| 1 | Supply of 16 meter High mast lighting system with its accessories.Mast shaft shall be in two sections with steel material confirming to BSEN 10025 and material shall be high tensile steel, grade S355, hot dip galvanised confirming to BSEN ISO 1461 and suitable for wind velocity as per IS 875. It shall also include accessories for high mast including head frame, 2 continues steel wire rope 6 mm dia (7/19 construction), trailing cable, double drum winch, Galvanised Lantern carriage arrangement suitable for up to 9 luminaires symmetrically & its control gear (Make of Gear Box : New Allen Berry works / Chandra Gear / Elecon Engineering / Shanti Engineering) boxes and lightning finial. The mast shall have an integral powertool installed inside the base compartment for its operation along with Supply & Fixing of Cu Cable of Power Tool motor, Wiring for Luminaries, Anchor Plate, Foundation Bolt, Nut, Washer, Common Template all complete. Luminaire wiring materials not included in this item. (Make: Bajaj / Transrail / Valmond/ Utkarsh /Skipper) |
| 2 | Erection of high Mast (16 M) on RCC foundation with cementconcrete considering actual SBC of soil, with the help of suitable modern engg. tools and Plants, wiring of luminaries with all wiring materials like PVC insulated flexible cable of suitable copper conductor core of 1.5 mm² lugs, up to 10 nos. 6A MCB along with construction of shallow foundation with cement concrete for high Mast considering the safe soil bearing capacity as per site condition, as per drawing and design of manufacturer of the mast. The soil test and submission of its report is within the scope of the work. |
| 3 | Erection, testing & commissioning of up to 12.0 / 12.5 / 16.0 meter high mast on the existing civil foundation by bolts with suitable tools, tackles, machines etc, all complete, as per direction of the EIC |
| 4 | Supply ofFlood light 200wattage +-5%, Operated voltage 140-270V, 50Hz,5700+/-6%K, PF>0.95, THD<10%, IP 65/66/67, inbuilt surge protection 4kV, external surge protection 10kV, Line to line 440VAC with stand capacity, IK 07/08, System Efficacy >=120LPW, CRI >=70, Pressure die cast alluminum body, optical lens, seperate potted driver, O/V protection, S/C protection, R/P protection, L70, LM 79 /LM 80 NABL Lab, BIS Certificate, warranty certificate provide by OEM latter head . Make Philips(Signify)/ Crompton/ Havells/ K-Lite/ LT |
| 5 | Fixing only Floodlight Fitting with suitable tie clamps and MS plate for mounting on Pole/Tower or similar structure |
| 6 | Supply & errection of Feeder pilar box with 63A FP Isolator-1no, 32A FP MCB -3nos. with 63A AL Four Bus bar , 70A Contactor- 1 no. Timmer -1no. With specing for installation of WBSEDCL 3 phase energy meter, All make Pwd Sch Approved |
| 7 | Supply and delivery at site of 4C X 16Sqmm 1.1 Kv grade PVC/XLPE armored Al. conductor(LT) cable, conforming IS: 7098 (Part-1) , Make: Havells/ Polycab/KEI / RR/ Gloster/ Mescab |
| 8 | Supply of PVC insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt, Conforming to IS 694 : 2010, Make: Havells/ Polycab/KEI / RR/ Gloster/ Mescab |
| 9 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre or through suitable size HDPE pipe , including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed |
| 10 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : 4C X 16Sqmm |
| 11 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe |