| 1 | Comprehensive maintenance of LT panel boards, indoor/outdoor typr after isolating the panel board from electric supply, opening all cover/doors, cleaning of all joints/contact points by using CRC,dismantling and taking out old unserviceable spares of Panel board of any type and shapeand fixing of new parts complete including tightening of all existing connections/screws/ nuts & bolts etc all as specified and directed .Note : Defective sapre parts required to be replaced will be measured and paid seperately as per relevent items as under. |
| 2 | Comprehensive maintenance of APFC panel boards, indoor/outdoor typr after isolating the panel board from electric supply, opening all cover/doors, cleaning of all joints/contact points by using CRC,dismantling and taking out old unserviceable spares of Panel board of any type and shapeand fixing of new parts complete including tightening of all existing connections/screws/ nuts & bolts etc all as specified and directed by Engr-in-Charge. Note : Defective sapre parts required to be replaced will be measured and paid seperately as per relevent items as under. |
| 3 | (a) Digital 3 Ph multifunction meter, model A, 5A class 1 Make: L&TCat part No WDM303FDWA1 or equivalent in Legrand/ Seimens |
| 4 | (b) CT up to 300/5 of class/burden 1.0/5 VA Make: L&Tor equivalent in Legrand/ Seimens |
| 5 | (c) LED Indicator Lamp in three colours RYB ( L&T) or equivalent |
| 6 | (d) Replacement of hinges, locking arrangements of each panel board by cutting/ welding etc all as specified and as directed |
| 7 | (e) Fabrication work of LT Panel with 3.00 mm thick MS Sheet (Outer cover), including cutting, welding, moulding all as directed. |
| 8 | (f) Fabrication work of LT Panel with 2.00 mm thick MS Sheet (Inner sheets), including cutting, welding, moulding all as directed. |
| 9 | (g) Aluminium busbar as per existing rating/size and colour coding |
| 10 | Supply only power factor correction capacitor cylindrical type 1 KVAR |
| 11 | Supply only power factor correction capacitor cylindrical type 2 KVAR |
| 12 | Supply onlypower factor correction capacitor cylindrical type 3 KVAR |
| 13 | Supply only power factor correction capacitor cylindrical type 5 KVAR |
| 14 | Supply only power factor correction capacitor cylindrical type 7.5 KVAR |
| 15 | Supply only power factor correction capacitor cylindrical type 10 KVAR |
| 16 | Supply only power factor correction capacitor cylindrical type 15 KVAR |
| 17 | Supply only power factor correction capacitor cylindrical type 20 KVAR |
| 18 | Supply only power factor correction capacitor cylindrical type 25 KVAR |
| 19 | Supply only power factor correction capacitor box type type 1 KVAR |
| 20 | Supply onlypower factor correction capacitor box type 2 KVAR |
| 21 | Supply only power factor correction capacitor box type 3 KVAR |
| 22 | Supply only power factor correction capacitor box type 5 KVAR |
| 23 | Supply only power factor correction capacitor box type 7.5 KVAR |
| 24 | Supply only power factor correction capacitor box type 10 KVAR |
| 25 | Supply only power factor correction capacitor box type 15 KVAR |
| 26 | Supply only power factor correction capacitor box type 20 KVAR |
| 27 | Supply only power factor correction capacitor box type 25 KVAR |
| 28 | Material and labour foronload change over switch for 125 Amp, 4 pole with all arrangements for fixingincluding taking out old UNSV on load change over switch all as directed.Make : L&T/ Schneider/ Havells |
| 29 | All as per item No 28 above but 160 Amp 4 pole |
| 30 | All as per item No 28 above but 250 Amp 4 pole |
| 31 | All as per item No 28 above but 400 Amp 4 pole |
| 32 | Material & Labour for MCCB 63 Amps 16 KA, 4 Pole with Thermal Magnetic Protection Unit including dismentling of old MCCB complete all as specified and directed.Make: Legrand Cat No 4200 13 or equivalent in Siemens/ Schneider/ L&T |
| 33 | All as per item No 32 above but MCCB 100 Amps 16 KA, 4 Pole Make: Legrand Cat No 4200 15or equivalent in Siemens/ Schneider/ L&T |
| 34 | All as per item No 32 above but MCCB 125 Amps 16 KA, 4 Pole Make: Legrand Cat No 4200 16 or equivalent in Siemens/ Schneider/ L&T |
| 35 | All as per item No 32 above butMCCB 160 Amps 16 KA, 4 Pole Make: Legrand Cat No 4200 17 or equivalent in Siemens/ Schneider/ L&T |
| 36 | All as per item No 32 above butMCCB 250 Amps 25 KA, 4 Pole Make:Legrand Cat No 4202 19 or equivalent in Siemens/ Schneider/ L&T |
| 37 | Material & Labour for new moulded case circuit breakers 400 Amp 4 Pole 36 KA in the existing feeder Pillar box/LT panel with new bolts and nuts including connecting the incoming and out going cables etc. Make: Legrand Cat No 4220 07or equivalent in Siemens/ Schneider/ L&T |
| 38 | Supply & fixing MCB TPN 63 amps of 10 KA, \"C\" curve with enclosure in existing panel with incoming and outgoing connection complete all as directed Make : Legrand 4086 83 or equvalant in Schneider/ Havells |
| 39 | All as per item No 38 above but32 amps. Make : Legrand 4086 80 or equvalant in Schneider/ Havells |
| 40 | Supply and fix thermoplastic cable junction boxes IP 55/IP 65 with metric knockout for cable entry including connector of size 295x255x120 mm on pole with MS clamps, nut bolts, washers and glands suitable for 10 to 25 sq mm 04 core cable incl dismantling and taking outold unserviceable cable junction boxes all as specified and directed . Make Sintex catpart No GSJB 2520 or equivalent in Hensel/ Neptune. |
| 41 | Material and labour for roughing old painting from the LT panels by paint removers, cleaning with scrapes and preparing the surface and applyingtwo coatsPainting complete with synthetic enameled paint of existing colour and writing incoming and outgoing feeder/area with stencil complete all as directed. |
| 42 | Material & Labour for Cement concrete in foundation, filling and mass concrete type B2 1:2:4 (40mm graded aggregate). Not exceeding 15 CM in deapth for plinth protaction for path including dismqntling of old surface complete all as specified and directed. |
| 43 | Material and labourfor PCC 1:2:4 for coping of existing LT pole of size 45X45X30cmwith 20mm graded aggregate type B-1 including dismantling of old broken coping complete and also including finishing work with plaster 15 mm thick CM (1:4) and necessary cleaning of surronding Pole of 1 metre distance complete all as specified and directed. |
| 44 | Cutting / trimming of tree branches which are touching of street light/ peremeter pole and disposal of timber complete all as specified and directed. |
| 45 | Taking out existing LT cable of sizes up to 95 Sqmm 2 to 4 core from duct/wall/floor/trenches and re-laying the same serviceable cable after fault rectification in existing position with supply and fixing connecting materials such as thimbles, lugs, nuts, bolts and washers as required at sitecomplete all as specified and directed. |
| 46 | All as per item No 45 above butLT cable of sizes from 120Sqmm to 300 Sqmm 2 to 4 core |
| 47 | Taking down the unserviceable LT cable of any size from trenches/ walls /floor etc complete all as specified and directed. |
| 48 | Material and labourfor LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 10 sq mm 2 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed. |
| 49 | All as per item No 48 above but cross sectional area 16 sq mm 4 core |
| 50 | All as per item No 48 above but cross sectional area 25 sq mm 3.5 core |
| 51 | All as per item No 48 above but cross sectional area 35 sq mm 3.5 core |
| 52 | All as per item No 48 above but cross sectional area 50 sq mm 3.5 core |
| 53 | All as per item No 48 above but cross sectional area 120 sq mm 3.5 core |
| 54 | All as per item No 48 above but cross sectional area 240 sq mm 3.5 core |
| 55 | Material and labour for Aluminium lugs for upto 25 Sqmm E-bolt hole 8.4 to 13 upto 4 core |
| 56 | All as per item No 55 above but for 35 Sqmm E-bolt hole 8.4 to 10.5 upto 4 core |
| 57 | All as per item No 55 above but for 50 Sqmm E-bolt hole 8.4 to 13 upto 4 core |
| 58 | All as per item No 55 above but for 70 Sqmm E-bolt hole 8.4 to 13 upto 4 core |
| 59 | All as per item No 55 above but for 95 Sqmm E-bolt hole 10.5 to 17 upto 4 core |
| 60 | All as per item No 55 above but for 120 Sqmm E-bolt hole 10.5 to 17 upto 4 core |
| 61 | All as per item No 55 above but for 150 Sqmm E-bolt hole 10.5 to 17 upto 4 core |
| 62 | All as per item No 55 above but for 185 Sqmm E-bolt hole 10.5 to 17 upto 4 core |
| 63 | All as per item No 55 above but for 240 Sqmm E-bolt hole 13 to 17 upto 4 core |
| 64 | All as per item No 55 above but for 300 Sqmm E-bolt hole 17 to 20.3 upto 4 core |
| 65 | Material and labour for Copper lugs for upto 25 Sqmm E-bolt hole 8.4 to 13 upto 4 core |
| 66 | Material and labour for copper sector connector upto 25 Sqmmupto 4 core |
| 67 | Material and labour for Aluminium sector connector barrel type upto 25 Sqmmupto 4 core |
| 68 | All as per item No 67 above but upto 35 Sqmmupto 4 core |
| 69 | All as per item No 67 above but upto 50 Sqmmupto 4 core |
| 70 | All as per item No 67 above butupto 70 Sqmmupto 4 core |
| 71 | All as per item No 67 above butupto 95 Sqmmupto 4 core |
| 72 | All as per item No 67 above but upto 120 Sqmmupto 4 core |
| 73 | All as per item No 67 above butupto 150 Sqmmupto 4 core |
| 74 | All as per item No 67 above but upto 240 Sqmmupto 4 core |
| 75 | All as per item No 67 above butupto 300 Sqmmupto 4 core |
| 76 | Material and labourfor Straight through joint kit Heat shrinkable type suitable for 1.1 KV XLPE under ground cable of size 6 sqmm to 16 Sqmm 3.5 core all as directed. Make : Denson/ 3M/ Raychem |
| 77 | All as per item No 76 above but cable of size 25 Sqmm to 50 sqmm3.5 core |
| 78 | All as per item No 76 above but cable of size 70-120 sqmm3.5 core |
| 79 | All as per item No 76 above but cable of size 150-185 sqmm3.5 core |
| 80 | All as per item No 76 above but cable of size 240 to 300 sqmm3.5 core. |
| 81 | Surface excavation n.exc 30 cm deep and averaging 15 cm deep and getting out hard/dense soil including cleaning away all grass vegetation saplings, brush wood under grouting, roots & tree and not exceeding 30 cm girth and removing rubbish to a distance of 50 mtr outside the periphery of area as directed |
| 82 | Excavation in trenches in hard/dense soil not exceeding 1.5 metre wide and not exceeding 1.5M in depth for laying of cables and getting out of excavated material complete all as specified and directed. |
| 83 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed. |
| 84 | Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed. |
| 85 | Material and labour forfor cutting of PCC/Hard standing/WBM road not exceeding 20 cm in width not exceeding 30 cm in depth for passing of LT cable and making good of disturbed surface to match with the existing surfaces by using old and new material i.e bitumen/PCC (1:3:6) type C-1 complete all as specified and directed . |
| 86 | Material and labourfor DWC pipe of 50 mminternal diafor cable protection complete all as specified and as directed .Make : Astral/Ketron Industries/Dutron |
| 87 | All as per item no 86 above but 75 mm internal dia. |
| 88 | Supply and laying in trenches/Floor or fixed to Pole/Wall GI pipe light grade with fitting of size 100 mm bore for protection of cable complete all as specified and directed. |
| 89 | All as per item No 87 above but 40 mm bore. |
| 90 | All as per item No 87 above but 20 mm bore. |
| 91 | Supply and fix 2 core 2.5 sqmm PVC insulated PVC sheathed weather proof multistranded copper conductor cable 1100 volts grade drawn through in GI conduit, pole etcfrom junction box to street light fitting all as specified and directed. |
| 92 | Material and labour for PCC cable routeindicator in mix of 1:2:4 type B1of size 450x200x100 mm with ovel shapeand writing the letter LT cable with synthtic ennamel paint over a coat of yellow paint and embedded with PCC foundation type D2 1:4:8 of size minimum 250mm deapth including necessary earth work complete all as specified and directed. |
| 93 | Dismantling/ taking down and Re-fixing/erecting of Old steel tubular swaged poles any type with accessories/fittings at other location as directedincluding necessary excavation, removal of soil, refilling of soil, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate for foundation of pole and coping with PCC (1:2:4) type B-1 using 20 mm graded stone aggregate all as per SSR part I complete all as specified and directed. |
| 94 | Dismantling/ taking down and erecting of new steel tubular swaged 9 m poleswith accessories/fittings at other location as directedincluding necessary excavation, removal of soil, refilling of soil, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate for foundation of pole and coping with PCC (1:2:4) type B-1 using 20 mm graded stone aggregate all as per SSR part I complete all as specified and directed. |
| 95 | Material and labour forfor preparing surfaces of LT/HT electric polesof any type size including street light brackets, bracket clamps, cable protection pipe, terminal box, stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of aluminium paint completely including painting strips on poles with one coats of sky blue and white synthetic enamel paint complete all as specified and as directed . |
| 96 | Taking out old UNSV earthing and Material and labourfor new earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 25X4mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soilto a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 50mm thick pit cover, reinforced with 8mm dia TMTbars 75mm c/c, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth leadprotection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 3 of SSR Part-I including testing complete. Note : GI strip and protection pipes 40 mm GI light grade up to 7.5 metre is included in unit rate and beyond that the same will be measured separately. |
| 97 | Material and labour for earth continuty conductor or main earthing lead as 25x4 mm GI strip fixed to wall on batten or recess or chasses or burried in ground or drawn in conduit /pipe or fixed to pole or any other situation for loop earthing etc complete all as specified and directed. |
| 98 | Material and labourfor detection of fault through cable fault locator machine by giving high voltage surge and to find out exact location with in minimum time complete all as specified and directed.Note : The item includes transportation, charging machine upto detecting fault at a time and fault should be immediately located after intimation of JE/ Engr-in-charge |
| 99 | Material and labourfor Air termination, single pointed aluminium rod 12mm dia and 300mm long complete all as specified and directed. |
| 100 | Material and labour aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and directed. |
| 101 | Supply & fixing of fire retardant /extinguishing electric 33 KV Rubber mat IS-15652/2006 insulated Synthetic matof 3 mm thick Rubber Material Dotted Textured of mat size 1 mtr * 10 mtrcomplete all as specified and directed. |
| 102 | Supply & fixing in replacement power factor controller relay 12 step 415 Volts, AC,50 Hz to automation to power capacitor including replacement ofcontrol wring as required at site including addition/alteration if required.Make: L&Teta SMART Cat No CS90903OOOO or equivalentLegrand/ seimens |