| 1 | Labour for taking out all incoming / outgoing electric connection from LT panel / starter / motor / voltage stabilizer carefully for repair to cable / rectification of the fault and reconnecting in position after repair and preparation the cable and fixing complete with nut, bolts, washers for cable size 25 to 120 Sqmm including preparation of 3.5 / 4 core cable, 4 wire each alongwith connected items like thimble, insulation tape and will be considerable in this job complete all as specified and as directed. |
| 2 | Material and labour for maintainence of LT panel / feeder pillar box indoor / outdoor type by cutting corroded mild steel lid from panel, welding the same with 3 mm thick / mild steel sheet in any desired shape including removing the carbonised / melted sparked thimbles cleaning the carbonised bus bar making cable end clean complete all as specified and as directed. |
| 3 | Material and labour in repairs powder coated CRCA sheet 3 mm thick complete all as specified and as directed. |
| 4 | Material and labour in repairs of old burnt out aluminium bus bar and connected link bar with proper colour coding with insulation tape of current rating 400/250 Amps including repairs of old rusted nut and bolts, washers complete all as specified and as directed by Engineer-in-Charge. |
| 5 | Supply and fixing in repairs unserviceable indicators LED set of three pieces as per existing size and sample complete all as specified and as directed by Engineer-in-Charge. |
| 6 | Supply and fixing in repairs ampere meter analog type 0-400 Amp CT with suitable set of size 96 Sqmm square type flush panel mounted complete all as specified and as directed by Engineer-in-Charge. |
| 7 | Supply and fixing Volt meter analog type 0-500 Volt 96 Sqmm square type flush panel mounted complete all as specified and as directed by Engineer-in-Charge. |
| 8 | Material and labour in repairs of MCCB 3 pole, current rating 63 Amp, thermal setting adjustable type 70%-100% rupturing capacity 16 KA at 415 V, 50 Hz complete all as specified and as directed. |
| 9 | Material and labour in repairs of MCCB 3 pole, current rating 100 Amp, thermal setting adjustable type 70%-100% rupturing capacity 16 KA at 415 V, 50 Hz complete all as specified and as directed. |
| 10 | Material and labour in repairs of MCCB 3 pole, current rating 125 Amp, thermal setting adjustable 70%-100% rupturing capacity 16 KA at 415 V, 50 Hz complete all as specified and as directed. |
| 11 | Material and labour in repairs of MCCB 4 pole, current rating 160 Amp, thermal setting adjustable 70%-100% rupturing capacity 36 KA at 415 V, 50 Hz complete all as specified and as directed. |
| 12 | Material and labour in repairs of MCCB 4 pole, current rating 200 Amp, thermal setting adjustable 70%-100% rupturing capacity 36 KA at 415 V, 50 Hz complete all as specified and as directed. |
| 13 | Material and labour in repairs of MCCB 4 pole, current rating 250 Amp, thermal setting adjustable 70%-100% rupturing capacity 36 KA at 415 V, 50 Hz complete all as specified and as directed. |
| 14 | Supply and fixing in repairs of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 100 Amp, 415 volts 3 phase, four pole complete all as specified and as directed. |
| 15 | Supply and fixing in repairs of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 200 Amp, 415 volts 3 phase, four pole complete all as specified and as directed. |
| 16 | Taking out old / unserviceable underground LT cables and connections including pipes, bricks or precast concrete cable cover etc of any type from trenches / walls / poles of any cross sectional area and removing from site complete all as specified and as directed. |
| 17 | Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sqmm, 4 core, complete all as specified and as directed by Engineer-in-Charge.Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation. |
| 18 | Description all as per Ser item No 17.00 here-in-before but cross sectional area 25 Sqmm 4 core complete all as specified and as directed. |
| 19 | Description all as per Ser item No. 17.00 here-in-before but cross sectional area 50 Sqmm 4 core complete all as specified and as directed. |
| 20 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deepin any type of soil, getting out and levelling of bottom surface to required level for poles / stay assembly / cable complete all as specified and as directed. |
| 21 | Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25m thick complete all as specified and as directed. |
| 22 | Removing excavated material from site to a distance not exceeding 50 metre away and depositing where directed not exceeding 1.5 metre from the starting point complete all as specified and as directed. |
| 23 | Material and labour in repairs of galvanised iron pipe light grade 50 mm bore for cable protection as a guard pipe complete all as specified and as directed. |
| 24 | Supply and laying in replacement of well burnt old size sub class \"B\" bricks laid flat with width equal to length of brick perpendicular to the direction of cable, adjacent / abutting each other in trenches over the cable for protection complete all as specified and as directed by Engineer-in-Charge. |
| 25 | Supplying and laying in trenches clear sand for cushioning underground cable 8 cm below and 15 cm above complete in level all as specified and as directed. |
| 26 | Maintainence of Automatic power factor controlling panel at diffrent location of Miran Sahib by cleaning, rewiring, repairs of components like capacitors, contactors, MCB / MCCB, APFC Controller / Relays, Indicating lamps, Instruments Push Buttons, switches, wires cable termination etc. and demo of working panel with proper relay setting and loadwise capacitor switching at location complete all as specified and as directed. |
| 27 | Supply and fixing in repairs APFC relay set for APFC panel of 120 / 200 KVAR capacity including taking down old unservicable one complete all as specified and as directed by the Engineer-in-Charge. |
| 28 | Supply and fixing in repairs push buttons, switches as per sample complete all as specified and as directed. |
| 29 | Supply and fixing in repairs indicating lamps Red R, Y, B as per sample complete all as specified and as directed. |
| 30 | Supply and fixing in repairs current transformer with CT ratio 200 / 5, as per sample complete all as specified and as directed. |
| 31 | Supply and fixing in repairs current transformer with CT ratio 300 / 5, as per sample complete all as specified and as directed. |
| 32 | Supply and fixing in repairs 3 phase contactor type (MNX 18 to 50) as per sample including taking down old unserviceable one complete all as specified and as directed by the Engineer-in-Charge. |
| 33 | Supply and fixing in repairs of MCCB 400 Amp 4 pole, 415 V, adjustable type, breaking capacity 36 KA including taking out the old unserviceable one complete all as specified and as directed. |
| 34 | Supply and fixing in repairs of MCCB 350 Amp 4 pole, 415 V, adjustable type, breaking capacity 36 KA including taking out the old unserviceable one complete all as specified and as directed. |
| 35 | Supply and fixing isolator TPN 63 Amps, 415 volts, breaking capacity 10 KA including taking out the old unserviceable one complete all as specified and as directed. |
| 36 | Supply and fixing in repairs capacitor heavy duty cylindrical type 1 KVAR complete all as specified and as directed. |
| 37 | Supply and fixing in repairs capacitor heavy duty cylindrical type 2 KVAR complete all as specified and as directed. |
| 38 | Supply and fixing in repairs capacitor heavy duty cylindrical type 5 KVAR complete all as specified and as directed. |
| 39 | Supply and fixing in repairs capacitor heavy duty cylindrical type 7.5 KVAR complete all as specified and as directed. |
| 40 | Supply and fixing in repairs capacitor heavy duty cylindrical type 10.0 KVAR complete all as specified and as directed. |
| 41 | Supply and fixing in repairs capacitor heavy duty cylindrical type 12.5 KVAR complete all as specified and as directed. |
| 42 | Supply and fixing in repairs capacitor heavy duty cylindrical type 25.0 KVAR complete all as specified and as directed. |
| 43 | Supply and fixing in repairs capacitor heavy duty cylindrical type 40.0 KVAR complete all as specified and as directed. |
| 44 | Supply and fixing in repairs unserviceable aluminium lugs / thimble of size 16 Sqmm complete all as specified and as directed. |
| 45 | Supply and fixing in repairs unserviceable aluminium lugs / thimble of size 25 Sqmm complete all as specified and as directed. |
| 46 | Supply and fixing in repairs unserviceable aluminium lugs / thimble of size 50 Sqmm complete all as specified and as directed. |
| 47 | Supply and fixing in repairs unserviceable aluminium lugs / thimble of size 70 Sqmm complete all as specified and as directed. |
| 48 | Material and labour in repairs for LT panel box size (1.0 X 1.0 X 0.6 mm) having thickness of 3.15mm and inner shell made out of 2mm thick mild steel sheet and mild steel angle section 50 x 50 x 6 mm mounted on PCC (1:2:4) type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front openable double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable / openable by Keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust / vermin proof and general construction confirming to IS:8623/93 complete all as specified and as directed.(i) Incoming: - (a) MCCB, 250 Amps, 4 Pole, 415 V, 35 KA - 01 Each, Al busbar of capacity 315 Amps - Set of three.(ii) Outgoing: - (a) MCCB, 160 Amps, 4 Pole, 415 V, 10 KA - 01 Each(b) MCCB, 100 Amps, 4 Pole, 10 KA - 02 No.(iii) Digital Ammeter 0-400 A of size 96 Sqmm with selector switch - 01 No.(iv) Digital Voltmeter 0-500 V of size 96 Sqmm with selector switch - 01 No.(v) Indicator Lamp RYB 22.5mm dia LED type 240 volts AC with incoming including back up protection by 2 Amp MCB RYB with holder - 01 set of three.(vi) CT Coils of suitable ratio - 01 Set. |
| 49 | Material and labour in repairs of APFC panel 50 KVAR, 3 steps (20 KVAR x 2 and 10 KVAR x 01), CPRI certified, 440 V, auto charging outdoor type auto charging switching, compartimentalized modular, 3.15 mm CRCA sheet of appropriate size front operatable double doors, powder coated grey shade on body doors and orange shade on mounting/gland plates - incoming 3 phase HR sleeved colour coded aluminium main busbar of 200 amps 03 Nos busbar running across the whole length of the LT panel with 02 Nos studs at both the side ends, lifting arrangement/hooks at the top wiring with appropriate size copper industrial cables, black painted base frame 40x40x6 mm mild steel angle frame fitted with following accessories: -(a) Type of capacitor = Super heavy duty square type of 415 volt.(b) MCCB, 4 Pole, 16 KA adjustable type with O/L and S/C protection of 100 Amp = 01 No\"s as incoming.(Make : Schneider/L&T/Siemens/ABB/Havells)(c) Phase indicating lamp = 01 set.(d) Digital VAF meter = 01 set.(e) APFC relay = 01 Set.(f) CTs 300/5 Amp, CI 1.0 10 VA=03 Nos.(g) Sensing of suitable capacity with control cable shall be provided by the contractor. |
| 50 | Supply and fixing in repairs of submersible cable 16 Sqmm 3 core flat copper conductor heavy duty 1100 Volts grade confirming to ISI complete all as specified and as directed by Engineer-in-Charge.Note: - Old cables shall be deposited in store yard. |
| 51 | Taking down unserviceable street / security light / flood light fitting of any type from the pole / building after disconnecting electric connection carefully complete all as specified and as directed.Note: - Repairs of spares shall be measured separately. |
| 52 | Supply and fixing in repairs of distribution board with time switches astro type (having longitude and latitude of Indian cities in memory) 250 V single phase of 20 Amp rating with contactor fitted inside steel enclosure complete all as specified and as directed. |
| 53 | Supply and fixing in repair LED street light fitting 35 / 45 Watt 230 V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed. |
| 54 | Supply and fixing in repair of LED flood light fitting of capacity 100 watt including inbuilt surge protection as per requirement LED flood light fittngs along with IP 65/66 protection complete all as specified and as directed. |
| 55 | Material and labour including replacement for Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.00mm thick buried directly in ground to a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.50 metre below ground level, earth plate surrounded by 15 cm thick packed layer of charcoal and common salt alternatively upto 90 cm and connected with and including GI strip of size 32x6 mm by means of bolts, nuts, check nuts and washers of GI 20 mm bore, GI pipe light grade for protection of GI wire from earth plate to testing point for protection, 20mm bore GI pipe for water with wire mesh and funnel forwatering including necessary excavation and earth work, PCC chamber (1:3:6) type C-2 with RCC cover complete all as shown in electrical plate No 3 of MES Schedule Part I of SSR Part I (2009) complete all as specified and including dismantling and taking down old unserviceable all as directed.Notes: - (i) RCC pit cover shall be precast of RCC (1:2:4) type B-1, 80 mm thick reinforcement with 8 mm TOR steel @ 100 centre to centre in lieu of CI cover and the rate includes in the unit rate of item.(ii) Earth electrode shall be protected upto test point using necessary arrangement with suitable size GI pipe up to 7.50 m and the rate includes in the unit rate of item.(iii) Earth pit chamber and RCC cover shall be painted with red paint over a primer coat and the rate includes in the unit rate of item.(iv) The earth chamber shall be constructed 5m away from the edge of the earth pit and the cost of the same is deemed to be included in the rate quoted for this item.(v) Excavation and earth work for drilling hole for electrode in soft / loose soil.(vi) PCC pit in cement concrete (1:2:4) type B-1, precast RCC cover with suitable handle 40 mm thick in PCC (1:2:4) type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg / Sqm.(vii) Funnel with watering pipe of galvanized iron 20 mm nominal bore light grade and lugs etc complete all as specified and as directed.(viii) 40 mm nominal bore medium grade galvanized iron protection pipe for protection of earthing lead complete all as specified and directed.(ix) Requisite quantity of common salt and charcoal.(x) Testing of earthing. |
| 56 | Material and labour for road cutting, PCC hard standing as per site requirement including excavation for laying of galvanized iron pipe and making good the disturbed surfaces all as per existing surface complete all as specified and as directed. |
| 57 | Material and labour in replacement of galvanized iron pipe light grade 80 mm bore for cable protection as a guard pipe complete all as specified and as directed. |
| 58 | Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 Sqmm, 2 core complete all as specified and as directed by Engineer-in-Charge.Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation. |
| 59 | Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sqmm, 2 core complete all as specified and as directed by Engineer-in-Charge.Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation. |
| 60 | Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sqmm, 3.5 core complete all as specified and as directed by Engineer-in-Charge.Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation. |
| 61 | Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 Sqmm, 3.5 core complete all as specified and as directed by Engineer-in-Charge.Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation. |
| 62 | Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm, 3.5 core complete all as specified and as directed by Engineer-in-Charge.Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation. |
| 63 | Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 Sqmm, 4 core complete all as specified and as directed by Engineer-in-Charge.Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation. |
| 64 | Supply and fixing in replacement of unserviceable aluminium lugs / thimble of size 120 Sqmm complete all as specified and as directed. |
| 65 | Supply and fixing in replacement of unserviceable aluminium lugs / thimble of size 35 Sqmm complete all as specified and as directed. |
| 66 | Supply and fixing in replacement LED street light fitting 60 Watt, 230 V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP-65/66 protection complete all as specified and as directed. |
| 67 | Supply and fixing in replacement LED street light fitting 90 Watt, 230 V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP-65/66 protection complete all as specified and as directed. |
| 68 | Supply and fixing in replacement LED street light fitting 120 Watt, 230 V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP-65/66 protection complete all as specified and as directed. |
| 69 | Supply and fixing in replacement LED flood light 120 watt, 230 V AC outdoor type with thermal management in multiple optics and equipped with IP-66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed. |
| 70 | Supply and fixing in replacement LED flood light 210 watt, 230 V AC outdoor type with thermal management in multiple optics and equipped with IP-66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed. |
| 71 | Supply and fixing and fabrication bracket made out of galvanized iron tubing suitable for 45 / 60 / 90 watt LED light grade upto 1.2 metre length, bend to shape suitable for security light fitting with necessary mild steel clamps with one coat of red oxide primer and two coats of aluminium paint including nut, bolt, washers etc and including taking out unserviceable bracket and removing from site of work complete all as specified and as directed. |
| 72 | Supply and fixing in replacement of 1100 Volt Arial bunched cable having three phase conductor of multistranded compacted circular aluminium conductor screen of extruded semiconducting compound extruded XLPE insulated, insulation screen of extruded semiconducting compound over all metallic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS : 7098 Part-II of size 3 x 35 Sqmm + 1 x 25 Sqmm complete with dead end clamp, suspension clamp, Eye Hook, welding and cable jointing kit as per site requirement with the existing LT distribution system complete all as specified and as directed. |
| 73 | Supply and fixing in replacement of 1100 Volt Arial bunched cable having three phase conductor of multistranded compacted circular aluminium conductor screen of extruded semiconducting compound extruded XLPE insulated, insulation screen of extruded semiconducting compound over all metallic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS : 7098 Part-II of size 3 x 50 Sqmm + 1 x 35 Sqmm complete with dead end clamp, suspension clamp, Eye Hook, welding and cable jointing kit as per site requirement with the existing LT distribution system complete all as specified and as directed. |
| 74 | Supply and fixing in replacement of 1100 Volt Arial bunched cable having three phase conductor of multistranded compacted circular aluminium conductor screen of extruded semiconducting compound extruded XLPE insulated, insulation screen of extruded semiconducting compound over all metallic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS : 7098 Part-II of size 3 x 70 Sqmm + 1 x 50 Sqmm complete with dead end clamp, suspension clamp, Eye Hook, welding and cable jointing kit as per site requirement with the existing LT distribution system complete all as specified and as directed. |
| 75 | Supply and fixing in replacement of 1100 Volt Arial bunched cable having three phase conductor of multistranded compacted circular aluminium conductor screen of extruded semiconducting compound extruded XLPE insulated, insulation screen of extruded semiconducting compound over all metallic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS : 7098 Part-II of size 3 x 95 Sqmm + 1 x 70 Sqmm complete with dead end clamp, suspension clamp, Eye Hook, welding and cable jointing kit as per site requirement with the existing LT distribution system complete all as specified and as directed. |
| 76 | Material and labour for LT panel box size (1.0 X 1.0 X 0.6 mm) having thickness of 3.15mm and inner shell made out of 2mm thick mild steel sheet and mild steel angle section 50 x 50 x 6 mm mounted on PCC (1:2:4) type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front openable double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable / openable by keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust / vermin proof and general construction confirming to IS : 8623 / 93 complete all as specified and as directed.(a) Incoming: - (i) MCCB, 630 Amps, 4 Pole, 415 V, 35 KA - 01 Each, Al busbar of capacity 315 Amps - Set of three.(b) Outgoing: - (i) MCCB, 250 Amps, 4 Pole, 415 V, 10 KA - 02 Each.(ii) MCCB, 100 Amps, 4 Pole, 10 KA - 02 No.(c) Digital Ammeter 0-400 A of size 96 Sqmm with selector switch - 01 No.(d) Digital Volt meter 0-500 V of size 96 Sqmm with selector switch - 01 No.(e) Indicator Lamp RYB 22.5mm dia LED type 240 volts AC with incoming including back up protection by 2 Amp MCB RYB with holder - 01 set of three.(f) CT coils of suitable ratio - 01 Set. |
| 77 | Material and labour in replacement of PVC insulated and sheathed cable of size 1.5 Sqmm 3 core copper conductor multistranded 1100 Volt grade 230 volts running through PVC conduit of dia 20 mm with strip clamping complete all as specified and as directed by Engineer-in-Charge. |