| 1 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface/truss as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 2 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sqmm |
| 3 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in ground including excavation and refilling of trench etc as required, but excluding sand cushioning andprotective covering Upto 35 Sqmm |
| 4 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 way(4+12), Double door |
| 5 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way |
| 6 | Supplying and fixing 5 to 32 A rating, 240/415V, 10kA, \"C\" curve, miniature circuit breaker suitable for inductive load of the following poles existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 7 | Single pole |
| 8 | Double pole |
| 9 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A |
| 10 | Supplying and fixing following rating, double pole (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A |
| 11 | Earthing with G.I. plate earth plate 600mm x 600mm x 6mm thick including accessories , and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coal and salt as required |
| 12 | Providing and laying earth electrode connection from earth electrode with 6 SWG dia GI wire in 15mm dia GI Pipe from earth electrode including connection with GI thimble excavation and re-filling as required. |
| 13 | Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing as required |
| 14 | Supplying and fixingof the following sizes of steel conduit along with accessories in surface /recess including painting in case of surface conduit or cutting the wall and making good the same in case of recessed conduit as required 25 mm |
| 15 | Supplying and drawing following sizes of FRLS PVC insulated copper condutor, single core cable in the existing surface/recessed steel/ PVC conduit as required. |
| 16 | 5 x 4 sqmm |
| 17 | 3 x 1.5 sqmm |
| 18 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required. |
| 19 | Supply of the following sizes PVC insulated and PVC sheathed / XLPE POWER CABLE of 1.1 kv grade armoured Al. cablecompulsory ISI mark confirming to IS:7098/ PART –I / 88 with amendment no.1 |
| 20 | 4 x 16 sqmm cable |
| 21 | 2 x 6 sqmm cable |
| 22 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size OverHead using 8 SWG GI wire, Shackle insulator, clamp, nut bolt cable clips etc as required. Upto 35sqmm |
| 23 | Supplying and fixing out door type loop in loop out cable junction box (200 mm X 150 mm X100 mm)fabricated from 1.6 mm MS sheet enclosed wheather proof, dust proof, water proof and locking arrangement internally embedded gasket with bottom cable entry plat through cable glands. Seperate for incoming and out goingcables and wires duly fitted with following in it.HD Connector for 10 to 16 sqmm-4 Nos.6 amp SP \"C\" curve 10 KA MCB-1 No.fixing Clamps-2 Nos. |