| 1 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Outgoing SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Frequency Meter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Double Core Epoxy Casted CT with CTR :100-50/5-5A,TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixingof earthing & Feeder Name Plate with Name of feeder written on itby using high intensity reflective Tape |
| 2 | Supply, Carriage upto site (including Loading/Unloading), Testing andErection ofSteel Tubular Pole, 9 Mtr. Long Pole(ST-410 SP33) with planting depth of 1/6 th of the height of the pole, (9 mtr. Long ) as per approved drawings/standards |
| 3 | Carriage upto site (including Loading/Unloading), Laying ,Stringing, Tensioning & Binding ofACSR Conductor, (100mm2 ACSR Conductor) (Conductor to be provided by the department)as per approved drawings/standards |
| 4 | Supply, Carriage upto site (including Loading/Unloading),Testing,Fabrication & Fixing of GI Channel/Angle/Flat of sizes including clamps as per approved drawings/standards |
| 5 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm as per approved drawings/standards |
| 6 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting as per approved drawings/standards |
| 7 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 11 kV Isolator, Double Break,3-pole, 630 Amp, Horizontal mounting Type, with Earth Switch (Reputed Make, Sample to be approved before installation) as per approved drawings/standards (1 Set- 3 Pieces) |
| 8 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type (Reputed Make) as per approved drawings/standards (1 Set-03 No.) |
| 9 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Spike Earthing Rod 20mm 2,5 Mtr long with GI strip (25x3)mms as per approved drawings/standards |
| 10 | Supply,Testing,Loading,Carriage,Unloading and fixing ofGalvanised Nuts & Bolts of sizes |
| 11 | Supply,Testing,Loading,Carriage,Unloading and fixing ofDanger Plates with Clamps as per approved drawings/standards |
| 12 | Supply,Testing,Loading,Carriage,Unloading and fixing of Anti-Climbing Device with Clamps as per approved drawings/standards |
| 13 | Providing & Painting of Poles with one coat of Red Oxide and two coats of aluminium paint and as per approved drawings/standards |
| 14 | Supply,Carriage upto site (including Loading/Unloading), Laying & Testing of Cement bottoming for ST Poles 9 Mtrin the mixture of 1:2:40.48 cum/pole as per approved drawings/standards |
| 15 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make)as per approved drawings/standards |
| 16 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 36 V,200 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply of reputed make)as per approved drawings/standards |
| 17 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of Battery Bank 36 V,200 AH , of 18 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant of reputed make) as per approved drawings/standards |
| 18 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 11kV Three core 185 mm2 Aluminium wound wire Armoured XLPE Cable as per approved drawings/standards |
| 19 | Supply, Carriage upto site (including Loading/Unloading),Testing,Fabrication & Fixing of Mild Steel Chequered Plates, Material Grade: Is 3502, 8 mm as per approved drawings/standards |
| 20 | Supply, Carriage upto site (including Loading/Unloading) & Fixing of Rubber Mat 1mx2m 19mm thickness as per approved drawings/standards |
| 21 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of11 kV Heat Shrinkable Outdoor Cable Termination Kit suitable for 185 mm² ( 3 Core) cable as per standards |
| 22 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of11 kV Heat Shrinkable Indoor Cable Termination Kit suitable for 185 mm² ( 3 Core) cable as per standards |