| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular type switch,modlar plate, suitable size GI. box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group-B |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | Supplying and fixingsize /module ,GI box alongwith modular base & cover plate for modular switch in recess etc as required .(a)6 module (200mmx75mm) |
| 5 | Supplying and fixing follow modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 5/6 A switch |
| 6 | b) 3 pin 5/6 A A socket outlet |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 8 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 9 | Supplying and fixing PVC batten/ angle holder including connection etc. as required. |
| 10 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB / RCCB / Isolator) a) 6way double door |
| 11 | (b) 12 way Double pole |
| 12 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of single poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a)Single pole |
| 13 | (b) double pole |
| 14 | Supplying and fixing of 250 mm sweep, pvcexhaust fan suitable for single phase, 50 Hz, 230 volts, AC supply in existing hole and S/F of louver / shutter including connections etc. as required.Make . |
| 15 | SITC of 1200 mm sweep ceiling fan, suitable for 240 Volts 50 Hz, AC supply, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc as required. |
| 16 | Supplying and Fixing of 9 WLED Mirror Light, 2 feet,6500k environmental friendly, energy efficient, LED batten directlyon ceiling/ wall, including connections etc as required. |
| 17 | Providing and fixing of 9 Watt, LEDbulb including connection etc as required. |
| 18 | Supplying & fixing of20 watt, 4 feet,6500k environmental friendly, energy efficient, LED batten directlyon ceiling/wall, including connections etc as required. |
| 19 | Provding and fixing of 50 wattenergy saving and environmental freindly LED street light, made up of presure die cast aluminium housing, sparate driver compartment with IP66 protection,includingSupplying and fixing of 32 mm dia G.I pipe (medium duty) bracket of 0.75 mtr length bend to required shape on existing wall by suitable clamping arrangement for installation of 50 watt LEDlight fittingetc. as required. |
| 20 | SITC of outdoor type feeder piller, double door made out of 14 SWG CRCA sheet of size 600 mm x 450 mm x300 mm deep having 200 Amp, 4 Nos insulated aluminium bus bars and to accommodate following accessories, front & back door openable and P & F of internal connection with suitable size of cu wires & angle iron frame of size 600 mm x 450 mm with 600 mm long legs made out of 40 mm x 40 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, arrangement for incoming / outgoing cabling / cable termination, earthing, locking, interconnection etc. as required..(i) 63 Amp, DP, MCB, 10 KA, C curve, 240 V, 50 Hz = 01 Nos, make of Havells (ii) 40 Amp, DP, MCB, 10 KA, C curve, 240 V, 50 Hz = 03 Nos, make of Havells |
| 21 | Providing & fixing of following aceesories on existing feeder pillerincluding connection etc as required. (i) 100 amp four pole MCCB- 01 No(ii)80 Amp, 4 pole MCB , - 1 No (iii)63 Amp, 4 pole MCCB , - 1 No(iv)40 Amp DP MCB-05 Nos. |
| 22 | Supplying & laying of one number XLPE insulated and PVC sheathed armoured aluminium power cable of 1.1 KV Grade of size 2 X 10 Sq. MM conf to IS: 7098 (Part-I)direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 23 | Supplying & laying of one numberXLPE insulated and PVC sheathed, armoured aluminium power cable of 1.1 KV Grade of size 2 X 10 Sq. MM conf to IS: 7098 (Part-I) in the existing OPEN duct as required. |
| 24 | Supplying & laying of one numberXLPE insulated and PVC sheathed, armoured aluminium power cable of 1.1 KV Grade of size 2x10 Sq. MM conf to IS: 7098 (Part-I) in the existingHume/METAL/PVC PIPE as required. |
| 25 | Applicable rate of GST@18% ([email protected]) in place of 12 % on total of DSR items |
| 26 | Add labour cess @1% on Total |