| 1 | M & L for submainwiringwith 2 x 2.5 sqmm (Nominal area) single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cabledrawn through in and including FRLS PVC Conduit mediumgrade with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 2.5 sqmm as earth lead and connected to earth dollyincl dismentling taking down old unserviceable wiring and making good to disturbed surfaces all as specified and directed. Note :- (a) Two run of cable with one run of earth wire and one run of casing capping/conduit will be measured as one length. (b)working height upto roof level of wksp buildings for item No- 1 to 4 only. |
| 2 | All as per item No. 1.00 above,but cable of size 2 x 6.0 sqmm and earth wire 1 x 6 sqmm |
| 3 | All as per item No. 1.00 above,but cable of size 4 x 6.0 sqmm and earth wire 2x 6 sqmm |
| 4 | All as per item No. 1.00 above,but cable of size 4 x 10.0 sqmm and earth wire 2 x 10 sqmm |
| 5 | S&FFRP box of suitable sizewith connector incl dismantling taking down unsv one all as specified and directed. |
| 6 | M &L for \"L\" shape of angle iron 40 mm size duly welded on workshop truss for fixing of highbay light along with \"S\" type hook complete with fixing arrangement incl dismantling taking down unsv oneall as specified and directed. |
| 7 | S&FMCB, Single Pole, 6 to 32 amps, 240 Volts, 10 KA breaking cap, ‘’C” curve incl dismantling taking down unsv oneall as specified and directed. Make :- Legrand/L&T/ABB/ Schneider/ BCH |
| 8 | S&FMCB, Double Pole, 6 to 32 amps, 240 Volts, 10 KA breaking cap, ‘’C” curve incl dismantling taking down unsv oneall as specified and directed. Make :- Legrand/L&T/ABB/ Schneider/ BCH |
| 9 | S&FMCB, three Pole, 40 to 63 amps, 415 Voltsincl dismantling taking down unsv oneall as specified and directed. Make :- Legrand/L&T/ABB/ Schneider/ BCH |
| 10 | S&FMCB, Four Pole, 40 to 63 amps, 415 Voltsincl dismantling taking down unsv oneall as specified and directed. Make :- Legrand/L&T/ABB/ Schneider/ BCH |
| 11 | S&FMCB distribution board, IP 43 protection, Double door, metal enclosure, TPN, 415 Volts, 4 way incl dismantling taking down unsv oneall as specified and directed. Make :- Legrand/L&T/ABB/ Schneider/ BCH |
| 12 | S&FVertical MCB distribution board suitable for MCCB incomer, IP 43 protection, Double door, metal enclosure, TPN, 415 Volts, 8 way incl dismantling taking down unsv oneall as specified and directed.Make :-Legrand/L&T/ABB/ Schneider/ BCH |
| 13 | S&F MCCB, 25KA, 4 pole, with thermal magnetic trip unit, rated current 125amps complete with spider link incl dismantling taking down unsv oneall as specified and directed (Suitable for MCCB incomer DB). Make :- Legrand/L&T/ABB/ Schneider/ BCH |
| 14 | S&FMetal plug and socket board with MCB SP 20 amp, 16 KA incl dismentling taking down unsv oneall as specified and directed. Make :- Legrand/L&T/ABB/ Schneider. |
| 15 | Supply & Fix Square shaped recess mounted LED slim panel down lighter, 36 watt (2`x2`), to POP/grid celing complete with all fixing accessories and including connecting up to ceiling rose with 0.5 sqmm two core copper flexible conductor cableincl dismantling taking down unsv FTL/CFL fiitingsany type all as specified and directed. Make :- Philips/ Havells/Syska/ Crompton |
| 16 | Supply & Fix LED high bay light 150 watt at roof truss level of wksp buildings and other places incl dismantling taking down unsv one any typeall as specified and directed. Make :-Philips/ Havells/Syska/ Crompton |
| 17 | Fixing only LED high bay light 200 watt at roo truss level of wksp buildings and other places incl dismantling taking down unsv one any type all as specified and directed.Note :- LED fitting will be issued under Sch \"B\" free for fixing only. |
| 18 | Supply & Fix LED recessed (4\"x1\") polycarbonate housing down lighter with superior light output and integral driver , 40 watt complete with fixing spring clip 4 nos, fixed flush togypsum/grid ceilingincl dismantling taking down unsv one any type all as specified and directed.Make :- Philips/ Havells/Syska/ Crompton |
| 19 | Supply & fix LED building security light 90 watt, 230V complete with all accessories and including connecting up to ceiling rose with 0.5 sqmm three core copper flexible conductor cable, One GI medium grade 20mm dia bracket of total length 50 cm and fixed to wall with 2 Nos MS Clamp and fastener incl dismantling taking down unsv fitting any type all as specified and directed.Make :- Philips/ Havells/Syska/ Crompton |
| 20 | M & L for Earthing complete with GI Pipe electrode, 40 mm bore, Medium grade, 2.5 mtr longburied directly and vertically in ground with top edge at ground level after making manual bore hole of size not less than 300 mm dia and 2.65 Mtr long near the specified bldg, connected with galvanised steel strip earthing lead of size 32mmx 6mm all as shown in Plate No-2, connected to the earthing test point, concrete pit in PCC 1:3:6 type C-2with RCC precast pit cover slab 80mm thick with handle for lifting made out of 8mm dia MS rod, wiremesh, charcoal and salt in alternate 150mm thick layers around CI earth pipe, including necessary returning filling in & removal all as specified or indicated in SSR Part-I, including testing to achieve earth resistance value as per IS specification on completion after dismantling taking out unserviceable one all as specified and directed. |
| 21 | Taking down and refixing of loose conduit/casing capping/ cable /wiring of size upto 25sqmm all as specified and as directed |
| 22 | Dismantling and refixing Aluminium strip 25 x 3.15 mm laid in trench/ roof/ wall for earthing connection for various machines/ other incl dismantling taking down unsv strip all as specified and directed. |