| 1 | Comprehensive annual maintenace of runway lighting system in complete including the electrical system runway lighting networks ,equipments as per CA specification/PS for Egineer/technician visit for major complaints/breakdowns rectification with equipments including monthly checking of complete system.Note:1. Contractors having experience in maintenance of \"Air field Lighting system\" are eligible to participate in bidding.Otherwise the contractor shall get the work done by authorized dealer/firms having experience in airfield lighting works.2. Monthly checklist of essential items of air field lighting for proper function of the system to be followed and user satisfaction to be obtained and kept on records. |
| 2 | Manitenance of runway lighting system including CCR for taxiway light & runway edge light , Approach light , CCR control panel ,Aviation obstruction light,ground traffic control light,AVASI light, Tower red lamp dagger,hooter,aerodrome beacon lamp & complete circuit to runway lighting system by providing 1XElectrician & 1 X Helper along with two wheeler(Bike) model -2020 onward for any shift of 8 hours as directed by Engineer-in-charge as per requirment including FOL charges & maintenace charge of vehicle complete all as directed by Engr-in-charge.Note : (i) Contractor need to submit all connecting document of two wheeler i.e RC ,DL of person driving vehicle(electrician/helper).(ii)The contactor willprovide uniform andall the safety equipments to electrician.(iii) The contractor will provide basic tools kits, tester, LT megger/HT megger, clamp meter,test lamp,ladders including upto and also above 9 mts,tools for maintenace of runway lighting system as required. (iv) If the contactor fail to provide the electricain/helper/two wheeler on any shift the penalty of 2 times of quoated ratewill be imposed on contractor. (v) If the staff employed for maintenance of runway lighting system are found not efficient /suitable to the requirements as assigned by Engr-in-charge. The contractor neeed to provide suitable replacement immediately and penalty of 2 times the quoted rate will deducted per shift and decision ofof Engineer -in-Charge/GE will be final. |
| 3 | Supply & fix in replacementmandatory spares for AFLS including necessary connected items in complete and testing after fixing of the spares |
| 4 | (a)CCR(15 KW) :-Contactors 100 Amps 3 pole |
| 5 | Bussmann fuse unit40 Amps |
| 6 | (b)FOR RUNWAY EDGE LIGHT :-Base plate for runway edge light Suitable for 200 W 6.6 Amp runway edge light |
| 7 | Stem pipe Suitable for 200 W 6.6 Amp runway edge light |
| 8 | Glass Suitable for 200 W 6.6 Amp runway edge light |
| 9 | Glass clamp Suitable for 200 W 6.6 Amp runway edge light |
| 10 | Reflectors Suitable for 200 W 6.6 Amp runway edge light |
| 11 | Essna connector Suitable for 200 W 6.6 Amp runway edge light |
| 12 | Rubber Gasket Suitable for 200 W 6.6 Amp runway edge light |
| 13 | Base plate bolts Suitable for 200 W 6.6 Amp runway edge light |
| 14 | Glass clamp bolts Suitable for 200 W 6.6 Amp runway edge light |
| 15 | CI box Suitable for 200 W 6.6 Amp runway edge lightNote: make of spares to be ofAMA , VARDHMAN or MANUFACTURERES WHO MEET ICAO REQUIREMENT & Approved by GE |
| 16 | (c)FOR TAXIWAY LIGHTTaxi way lamp 45 W 6.6 Amp |
| 17 | Base plate suitable for taxiway elevated light of 45 W 6.6 Amp |
| 18 | Stem pipe suitable for taxiway elevated light of 45 W 6.6 Amp |
| 19 | Glass clamp suitable for taxiway elevated light of 45 W 6.6 Amp |
| 20 | Reflectors suitable for taxiway elevated light of 45 W 6.6 Amp |
| 21 | Lamp holder suitable for taxiway elevated light of 45 W 6.6 Amp |
| 22 | Essna connector suitable for taxiway elevated light of 45 W 6.6 Amp |
| 23 | Rubber Gasket suitable for taxiway elevated light of 45 W 6.6 Amp |
| 24 | Base plate bolts suitable for taxiway elevated light of 45 W 6.6 Amp |
| 25 | Glass clamp bolts suitable for taxiway elevated light of 45 W 6.6 Amp |
| 26 | CI Box suitable for taxiway elevated light of 45 W 6.6 AmpNote: make of spares to be ofAMA , VARDHMAN or MANUFACTURERES WHO MEET ICAO REQUIREMENT & Approved by GE |
| 27 | (d)APPROACH LIGHTApproach lamp suitable for 200 W ,6.6 AmpApproach light fitting |
| 28 | Glass with connected accessories suitable for 200 W ,6.6 AmpApproach light fitting |
| 29 | Isolation transformer of magnetic C core type having primary & secondary winding of super enameled copper wire ,polyster insulation,Neoprene rubber coating,Single core 5 KV EPR /PCP Primary cable ,twin core 1.1 KV EPR /PCP Secondary cable, moulded two pin receptable ,moulded single pin plug,moulded single pin receptable suitable for 200 W ,6.6 AmpApproach light fitting |
| 30 | Rubber Gasket suitable for 200 W ,6.6 AmpApproach light fitting |
| 31 | Base plate bolts suitable for 200 W ,6.6 AmpApproach light fitting |
| 32 | CI Box suitable for 200 W ,6.6 AmpApproach light fittingNote: make of spares to be ofAMA , VARDHMAN or MANUFACTURERES WHO MEET ICAO REQUIREMENT & Approved by GE |
| 33 | (e)GROUND TRAFFIC CONTROL LIGHTING GTC Traffic signal light(RED) |
| 34 | GTC lamp screw type |
| 35 | Hooter heavy duty 5 KM range |
| 36 | Painting of lamp post |
| 37 | Junction boxNote: make of spares to be of Make : REVERSE ELECTRIC MFG CO. or MANUFACTURERES WHO MEET ICAO REQUIREMENT & Approved by GE |
| 38 | (f)TOWER RED LAMP DAGGER TRLD Lamp Fitting |
| 39 | Junction Box |
| 40 | (g)AVIATION OBSTRUCTION LIGHT Metal Flexible pipe |
| 41 | Junction box 0f size 140X140X95 IP 65with terminal end connectors |
| 42 | 19mm PVC glands |
| 43 | Lamp fitting LEDNote: make of spares to be of Make : AMA/WESTING HOUSE or MANUFACTURERES WHO MEET ICAO REQUIREMENT & Approved by GE |
| 44 | (h)AVASI LIGHTFoundation of AVASI light as per existing size |
| 45 | AVASI light body |
| 46 | Isolation transformer |
| 47 | LampNote: make of spares to be of Make : AMA /VARDHMAN or MANUFACTURERES WHO MEET ICAO REQUIREMENT & Approved by GE |
| 48 | (j)AERODROME ROATATING BEACONEnd terminal connector |
| 49 | Aerodrome rotating beacon lamp 6.6 Amp ,200 watt |
| 50 | Aerodrome rotating beacon motor |
| 51 | Beacon lamp equipmentbodyNote: make of spares to be of Make : AMA /VARDHMAN or MANUFACTURERES WHO MEET ICAO REQUIREMENT & Approved by GE |
| 52 | (k)CCR 4 KWOutput transformer 4 KVA |
| 53 | Variable transformer |
| 54 | Tuned circuit |
| 55 | 4P, 40 Amp contactor |
| 56 | Overcurrent relay |
| 57 | Auxiliary relay |
| 58 | 10 MFD 575 V Capacitor |
| 59 | 25/30 MFD 575 V Capacitor |
| 60 | End termination connectors/lugsNote : Make of spare to be of make : SIB heavy duty electric or manufacturers who meet ICAO requirement as approved by GE. |
| 61 | S & F in replacement anticipatory spares for AFLS including necessary connected items in complete and testing after fixing of the spares |
| 62 | Low intensity LED Taxiway Edge Omni-Directional Elevated light fittings 45 W ,6.6 A with lamps and blue lens complete having with an average lamp life of approximately 80,000 hours due to utilization of long life LEDs.Very low energy consumption – below 10w.,Fully compatible with existing AFL Taxiway Circuit. Proven Light Fitting with frangible coupling.Omni-directional Light Output, LED with Rated Life of 50,000 hours,Blue dome features smooth top surface which remains dirt-free and enables easier cleaning. Lenses are also available in red, green and yellow.Sturdy and Non Corrosive Construction: all as specified and as directed.ICAO :In compliance with Annex 14, Volume 1, Aerodrome Design and Operations for use as a Taxiway and Apron Edge LightFAA : In full compliance with FAA L-861T Specifications AC No. 150/ 5345-46IS : In full compliance with IS Specifications IS 7785 Part – I to V Maintenance free (except for cleaning of lens) |
| 63 | High intensity unidirectionalApproach, Threshold, Runway End High Intensity Elevated Light fittings 200 W ,6.6 A with lamps having State-of-the-Art Optical Design:Light Weight Aluminium Construction:Frangible Body on Hinged Arrangement:Sturdy and Non Corrosive Construction:Lens Clamping Band with Neoprene Rubber Gasket, Front Glass (Clear or Coloured),Anodized Aluminium Reflector,Die- cast Aluminium Alloy Body ,Pre-focus Halogen Lamp,Lamp Holding Aluminium Body,Moulded Secondary Lead complete all as specified and as directed. ICAO :In full compliance with Fig 2.1 of Annexure 14, July 1990 edition for use in Precision Approach Runway Categories I, II, and III. FAA :In Full compliance with FAA E-982 Specifications. |
| 64 | High intensity Bi-directional runwayedge light fittings 200 W ,6.6 A with white lamps lighthaving High intensity, Elevated bi-directional (with omni-directional component), elevated runway edge light for use in all weather operation installations up to ICAO category III systems. Medium intensity, bi/uni-directional elevated threshold/end light. having Aluminium alloy body- light weight, corrosion-resistant & powder coat.Lamp life is greater than1000 hours at 6.6A. 5-step constant current operation.Frangible coupling to ensure flight safety complete all as specified and as directed. |
| 65 | Certain repairs to remote control system/Panel including repair/replacement to existindg circuits contacts /relays /rotary switches/indicators/Cables complete include necessary testing all as specified and as directed. Make – Crouse hinds company/Telectro industries Corp. |
| 66 | Excavation in trenches, n.exc 1.5 m wide and n.exc 1.5 m in depth for foundation or taking up / down electrical cables / pipe. and getting out in soft/loose soil concrete all as directed. |
| 67 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed. |
| 68 | Removing excavated spoil to a distancen.exc. 50 m and depositing where directed at a level n.exc 1.5m above the starting pointcomplete all as specified and as directed. |
| 69 | M&L for sand cushion for under ground cable protection and consolidated and compacted with clean dry river sand complete all as specified and as directed. Note- Punned thickness will be measured at the time of measurement and payment. |
| 70 | S&F un-reinforced precast concrete cable cover HV, Type 1, flat, size 300mmx l80mm x 40mm trenches over sand cushioning for cable protection complete all as specified and as directed. |
| 71 | S&F bricks fly ash bricks locally available of size 230mm x 115mm x 75mm best quality laid in trenches over sand cushioning for cable protection complete all as specified and as directed. |
| 72 | Supply, laying, connecting and testing XLPE round sheathed , stranded copper conductor cable, 1100 volts grade, cross-sectional area 2 core 6 sq mm , including taking down old UNSV cable complete all as directed. |
| 73 | Supply, laying, connecting and testing XLPE insulated 3 core 2.5 Sq mm stranded copper conductor cable including taking down old unserviceable cable complete all specified and directed.Make: Plaza/ Gloster/Polycab/Havells. |
| 74 | Supply, laying, connecting and testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 2 core 6 sq mm, including taking down old UNSV cable complete all as directed. |
| 75 | Supply, laying, connecting and testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 2 core 16 sq mm, including taking down old UNSV cable complete all as directed. |
| 76 | Material and labour for 5 KV 16 Sqmm single core copper cable including taking down old UNSV cable complete all as directed.MAKE : KEI/ALOKE/ RALLISION/ BHANSALI/ GLOSTER/ DYNAMIC & MANUFACTURER HAVING11KV GRADE BIS/ FAA CERTIFIED CABLES |
| 77 | Material & Labour for earthing with using copper plate 60×60cm ×3.15mm thick electrode buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level,connected to the copper earth lead by means of bolts, nuts check nuts and washers of galvanised iron or steel using20×3mm copper strip as earthing lead shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation andearth work insoft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregatepit, funnel, 40mm dia GI medium grade watering pipe and earth lead protection pipe and pre-cast earth pit cover made of RCC (1:1.5:3) type A1 duly reinforced with 8mm dia TMT bar @150 c/c both ways, one lifting handle made out of 10mm dia TMT bar 250mm long embedded in cover slab and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternate layer of 15cm thick complete all as specified and directed. |
| 78 | Supply & Fix Earth continuity conductor 20x3mm copper strip complete all as specified and directed. |
| 79 | Supply & filling Tranformer oil/CCR oil complete all as specified and as directed. |
| 80 | M&L for Filteration of CCR oil including necessary dismantling/opening lifting etc.complete all as specified and as directed |
| 81 | M&L for cleaning grass cutting ,small vegetation/plants clearing at areaaroundAF lighting system itemcomplete all as specified and as directed |
| 82 | Supply & Fix in replacement CCR 15 KW,6.6 Amp resonant type/thyristor type having ammeter .5 % Accuracy ,regulation + 1 % over 0 to 100 % load and +10 % to -5% line voltage with no tap changes,on off switching under load,lightning and transient protection : input and output lines ,Efficiency -90 % minimum ,High power factor ,remote reset capability ,open circuit protection,over current protection ,having 5 step brightness controloutput current step wise 6.6/5.2/4.1/3.4/2.8 Amp havingpercentage light output 100/80/60/50/40 respectively compatible with existing runway lighting system after commissioning test report will be submitted Complete all as specified and as directed. Make : HONEYWELL/ HIND RECTIFIER/ AMA/ NASU/ THORN/ IDMAN-OY/ CEGELEC/ ADM/ YOUYANG |