| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor ingle core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(i) Group B |
| 2 | Wiring for light point/ power plug with 2x 4 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit, along with 1 No 4 sq.mm. FR PVC insulated copper conductor single core cable for loop earthing as required . |
| 3 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as rerquired. i) 2 x 1.5 sqmm + 1 x 1.5 sqmm earth wire |
| 4 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. i) 5/6 amps switch |
| 5 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. ii) 3 pin 5/6 amps socket outlet |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing2 Nos 3 pin 5/6 AA modular socket outlet and 2 nos ,5/6 A modular switch, connections etc. as required. (for light plug to be used in non residental buildings) |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 8 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 9 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 10 | Supplying and fixing 3 pin, 5 amps ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 11 | Supplying and fixing PVC batten /angle holder including connection etc as required |
| 12 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 13 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (ABB/Legrand/Schneider /L&T/ Siemens)(i) 12 way, Double door |
| 14 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc as required.(i) Single pole |
| 15 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.(i) 63 amp |
| 16 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 17 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. wire in 15 mm dia G.I. pipefrom earth electrode including connection with GI thimble excavation and re-filling as required. |
| 18 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 19 | Providing and Fixing of 300 mm sweep turbo force double ball bearing medium speed, HD Exhaust fan, single phase, 240 volt 1400 rpm in existing opening, including making good the dmage, connection, testing, commissioning etc as required. Make Crompton/ Havells/ Bajaj / Usha/ orient etc. |
| 20 | Supplying and Fixing of Wall Bracket, Decorative wall light fixture made up of Polycarbonate, suitable for 9 W retrofit LED lamp B22 base including 9 watt lamp etc as required. Make : Havells/ Crompton/ Philips / bajaj/ syska. |
| 21 | Supplying and Fixing of 20/22 W Dimmable LED Batten, 4 feet batten type 6500 K LED batten with premium metallic grey finish along with superior grade diffuser for glare free soothing light with 4 V Surge protection & High voltage protection up to 440 V Make : Havells/ Crompton/ Bajaj/ philips / Bajaj / Syska etc. |
| 22 | Supplying and fixing of 12 Watt ,6500 K cool daylight surface mountingbolt round/ squaredown light of Havells/ Crompton / Phillips /Bajaj / syska etc. |
| 23 | Providing and Installation of Green Line road lighting luminiaries with 30 watt high power LED and unique peanut lens to ensure uniform distrubution, heigher soacing between poles and maintenance free system, including suitable size GI pipe bracket size 1 Mtr with suitable angle in existing wall/ ceiling (bracket with nuts & bolts/ bricks works) etc as required. Make Crompton/ Bajaj/ Havells/ Philips/ syska etc. |
| 24 | Supplying, installation, testing and commissioning of 1200 mm sweep, 240 Volt, 50 Hz A.C. ceiling fan having double ball bearing along with 3 nos aluminium alloy blades, Canopy and300 mm down rods including wiring the down rod of standrad length (up to 30 cm) with 1.5 sqmm, FRLS PVC insulated, copper conductor, single core cable etc as required (Make : CG/ Usha/ Havells / Khaitan/ Orient etc) |
| 25 | Supplying and fixing of 9 W LED, Lampin existing PVC holder. Make : Havells/ Bajaj/ Crompton/ Philips / syska etc |
| 26 | Add Cost Index |
| 27 | Credit for dismantled copper wire from circuit/ submainfollowing size FRLS PVC insulated copper conductor, single core cable as required. A) 1.5 sqmmwire |
| 28 | Credit for dismantled copper wire from circuit/ submainfollowing size FRLS PVC insulated copper conductor, single core cable as required. A) 4.0 sqmmwire |
| 29 | Credit for dismantled enamelled copper wire rewinded 1200/1400 mm sweep ceiling fan and fan body as required. |
| 30 | Credit for dismantled pre wire complete flourescent tubelight fittings as required. |
| 31 | Credit for dismantled 20 mm steel conduit pipe. |
| 32 | Credit for dismantled of sheet steel, MCB distribution board, 240 volts, from surface/ recess complete as required. (A) 12 way DB |
| 33 | Credit for dismantled SP/SPN type6-32 amp MCB as required. |
| 34 | Credit for dismantled copper wire winded 300/400 mm Exhaust Fan and fan body as required. |
| 35 | Credit for dismantledof 5 Amp piano type switch as required. |
| 36 | Credit for dismantledof 5 Amp socket as required. |