| 1 | COPPER WIRING IN EXISTING PVC/MS CONDUIT PIPE SURFACE/RECESSED FOR ELECTRICAL POINTS Wiring only in 1.5 sqmm PVC insulated copper conductor cable for LIGHT/FAN/Call bell point in existing conduit pipe and MS boxes including cost of Bakelite cover for MS box, switch, wall socket, ceiling rose/connector etc. Group C |
| 2 | Wiring only in existing conduit and MS box for Twin control light point with 2 nos , 2-ways, 5 amp. switch in 1.5 sqmm FRLS PVC insulated copper conductor cable . Group C |
| 3 | Wiring in existing conduit and MS box for 3-pin 5amp. Plug point by using 2 no 1.5 sqmm FRLS copper wire and 1 no 1.5 Sqmm FRLS copper wire , including providing 1 no 5/6 Amp 3/5 pin socket and 1 no 5/6 Amp switch etc complete as required Group C |
| 4 | Wiring in existing conduit system for 3-pin 15amp. Plug point by using 2 no 4 sqmm FRLS copper wire and 1 no 4 Sqmm FRLS copper wire for earthling , including providing 1 no 15/16 Amp 3/6 pin socket and 1 no 15/16 Amp switch etccomplete as required Group C |
| 5 | Wiring main and sub mains in twosingle core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 1.50 Sqmm(1/1.40mm) |
| 6 | 1 run of Size 4 Sqmm(1/2.24mm) |
| 7 | FITTING AND ACCESSORIES Providing and fixing GI concealed sheet metal boxes with inner and outer face plate including concealing the box in wall and fixing in position with inner plate and face plate with all labour and material required for the job complete in all respects. 1 & 2 Modules including combined plate for Telephone and data |
| 8 | 3 Modules |
| 9 | 4 Modules |
| 10 | 6 Modules |
| 11 | 8 Modules |
| 12 | 12Modules |
| 13 | Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. 5 amp 1 way switch |
| 14 | 5 amp 2 way switch |
| 15 | 15 amp 1 way switch |
| 16 | 5 amp Socket |
| 17 | 15 amp 6 pin Socket |
| 18 | Step type Fan Regulator 2 modules 300 watt |
| 19 | Erection of exhaust fan in existing opening, complete with necessary earthling of fan including carriage from PWD store to the site of work. |
| 20 | Making suitable hole in the wall suitable for exhaust fan up to 450 mm sweep including finishing the same and fixing of Stainless stell wire mesh 2 mm thick having about 50 meshes per inch at exhaust sidecomplete as required |
| 21 | Providing and fixing outdoor duty Ply of 8 mm thick frame suitable for exhaust fan up to 450 mm sweep etc complete as required |
| 22 | Fixing of LED Tube light/ 2*2 ft square panel fitting directly on wall /ceiling or false ceiling including making connections etc as required. |
| 23 | Fixing of LED Down lighter 7 to 28 Watt on ceiling or in false ceiling , including cutting/making hole in ceiling including making connections etc as required |
| 24 | MCCB ,DISTRIBUTION BOARDS, MCB\"s, RCCB\"s, CHANGE OVER etc. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. Triple pole MCCB 16 to 100 Amp, 25 KA |
| 25 | Triple pole MCCB 600 to 800 Amp, 50 KA |
| 26 | 4 pole MCCB 6 amp to 100 amp, 25 KA |
| 27 | 4 pole MCCB 200 to 250 amp, 25 KA |
| 28 | 4 pole MCCB 300 to 400 amp, 50 KA |
| 29 | 4 pole MCCB 600 to 800 Amp, 50 KA |
| 30 | MCCB Enclosure made of Sheet Steel suitable for mounting MCCB of following ratings MCCB up to 250 A FP |
| 31 | MCCB above 250 A and up to 630 A FP |
| 32 | Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to to the entire satisfaction of the Engineer-in-Charge of the work. TPN DBHorizontal type Double Door 4 way ( 8 incoming and 3phase*4 outgoing) |
| 33 | Supply and erection of miniature circuit Breaker/isolator 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp Single Pole |
| 34 | 40 amp to 63 amp. MCB\"s Four Pole |
| 35 | SITC Four pole ON LOAD Manual change over switch in SS enclosureof following Ratings 100 amp 415 volts |
| 36 | MS STAND, BUS BAR CHAMBER AND PANELS Supply, installation, testing and commissioning of load bank with digital meter module cost of digital Amp./ volt meter with selector switch wiring (but EXCLUDING COST of incoming and outgoing MCCB’s) etc. suitable for operation of 240/415 volts A.C. Supply with both side cable allay, inter connection and fixing the same in existing MS pedestal/ wall complete with all labour and material required for the same up to the entire satisfaction of Engineer-in charge of work. Load Bank 4 way 250 A |
| 37 | Load Bank 8 way 400 A |
| 38 | SAFETY ITEMS Supply and erection of Medium Voltage caution notice plate of size 200*150 mm in three languages. |
| 39 | Supply and erection of High Tension Voltage caution notice plate of size 250*200 mm in three languages. |
| 40 | Supply and election of Goodridge Almirante type M.S. pedestal made of 50 mm *50 mm * 6 mm angle Iron frame with 3.00 mm thick M.S. sheet covering including shutters with suitable hinges and looking arrangement with the Godrich type handle including round bars. The to covering should have a downward overhang of 75 mm on all sides of pedestal, having two sets of water proof ventilation holes of suitable size on the sides, at top and bottom, Each set containing four No’s. holes to discharge the heat produced by suitable size to make it water proof . The pedestal duly painted both inside and outside with two coats of approved paint and primary coat and its legs are embedded upto the entire depth in 1:2:4 cement concrete block, projected 75 mm all around the pedestal and 200 mm above the ground level including the cost of all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in charge of the work. M.S. pedestal of size 600 mm wide, 750 mm high, 300 mm deep and bottom totally open , duly embedded in cement concrete block of size 900 mm*450 mm*200 mm above ground level , having a base of size 900 mm* 600 mm* 250 mm below ground level. |
| 41 | EARTHING AND LIGHTENING ARRESTOR Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required. |
| 42 | Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode. |
| 43 | Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required. |
| 44 | Supply and erection of 20mm x 3 mm thick GI, tape fixed with suitable G.I. stapples of same size. |
| 45 | Supply and erection of 25mm dia 1.5 P.mtr. long lightening GI. tube rod tapered into a point at the top with 16cm x 16cm x 3mm thick G.I. base plate and necessary nuts and bolts with washers. |
| 46 | Supply and erection ofsuitable compression type brass cable glands for underground Cable :- 10 sqmm to 16 sqmm Cable 2 to 4 Core |
| 47 | 25 sqmm to 50 sqmm Cable 2 to 4 Core |
| 48 | 70 sqmm to 95 sqmm Cable 3 to 3½ Core |
| 49 | 120 sqmm to 185 sqmm Cable 3 to 3½ Core |
| 50 | 240 sqmm to Cable 3 to 3½ Core |
| 51 | Supply and erection of aluminium lugs heavy duty including crimping etc. upto the entire satisfaction of the Engineer-in-charge of the work. 16 sqmm |
| 52 | 35 sqmm |
| 53 | 95 sqmm |
| 54 | 120 sqmm |
| 55 | 240 sqmm |
| 56 | STREET LIGHT Supply and erection of Single Phase weather proof M.S. box of size 20 cm x 15 cm x 10 cm with hinged cover made of 2 mm thick MS sheet, locking arrangements, housed in wall/fixed on pole , including the cost of 1 no 4 way 16 A bakellite connector, 1 no. 6 amp SP MCB and 1 Nos. 16 amp. neutral links fixed on bakellite sheet in the M.S. box including painting and necessary connections. |
| 57 | B.S.E.N. 10025 High Masts Supply, installation, testing and commissioning of 16 mtr. long High Mast manufactured from B.S.E.N. 10025 or equivalent grade material in,2 (two) section hot dip , galvanized inside and outside in single dip, suitable for wind velocity as per IS 875 Part-3suitable for 9/12 no’s. luminarie loading fully motorized (power tool) with starter & cable complete along with standard accessories supplied by the manufacturer with 3 no’s steel wire rope double drum system and twin dome aviation light with LED without foundation but including cost of set of foundation nut and bolts, installation at site complete I all respect upto entire satisfaction of Engineer-in Charge.Thickness of Top and Bottom Section = 3 mm & 4 mm (minimum). Top Dia = 150 mm and Bottom Dia = 410 mm. Thickness of Galvanization - Top = 65 micron (minimum) and Bottom = 85 micron (minimum) |
| 58 | MISCELLANEOUS ITEMS S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Mtr below ground level includingdiging and refilling of earth including cost of suitable size socket/cuppler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work DWC/HDPE pipe 50/40 mm outer dia/ inner dia |
| 59 | DWC/HDPE pipe 120/105 mm outer dia/ inner dia |
| 60 | RCC FOUNDATIONS FOR HIGH MAST OCTAGONAL POLES Providing RCC foundation of M25 grade (1 Cement:1 Stone aggregate: 2 Coarse sand) i/c excavation, steel reinforcement (Fe 500) @ 75 kg/cum of concrete contents, concrete cover 50mm, anchor bolts etc. over a bed of PCC 1:5:10 of required dimensions for high mast octagonal poles of various heights as per following specifications complete in all respects and as per directions of Engineer-in-charge 16m high mast pole |
| 61 | Providing and erection/ laying of PVC/ XLPE insulated underground aluminium conductor cable 0.75 meter below ground level covered without sand and bricks including excavation and refilling of trenches 16 Sq mm 4 core (Arm.) |
| 62 | 35 Sq mm 3.5 core (Arm.) |
| 63 | 95 Sq mm 3.5 core (Arm.) |
| 64 | 240 Sq mm 3.5 core (Arm.) |
| 65 | Providing & erection/ laying of PVC/ XLPE insulated underground aluminium conductor underground cable loose in existing pipe or trenches complete in all respect with necessary connection upto the entire satisfaction of engineer in charge of the work. 16 Sq mm 4 core (Arm.) |
| 66 | 35 Sq mm 3.5 core (Arm.) |
| 67 | 240 Sq mm 3.5 core (Arm.) |
| 68 | Providing & erection/ laying ofPVC/ XLPE insulated underground aluminium conductor underground cable on surface/ existing cable tray complete in all respect with necessary connection upto the entire satisfaction of engineer in charge of the work 16 Sq mm 4 core (Arm.) |
| 69 | 120 Sq mm 3.5 core (Arm.) |
| 70 | Charges of boaring upto 2.5 mtr. below the gound level treanchless horizentalby HDD machine (for laying the cable & pipe) including all labour and material rrequired to complete the job in al respect with cost of laying of 50 mm dia plane HDPE pipe. |
| 71 | Erection of ceiling fan complete with necessary earthing of fan and regulator including carriage from local railway station /goods transport /PWD store to the site of work. |
| 72 | Supply and erection of 200 watt LED floodlight made up of pressure die cast aluminum housing with toughened glass and high power LEDs and secondary lenses with IP66 protection. System efficacy ≥ 110 LPW 10KV SPD included including erection of same on pole/ parapet with necessary nuts & bolts and making necessary connection of same complete in all respect. |
| 73 | Supply and erection of 150 watt LED floodlight made up of pressure die cast aluminum housing with toughened glass and high power LEDs and secondary lenses with IP66 protection. System efficacy ≥ 110 LPW 10KV SPD included including erection of same on pole/ parapet with necessary nuts & bolts and making necessary connection of same complete in all respect. |
| 74 | Supply and erection of PVC round sheathed multicore annealed bare copper conductor cable 1100 volts grade in pipe of suitable size excluding cost and erection of pipe complete in all respect upto the entire satisfaction of Engineer in charge of the work 4 sq.mm 3 core copper wire |
| 75 | Supply and erection of Double door sheet, steel Vertical distribution boards suitable for FP MCCBs. MCCB upto125 amp as incomer (but without cost of MCCBs) complete with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of the work. (loadline) 4 way load line |
| 76 | 12 way load line |
| 77 | Supply and erection of 32 amp. 3 pole/ 230 volt - digital time switch including cost of contactor, MCBfor controlling the street light with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In - charge of work. |
| 78 | Designing, fabricating, transporting, unloading, storing, fixing in position, testing and commissioning the following sheet steel cubicle type panels fabricated from 1.6mm thick CRCA sheet, dead-front construction, dust and vermin proof, indoor type TPN Panels with hinged lockable doors fabricated from 2mm thick CRCA sheet, suitable for 415V, 3 phase 4 wire 50Hz AC supply with separate cable alley and lockable bus-bar chamber including supplying and fixing following switchgears and accessories, inter-connections, bonding to earth, powder coated painting as per following specifications :- Incomer 800 Amps 433V 4P 50Hz 50KA Fixed Manual Type Air Circuit Breaker (ACB) with Microprocessor based release for Overload , Short-circuit and Earth Fault protection (Make: ABB /Siemens/ Schneider/ L&T)= 1 no. other specifications as per DNIT in PDF. |
| 79 | Deducation of old panel scrab without MCCB |
| 80 | Deducation of old wiring (L.S.) |