all as specified and directed by Engineer-in-Charge |
| 19 | Ditto All as per Srl Item No.07 Here in above but 400 Sqmm 3.5 corecomplete all as specified and directed by Engineer-in-Charge |
| 20 | Material and labour forCable jointing kitfor LV/LT 1100 V cable for straight through, heat shrinkable type joint kit complete with jointing material and accessories suitable for 25 Sqmm to 50 Sqmm 3.5 coreXLPE armoured aluminium conductor cable including testing after jointing, fixing in replacementcomplete all as specified as directed by Engineer-in-Charge. |
| 21 | Ditto All as per Srl item No 11 here in above but 70 Sqmm to 150 sqmm 3.5 Core complete all as specified and directed by Engineer-in-Charge |
| 22 | Ditto All as per Srl item No 11 here in above but 185 Sqmm to 300 sqmm 3.5 Core complete all as specified and directed by Engineer-in-Charge |
| 23 | Laying onlyin replacement Cross linked poly-ethylene (XLPE) insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables ( heavy duty) with strandedaluminium conductor, 1100 voltsLT grade of cross-sectionalarea 10 Sqmm 02 core laid in trenches/through pipein road crossings/ paths /drains /ducts /floors /along poles/walls/ceilings/ equipments etcsupplied, fixed/ laid in repair including commissioning and testingcomplete all as specified and as directed by Engineer-in-Charge.(Note: :-(i) Necessary excavation and earth work, brick protection, sand cushioning and cover and GI pipe shall be measured and paid for separately.(ii) Road manually cutting/floor cutting/cutting holes etc in wall required for laying /fixing of cable etc shall be made good as per existing site condition. Nothing extra shall be admissibleon this accountand quoted rate for this item shall bedeemed to include for the same) |
| 24 | Ditto All as per Srl item No 14 here in above but size of cable 16 Sqmm 4 core |
| 25 | Ditto All as per Srl item No 14 here in above but size of cable 25 Sqmm 4 core |
| 26 | Ditto All as per Srl item No 14 here in above but size of cable 35 Sqmm 3.5 core |
| 27 | Ditto All as per Srl item No 14 here in above but size of cable 50 Sqmm 3.5 core |
| 28 | Ditto All as per Srl item No 14 here in above but size of cable 95 Sqmm 3.5 core |
| 29 | fixing onlyin replacement GI pipe light grade 40 mm bore (ISI marked) laid in trenches/ road crossings/ fixed to poles/ceiling / along walls/ path /drain/floors with and including all necessary clamps, nuts, bolts, washers etc and all fittings as required, complete all as specifiedand as directed by the Engineer-in-Charge.(Note :- Necessary excavation, earth work and same work shall be measured and paid for separately.) |
| 30 | Ditto All as per Srl item No 20 here in above but dia of pipe 50 mm |
| 31 | Boring of holes under road 100 mm dia, pavement, hard standingby trench less technology(manually) with out disturbing the top surface of roadsfor laying of cables/GI pipescomplete all as specified and as directed by the Engineer-in-Charge. |
| 32 | Taking out old LT underground cable from trench depth upto 1.5 mtrs and laying after removing of defects any type/size laid in trenches including testingcomplete all as specified and as directed by Engineer-in-Charge. |
| 33 | fixing only in replacementdigital type tree phase Ampere meterrange 0–400/300/200 Amps, with built in selector switch includingCTs with proper ratio, square type, flush mountedincluding making connection with copper conductor cable of suitable size complete all as specified and as directed by Engineer-in-charge. |
| 34 | fixing onlyin replacementdigital type Volt meter with built in selector switch, range 50 – 520 volts, square type, flush mounted , accuracy class 1.0, Aux supply 80-300 VAC, CT seconday site selectable 1A/5A, CT/PT programmable frequency including making connection with copper conductor cable of suitable size complete all as specified and as directed by Engineer-in-charge. |
| 35 | fixing onlyin replacementMCCB, 63 Amps, 4 pole, 415 Volts, rupturingcapacity not less than 25 KA, Icu=100% Ics, thermal magnetic trip with built in protection function for overload, short circuit andfast tripping mechanism Adjustable typecomplete withspreader link including thimbles, nuts, bolts, washers etc. making including incoming and outgoing connectioncompleteall as specified. |
| 36 | fixing only in replacementMCCB, 100 Amps, 4 pole, 415 Volts, rupturingcapacity not less than 25 KA, Icu=100% Ics, thermal magnetic trip with built in protection function for overload, short circuit and fast tripping mechanism Adjustable typecomplete withspreader link including thimbles, nuts, bolts, washers etc. making including incoming and outgoing connectioncompleteall as specified.Make :- Havells/L&T/legrand |
| 37 | fixing onlyin replacementMCCB, 160 Amps, 4 pole, 415 Volts, rupturingcapacity not less than 25 KA, Icu=100% Ics, thermal magnetic trip with built in protection function for overload, short circuit andfast tripping mechanism Adjustable typecomplete withspreader link including thimbles, nuts, bolts, washers etc. making including incoming and outgoing connectioncompleteall as specified. |
| 38 | fixing onlyin replacementMCCB, 200 Amps, 4 pole, 415 Volts, rupturingcapacity not less than 36 KA, Icu=100% Ics, thermal magnetic trip with built in protection function for overload, short circuit and fast tripping mechanism Adjustable type complete withspreader link including thimbles, nuts, bolts, washers etc. making including incoming and outgoing connectioncompleteall as specified. |
| 39 | fixing onlyin replacementMCCB, 320 Amps, 4 pole, 415 Volts, rupturingcapacity not less than 36 KA, Icu=100% Ics, thermal magnetic trip with built in protection function for overload, short circuit and double break fast tripping mechanism Adjustable type complete withspreader link including thimbles, nuts, bolts, washers etc. making including incoming and outgoing connectioncompleteall as specified. |
| 40 | fixing only in replacementMCCB, 400 Amps, 4 pole, 415 Volts, rupturingcapacity not less than 36 KA, Icu=100% Ics, thermal magnetic trip with built in protection function for overload, short circuit and fast tripping mechanism Adjustable type complete withspreader link including thimbles, nuts, bolts, washers etc. making including incoming and outgoing connectioncompleteall as specified |
| 41 | fixing onlyin replacementMCCB, 630 Amps, 4 pole, 415 Volts, rupturingcapacity not less than 50 KA, Icu=100% Ics, thermal magnetic trip with built in protection function for overload, short circuit andfast tripping mechanism Adjustable type complete withspreader link including thimbles, nuts, bolts, washers etc. making including incoming and outgoing connectioncompleteall as specified. |
| 42 | Repair of manual operated PF control panel/ micro processor based automatic power factor control panel capacity of 21 KVAR to 500 KVAR fixed on various locations including testing, checking and repair and after removing deposited dust/seals/sludge and including taking out burnt/defective items and after fixing required necessary new items ie capacitor, MCBs, circuit wiring etc all as directed by Engr-in-Chaerge. |
| 43 | Material and labour for replacement ofMPP type heavy duty power factor improvement capacitor (H/D ) with connector suitable for indoor/out door operation and provided with discharge resistors of rated voltage 440 v 50 HZ 3 phase with delta connection of rating 1 KVAR to 35 KVAR all as specified Make : L/T , SIEMEN Epcos |
| 44 | fixing only in replacement ofMiniature circuit breaker triple pole 63 Amp (C curve) 10 KA ofcapacity complete all as specified and directed by Engineer-in-Charge |
| 45 | fixing only in replacementMCCB, 100 Amps, 3 pole, 415 Volts, rupturingcapacity not less than 25 KA, Icu=100% Ics, thermal magnetic trip with built in protection function for overload, short circuit andfast tripping mechanism complete withspreader link including thimbles, nuts, bolts, washers etc. making including incoming and outgoing connectioncompleteall as specified. |
| 46 | fixing onlyin replacementMCCB, 160 Amps, 3 pole, 415 Volts, rupturingcapacity not less than 25 KA, Icu=100% Ics, thermal magnetic trip with built in protection function for overload, short circuit and ast tripping mechanism complete withspreader link including thimbles, nuts, bolts, washers etc. making including incoming and outgoing connectioncompleteall as specified. |
| 47 | Material and labour for replacement ofLT current transformers of capacity 100/5,200/5,300/5,500/5,Amps complete all as specified and directed by Engineer-in-Charge Make Alfa/ AE/ Veeco |
| 48 | fixing only Panel mounted 3 Pole contactor of suitable rating operational voltage 500 volts, AC 50 HZ, inbuilt aux. contacts- 1 No + 1 NC or 2 NO + 2 NC with standard coil voltage 220 volts the surge resistor contract shall be post break type and damping resistances after closing be cut of current rating cap 15 Amp. |
| 49 | Ditto all as per item No. 39 here in before but rating of capacity 25 Apms complete all as specified and directed by Engineer-in-Charge |
| 50 | Ditto all as per item No. 39 here in before but rating of capacity 40 Amps complete all as specified and directed by Engineer-in-Charge |
| 51 | Ditto all as per item No. 39 here in before but rating of capacity 63 Amps complete all as specified and directed by Engineer-in-Charge |
| 52 | Ditto all as per item No. 39 here in before but rating of capacity 100 Amps complete all as specified and directed by Engineer-in-Charge |
| 53 | fixing onlyin replacement APFC Relay 8 stage with built in multifuction meter for basic, THD and energy with 1 CT/3 CT sensing Option, smart switching, auto setup, THD protection, dual target PF, RS 485 communication, remote monitiring software complete all as directed by Eng-in-charge |
| 54 | Ditto all as per item No. 44 here in before but for 12 stage complete all as specified and directed by Engineer-in-Charge |
| 55 | Supply, installing, commissioning and testing factory made and tested (CPRI type test certified) LT Feeder Pillar Box cubical type (KIOSK) of size as per IS specifications, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, protection class IP-53, dust & vermin proof for outdoor use, made out of CRCA sheet 3.15 mm thick, powder coated inside & outside of flint grey shade (RAL-7032), machine pressed, both side opening in two halves with provision of rubber beading and locking system, including copperbus bar of 300 Amp capacity, 4 strip in colour code mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers for each MCCB/cubical switch shall have the independent opening, panel shall be mounted on angle iron frame and legs made from angle of size 50x50x5 mm including internal wiring with PVC insulated stranded copper conductor FRLSH cables of appropriate size but not less than 6 sqmm with proper ferrule & cable glands, including danger notice sticker, comprising & including the following accessories complete all as specified and as directed. |
| 56 | Description of serial item No. 46.00 contd…(a)MCCB 200 Amp 36 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current adjustable tybe complete with spreader link and extendable ON/OFF rotary handle - 01 No. (Incomer). Make:ABB/Siemens/ Schneider/Legrand.(b) MCCB 63 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current complete with spreader link and extendable ON/OFF rotary handle - 06 Nos (Outgoing). Make:ABB/Siemens/ Schneider/Legrand.(c) MCB 32 Amp 10 kA, 2 Pole, Icu=100% Ics- 02 Nos (Outgoing). Make: ABB/Siemens/ Schneider/Legrand.(d) Indicator Set RYB, “LED” type (set of three) -01 Set(e) Digital Amp meter (0-300) Amp with built in selector switch including necessary CTs(set of three) - 1 Set(f) Digital Volt meterwith built in selector switch (0-500) - 01 No. |
| 57 | M & L for earthing complete with GI Earth Plate Electrode 600mm x 600mm x6mm, thick burieddirectlyin ground vertically to a depth not less than 2.25 Metre below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 Metre below Normal Ground Level, connectedto Galvanised ironearthstrip 32X6 mm drawn through and including Galvanised Ironprotection Pipe 40 mm bore (dia) Light grade uptoheightl of thetransformer foundation where foundation situated by means of Bolts, Nuts, Check Nuts and Washers etc Earth plate surrounded by a packed thickness of charcoal or coke dust mixed with common salt in alternate layers of not exc 150mm thick PCC Pit in cement concrete 1:3:6 (20 mm graded aggregrate ), Precast RCC1:2:4 (20mm graded aggregrate )cover slab 350 x350 x 50mm thick reinforced with and including 8mm dia TMT Bars @ 10 cmCentre to Centreboth ways GIWire Mesh , Funnel, with GI Watering Pipe 20mm bore dia Medium grade necessary excavation in soft loose soil returning filling in and removal of surplus soil upto a distance of 50 METRE and all asshown in Electrical Plate No. 3 of MES schedule Part- I and testing on completion complete all as specified and as directed. |