| 1 | Excavation in trenches not exc 1.5m in width and 1.5 m in depth and getting out excavated soft/loose soil complete all as specified and as directed. |
| 2 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25cm complete all as specified and as directed. |
| 3 | Removing excavated material / soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 4 | Supply and layfine sieved excavated dry soilcushioning spreading levelling for cable trenches complete all as specified and directed. (Note: Punned thickness only shall be measured and paid.) |
| 5 | Supply and laying well burnt bricks sub class \"B\" in trenches for cable protection of U/G cable complete all as specified and directed. |
| 6 | Taking out the existing PVC/XLPE, 1100 volts grade,LT UG electric cable of size 95 sqmm x 3.5 corefrom trenches/ walls (or) passing through pipes/in floor, removing the unserviceable fault cable andcarefully stacking the serviceable cable for reusing complete all as specified and directed.Note:- Excavation and Earth work shall be measured and paid separately under appropriate item. |
| 7 | All as per item No.6abovebut150sqmm 3.5 core |
| 8 | All as per item No.6 abovebut185 sqmm 3.5 core |
| 9 | All as per item No.6 abovebut240 sqmm 3.5 core |
| 10 | Laying only the under ground cable any typeobtained fromItems No -06 above in trench/wall/floor etc are connecting with suitable cable lugs/sleeves etc, size 95sqmm 3.5 corecomplete all as specified and directed . |
| 11 | Laying only the under ground cable any typeobtained fromItems No -07 above in trench/wall/floor etc are connecting with suitable cable lugs/sleeves etc, size 150sqmm 3.5 corecomplete all as specified and directed . |
| 12 | Laying only the under ground cable any typeobtained fromItems No -08 above in trench/wall/floor etc are connecting with suitable cable lugs/sleeves etc, size 185sqmm 3.5 corecomplete all as specified and directed . |
| 13 | Laying only the under ground cable any typeobtained fromItems No -09 above in trench/wall/floor etc are connecting with suitable cable lugs/sleeves etc, size 240sqmm 3.5 corecomplete all as specified and directed . |
| 14 | Supply & Lay in trenches, fixed on wall (or) passing through pipes/in floors, connecting up, testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 95 sqmm 3.5 core complete all as specified and as directed. |
| 15 | All as per item No. 14.00 above but 150sqmm 3.5 core |
| 16 | All as per item No. 14.00 above but 185sqmm 3.5 core |
| 17 | All as per item No. 14.00 above but 240sqmm 3.5 core |
| 18 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable including taking down old existing one of size 95 sqmm 3.5 core complete all aspspecified and as directed. |
| 19 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable including taking down old existing one of size 150to 185 sqmm 3.5 core complete all aspspecified and as directed. |
| 20 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable including taking down old existing one of size 240to 300 sqmm 3.5 core complete all aspspecified and as directed. |
| 21 | M & L for GI pipe light grade of size 100mm in trenches /fixed on walls by suitable clamps and jointing including taking down existing old pipes complete all as specified and as directed. |
| 22 | S&F for PCC type C1 1:3:6 (20mm graded aggregate) as in foundations, filling and mass concrete complete all as specified and directed. |
| 23 | Fabrication and installation of cable route indicatormade out of 10 mm thick CI plate , oval shape of suitable size and embossed withMark of\"MES LT Cable \" including 30 cm length angle iron support and embedded in and including PCC,including taking down existing old one complete all as specified and as directed. |
| 24 | S& F for GI earthing strip 25x4 mm with nut and bolts complete includingtaking downold one allas specified and directed. |
| 25 | S&F of GI Strip ISI marked of size 32 x6 mm complete with nuts, bolts and washers, buried in ground including excavation and taking down existing old ones complete andall as specified and directed. |
| 26 | S & F Automatic Power Factor Correction(APFC) Panel for 3 Phase, 415 V & 50 Hzsystem of capacity2KVARincluding MCCB and taking downexisting old ones complete all as specified and directed |
| 27 | S & F Automatic Power Factor Correction(APFC) Panel for 3 Phase, 415 V & 50 Hzsystem of capacity5 KVARincluding MCCB and taking downexisting old ones complete all as specified and directed |
| 28 | S & F Automatic Power Factor Correction(APFC) Panel for 3 Phase, 415 V & 50 Hzsystem of capacity 10KVARincluding MCCB and taking downexisting old ones complete all as specified and directed |
| 29 | Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar of outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openablefrom both front and rear side made out of 3mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approvedhaving front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers. Including taking down the old panelrequired at site and comprising following:-Note :- (i)The rate deemed to be inclusive of disconnecting theLT cable and reconnecting the same with suitable size of cable glands and connecting complete.(ii)LT danger noticewith conventional skull and bones indication written with English and local language. |
| 30 | Incoming (a) S&Ffor Electrolytic grade high conductivitysolid 4 Nos Alubus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleeves.The bars shall be colour coded at required intervals for identification- 04 Nos(b )S&F for LED Indicating lamps for Main Supplyindicating R\", Y\" B\"- 01 Set of 3(C ) S&F Digital Multi Function meterNos -01 (d )S&F for MCCB 400 Amp 36KA 4 pole Thermal magnetic setting complete- N0s -01 Outgoing (a )S&FMCCB of 4 poleof capacity100 amps, with breaking capacity of16 KA with fixed thermal & fixed magnetic setting- 04 Nos (b )S&FMCCB of 4 poleof capacity125 amps, with breaking capacity of16 KA with fixed thermal & fixed magnetic setting- 04 Nos |
| 31 | Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar of outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openablefrom both front and rear side made out of 3mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approvedhaving front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers. Including taking down the old panelrequired at site and comprising following:-Note :- (i)The rate deemed to be inclusive of disconnecting theLT cable and reconnecting the same with suitable size of cable glands and connecting complete.(ii)LT danger noticewith conventional skull and bones indication written with English and local language. |
| 32 | Incoming (a) S&Ffor Electrolytic grade high conductivitysolid 4 Nos Alubus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleeves.The bars shall be colour coded at required intervals for identification- 04 Nos(b )S&F for LED Indicating lamps for Main Supplyindicating R\", Y\" B\"- 01 Set of 3(C ) S&F Digital Multi Function meterNos -01 (d )S&F for MCCB 350 Amp 36 KA 4 pole Thermal magnetic setting complete- N0s -01 Outgoing (a )S&FMCCB of 4 poleof capacity63 amps, with breaking capacity of16 KA with fixed thermal & fixed magnetic setting- 02 Nos (b )S&FMCCB of 4 poleof capacity160amps, with breaking capacity of36 KA with fixed thermal & fixed magnetic setting- 03 Nos (c )S&FMCCB of 4 poleof capacity200amps, with breaking capacity of36 KA with fixed thermal & fixed magnetic setting- 03 Nos |
| 33 | M&L for Repair to LT Panel board, dismantling the door and attending repair works to Hinges by providing suitable welding work, including repairs to Locking arrangement, complete including replacement of worn-out rubber beadings and covering the cable incoming and outgoing entry points with suitable MS sheets etc, and scraping, removal of rust and complete removal of existing painting, cleaning and applying spray painting with two coats of synthetic enamel paint after attending welding work over a corroded portion andcoat of red oxide primer and black for base frame complete all as specified and directed. |
| 34 | Earthing complete with galvanisedsteel earth plate electrode of size60cm x 60cm x6 mm thick buried directly in ground( earth pit not less than 2.25 m deep below the normal ground level) with top edge of the plate not less than 1.5m below normal GL connected to GI earth strip of size 32x6 mm by means ofbolts, nuts, check nuts washers of GI or steel all asshown in electrical plate No-5 of SSR Part I connected to machinery/equipments installed power house/sub station all as specified including testing on completion complete all as specified and as directed. Note: The unit rate shall also include for excavation earth work in any type of soil PCC (1:3:6) type C1 pit RCC 1:2:4 type B-1 cover reinforced with 8 mm dia CTD bars @ 150mm C/C both ways funnel with 15mm bore GI watering pipe 20mm dia bore GI protection pipe wire mesh and copper lugs complete in addition to item No 1(a) to (e) of preamble ( Notes) Under sub heading earthing specified on SI page NO-389 of SSR Part-II 2004. |