Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | ( PART-A ) Supplying anderecting HMS PVC conduitFRLS grade 20 mm dia. with PVC accessorieson wall / ceiling as per specification No: WG-MA/CON. |
| 2 | Supplying anderectingPVCtrunking (PVC casing-n-capping)ofsize20 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 3 | Supplying anderectingPVCtrunking (PVCcasing-n-capping)ofsize25 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 4 | Supplying anderectingPVCtrunking (PVCcasing-n-capping)ofsize32 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 5 | Supplying and erecting mains with 2x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 6 | Supplying and erecting green earth wire 2x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 7 | Supplying and erecting green earth wire1x2.5 sq.mmFRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 8 | Supplying and erecting mains with 2x2.5 sq.mmFRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 9 | Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 10 | Supplying and erecting green earth wire 1x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 11 | Supplying and erecting mains with 2x10 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 12 | Supplying and erecting mains with 4x16 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 13 | Supplying and erecting mains with 4x25 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 14 | Supplying and erecting PVC insulated PVC round sheathed 1.5 sq.mm (30 no. x 0.25 mm dia.) 3 core flexible multi strandedcopper Industrial cable for voltage grade up to 1.1 kV |
| 15 | Supplying and erecting PVC insulated PVC round sheathed 2.5 sq.mm (50 no. x 0.25 mm dia.) 3 core flexible multi strandedcopper Industrial cable for voltage grade up to 1.1 kV |
| 16 | Supplying and erectingCeiling rose / Batten holder / Slanting holder / hanging cord switch / hanging bell push / pendant holder bakelite base 6A. erected on filled polypropylene board or polished double wooden block/ PVC junction box. |
| 17 | Supplying and erectingmodular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete. |
| 18 | Supplying and erectingmodular type switch 16Aduly erected on provided plate and box with wiring connections complete. |
| 19 | Supplying and erectingmodular type bell-push with indicator 2 modules 6A / 10A, duly erected on provided plate and box with wiring connections complete. |
| 20 | Supplying and erectingmodular type 3 pin 6Amultisocket with safety shutter, duly erected on provided plate and box with wiring connections complete. |
| 21 | Supplying and erectingmodular type 3 pin 6 / 16Amultisocket with safety shutter,duly erected on provided plate and box with wiring connections complete. |
| 22 | Supplying and erectingmodular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete. |
| 23 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 2module duly erected. |
| 24 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3module duly erected. |
| 25 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 6module duly erected. |
| 26 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 12module duly erected. |
| 27 | Supplying and erecting 16 / 20 / 25 A starter (modular range) 2 module for AC unit on provided box complete & duly concealed with necessary material and connected. |
| 28 | Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthingand required accessories as per specification No: WG-PW/SW |
| 29 | Point wiring for ceiling fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthingand required accessories as per specification No: WG-PW/SW |
| 30 | Wiring for plug on board withSwitch socket surface/concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW |
| 31 | Supplying and erectingLED square / circular Max. 11 W down lighter/Panel Light having pressure die-cast aluminium housing,polystyrene diffuser havingsystem lumens output of Min. 1200 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%,THD<10%, p.f. >0.95, operating range of120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50,including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 32 | Supplying and erectingLED square / circular Max. 14 W down lighter/Panel Light having pressure die-cast aluminium housing,polystyrene diffuser havingsystem lumens output of Min. 1500 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%,THD<10%, p.f. >0.95, operating range of120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50,including driver,having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 33 | Supplying and erectingLED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing,polystyrene diffuser having system lumens output of Min. 2000 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%,THD<10%, p.f. >0.95, operating range of120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver,having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 34 | Supplying and erectingLED square / circular Max. 25 W down lighter/ Panel Light having pressure die-cast aluminium housing,polystyrene diffuser having system lumens output of Min. 2750 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%,THD<10%, p.f. >0.95, operating range of120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50,including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 35 | Supplying and erecting anodized aluminium corridor / passage / mirror light LED fitting (2 feet) Max. 12Wwith high transitivity diffuser with min. system lumens output of 1200 lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%,THD<10%,p.f. >0.95, operating range of200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver with end caps on provided PVC Block / wooden board with 3 years warranty. |
| 36 | Supplying & erecting inverter LED batten 10W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAh Lithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt,CRI>80, CCT of 6500K and THD<=20% havinguseful life of minimum 25000 hrs. with overheating protection with 2 years warranty. |
| 37 | Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAh Lithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt,CRI>80, CCT of 6500K and THD<=20% havinguseful life of minimum 25000 hrs. with overheating protection with 2 years warranty. |
| 38 | Supplying and erecting ding dong / electronic musical type call bell with heavy duty coilsuitable to operate on 230V A.C. supply erected on polished double wooden block/sunmica block of suitable size. |
| 39 | Supplying and erecting integrated LED street light fitting 23 to 25W IP65 & IK08 class having single piece pressure die-cast aluminium housing,havingsystem lumens output of Min. 2300 Lumens, min. efficacy of 100 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3Years warranty as per specification NoFG-ODF/FLS2. |
| 40 | Supplying and erecting integrated LED street light fitting 40 to 50W IP65 & IK08 class having single piece pressure die-cast aluminium housing,havingsystem lumens output of Min. 4400 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K,THD<10%, p.f. >0.95, operating range of140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty as per specification NoFG-ODF/FLS2. |
| 41 | Supplying and erecting integrated LED street light fitting 60W IP65 & IK08 class having single piece pressure die-cast aluminium housing,havingsystem lumens output of Min. 6600 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty as per specification NoFG-ODF/FLS2. |
| 42 | Supplying and erecting street light Wall bracket made from 40 mm. dia ‘ G.I. pipe 1.2 m. in total length complete as per specification no. FG-BKT/WB |
| 43 | Supplying and erecting regular/ standard model ceiling fan of 900 /1050 mm. sweep complete erected in position as per specification no. FG-FN/CF |
| 44 | Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete. |
| 45 | Supplying and erectingenergy saving ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF |
| 46 | Supplying and erecting fan hook of 10 mm. M.S. round bar grouted in RCC slab with making the site as original. |
| 47 | Supplying and erecting midget type 3.0 litres instant type water heater of rustproof & shockproof ABS plastic body, high grade SS inner tank & 3kW heating element with corrosion & hard water protection, with minimum 3 safety protections (i.e. thermostat & thermalcut-out, function valve) complete with 6.5 bar pressure withstanding capacity 230/250V, 50Hz, A.C. supply with inlet and outlet, with 3 core PVC flexible copper wire leads duly tested and marking sr. no. and date of erection complete. |
| 48 | Providing fiber reinforced PVC flexible pipe upto 1m length with brass locking nuts and washers and clips at both ends suitable for hot water and cold water both (1 set of 2 nos.) complete. |
| 49 | Supplying, installing, testing & commissioning split type variable speed invertertechnology with minimum 3 to 1 convertible mode for compressor, room air conditioning unit 1.3TR to 1.6TR capacity having ISEER minimum 3.8 to maximum 4.39 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser, minimum 2.5PM filter, self diagnosis feature, stabilizer free operation & temperature display on indoor unit, noise level maximum 50dBA at position as per specification no. APAC/ WAC |
| 50 | Supplying & erecting seamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigerant having 22SWG thickness and inner dia/size 12mm complete. |
| 51 | Supplying & erecting seamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigeranthaving 22SWG thickness and inner dia/size 16mm complete. |
| 52 | Supplying and erecting switch disconnector fuse (SDF) switch 415V, 160A, open execution, four poleAC23 A rated with terminal shrouds on both sides and phase barriers along with telescopic shaft for depth adjustments and door interlock and padlock complying to IS/IEC 60947-3 Part-1/3 HRC - DIN type fuse, insulation voltage 1000 Vfor enclosing in panel with rotary handle for ON / OFF operation (without HRC fuse) |
| 53 | Supplying, erecting & marking SPMCB 0.5A to 5A, C-series with rated short - circuit breaking capacity (Icn) 10kAin provided distribution board as per specification no. SW-SWR/MCB |
| 54 | Supplying, erecting & marking SPMCB 6A to 32A, C-serieswith rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 55 | Supplying, erecting & marking SPMCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 56 | Supplying, erecting & marking DPMCB 6 A to 32 A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 57 | Supplying, erecting & marking TPMCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 58 | Supplying, erecting & marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 59 | Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kAin provided distribution board as per specification no. SW-SWR/MCB |
| 60 | Supplying, erectingand marking double pole isolator only switch version of miniature circuit breakerof40Awith required wiring connections and lugs etc. in provided distribution board. |
| 61 | Supplying&erectingtriplepole and neutral distribution board (TPNDB), SP/TP MCBs total 4 ways /12 Poles, with door, 1.2mm thickness surface/flushmounted, IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB |
| 62 | Supplyingand erecting single pole and neutral distributionboard (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB |
| 63 | Supplyingand erecting single pole and neutral distributionboard (SPNDB), with 2 ways for incoming and 10 ways (10 poles) for outgoing SP MCBs,with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB |
| 64 | Supplying & erecting CRCA sheet metal enclosures of 1.2mm thickness with 20A, 2 pin plug & earth socket and 20A, 3 pin plugtop with 20A/30A single pole MCB having rated short - circuit breaking capacity (Icn) 10kA complete erected on angle iron/ GI frame. |
| 65 | Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame. |
| 66 | Supplying & erecting triple pole and neutral distribution board (TPNDB), 3 pole/ 4 pole MCCB as incomer & outgoing SP MCB (12 poles) or TPMCB of 4 ways (12 poles), with door, 1.2mm thickness, surface/flush mounted, on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1 |
| 67 | Providing & erecting 4 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 68 | Supplying and erecting plywood 12 mm thick fixed to wall or on provided panel board with necessary materials such as screws, wall fasteners supports, nuts bolts etc. complete.(1 mtr.x 1mtr.) |
| 69 | Supplying and erecting cupboard for enclosing switchgears orforany other purposemadefromselected marine plywood planks 19 mm thick duly varnished/ painted from inside and from outside with brass hinges and locking arrangement with suitable lock with keys in duplicate. Cupboard shall be duly grouted with suitable size of iron work in wall at the bottom. (Size of cupboard for 1No. 0.3x0.4x2Nos+0.4x0.3x2Nos+0.4x0.4x2 Nos.= 0.8 Cu.Mtr. So for such 8 panels. 0.8Cu.Mtrs.x8 Nos.= 6.4 CuMtrs.) |
| 70 | Supplyinganderectingiron work, sheet metal work consisting of CRCAsheets, varioussectionsofiron,plates, chequeredplates,rods,bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthepositionwith necessarymaterialsdulypaintedwith one coat of red oxide and two coats of enamelpaint to match the switchgears or as per directions by the authority.(Frame for main panel board by 50x50x6 mm equal angle @ 4.5 Kg/mtr. So weight of iron 0.75mtr.x 5 Nos +0.3mtrs.x4 Nos.= 4.95mtrs.+ Top frmaem to support G.I square mesh 0.75x5+0.3x 4= 4.95mtrs. i.e 9.90mtrs.x4.5kg= 44.55Kgs.) |
| 71 | Supplying and erecting expanded metal jali enclosure made from GI square mesh 15SWGhaving20/25 mm squares,properly fixed/welded and duly painted with one coat of red oxide and two coats ofsilver/enamelpaint complete. (size of jali 0.4X0.75X2M+0.4X0.75X2M+0.75X0.75X2M= 3.6 Sq.Mtrs.)) |
| 72 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 2 core 6sq. mm. aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 73 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core70sq. mm. aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 74 | Supplying & erecting G.I. pipe‘A’ class 40 mmdia.erectedfor enclosingXLPEarmouredcable on wall/poleas per specification no. CB-CE |
| 75 | Supplying andlaying (including excavation of suitable width & depth up to 90 cm) 50 mmoutside dia. double wall corrugatedpipes(DWC) ofHDPE for enclosing cable below ground/road surface, to required depth complete. |
| 76 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 75 mmoutside dia. double wall corrugatedpipes (DWC) ofHDPE for enclosing cable below ground/road surface, to required depth complete. |
| 77 | Supplying & erectingcast iron cable indicatorplate buried along with route of cable for PVC / XLPE armoured cableas per specification No. CB-CIP |
| 78 | Supplying & erecting FRP box of size 150mm x 125mm x 100 mm, 2.7 mm thickcomplete on pole/wallas per specification No. CB-SB |
| 79 | Providing & erecting 6 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL |
| 80 | Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT |
| 81 | Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results asper specification no. EA-EP |
| 82 | Providingpipetype earthing with 40mm. dia. G.I. pipe or 20 mm dia. G.I. Rodcomplete with all materials testing and recording the results as per specification no. EA-EP |
| 83 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete. |
| 84 | Making cement concretefoundationin 1:3:6 cement concrete,(20 to 25) mm. stone metal duly plastered with necessary curing forcomplete. (pole muffing or any other purpose). |
| 85 | MakingM- 20 grade reinforced cement concretefoundation by considering the safe soil bearing capacity at site as 10 T/sq.mat 1.5 m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 6m to 8m high octagonal /conical GI pole). |
| 86 | Provision for 3 Phase service connection Charges towards M.S.E.D.Co. Ltd. |
| 87 | ( PART-B ) Supplying anderecting HMS PVC conduitFRLS grade 20 mm dia. with PVC accessorieson wall / ceiling as per specification No: WG-MA/CON. |
| 88 | Supplying and erecting green earth wire 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 89 | Supplying, installing, testing and commissioning of5 kWp ON-GRID Solar PV System / Plant consisting Solar PV Poly Crystalline Panel (335 Wp X 15 Nos.) and Solar ON-GRID Inverter of similar capacity (THD<3%) with interconnectingwires / cables up to solar ON GRIDinverter, proper base plate, canopy box to house Inverter and necessary accessories i.e. ACDB/ DCDB , MCB etc. wiring up to solar Inverter in casing and capping, display board, sign board, two distinct earthing, lightning arrester, liaisoning charges, remote monitoring system with maintaining card/chip for 5 yearsincluding net charges for RMS system, complete up to net meter installation and export to the grid with 5 year ON-SITE warranty and fully comprehensive maintenance contract as per Specification no. ESD-RT-ONG |
| 90 | Supplying, erecting & marking DPMCB 40A to 63A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 91 | Supplyinganderectingiron work, sheet metal work consisting of CRCAsheets, varioussectionsofiron,plates, chequeredplates,rods,bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthepositionwith necessarymaterialsdulypaintedwith one coat of red oxide and two coats of enamelpaint to match the switchgears or as per directions by the authority. |
| 92 | Supplying and erecting static energy meter with 240V 50 Hz. AC supply 10 to 60 A, ISI mark,accuracy class 1.0 with backlit LCD display, (measuring and display kWh, kVAh, V,I,PF, frequency, kW, kVA, six months history of Energy & MD in kW & kVA ) with transparent hinge type box completeerectedonpolishedteak woodboardduly wiredwithrequiredsizeof weather proofPVC wires duly testedby electric supply company. |
| 93 | Supplyinganderectingsingle phase 10 to 60 A net meter of accuracy class 1.0, 240V, 50 Hz,with backlitLCD display, optical port ( measures import kWh, export kWh, net kWh, V, I, kW, 12 months history of energy)with wiring connections and mountinghardwareonprovidedpanelscompletewith calibration certificate from manufacturer. |
| 94 | Supplying, installation & marking of surge arrestor/ surge protection device at the sub main distribution board after the incoming breaker of type 2 tested forImax 40 kA for single phase and neutral with compliance to IEC 61643-11 as per specification no. CP-SPD |
| 95 | Supplying, erecting& terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core6sq. mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 96 | Providingpipetype earthing with 40mm. dia. G.I. pipe or 20 mm dia. G.I. Rodcomplete with all materials testing and recording the results as per specification no. EA-EP |
| 97 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clampsfixed on wall painted with insulating and non-corrosive bond with requiredjointsAs per specification no. EA-EP. (length of G.I strip 28 mtrs. & size 32x6mm.weight 1.510Kg/mtr. So weight of strip 28mtrs.x1.510Kgs=42.28 Kgs.) |
| 98 | Making cement concretefoundationin 1:3:6 cement concrete,(20 to 25) mm. stone metal duly plastered with necessary curing forcomplete. (c.c.foundation for stand of solar pv panel 0.3x0.3x8x2 = 1.44 cu.mtrs.) |
| 99 | ( PART-C ) Supplying and erecting marine (Waterproof) plywood 18/19 mm thick fixed to wall or on provided panel board with necessary materials such as screws, wall fasteners, supports, nut bolts etc. complete with compliance to IS 720:2010 ( 0.4572X0.6096 = 0.278 SQ.Mtr to fix DTC Mteter in CRCA sheet box) |
| 100 | Supplyinganderectingiron, sheet metal work consisting of CRCAsheets, varioussectionsofiron,plates, chequeredplates,rods,bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthepositionwith necessarymaterialsdulypaintedwith one coat of red oxide and two coats of enamelpaint to match the switchgears or as per directions by the authority.(, for erection ofdisc insulator, Channel100x50x5 mm. @9.6 Kgs/mtr. 1.6 mtrs. in length channel is proposed, and On pole to support the channel, 1.5 mtrs. on both side i.e 1.5x2=3 mtrs. angle 50x50x6 mm stud angle is proposed. @ 4.5 Kgs./mtr. So total weight4.5 x3 mtrs.= 13.5 Kgs. So total weight of channel and angle is 1 Nosx1.6 mtrs.= 1.6mx9.6kg=15.36 Kgs. mtrs.+13.50 Kgs. =28.86 Kgs ) (12 SWG CRCA Sheet for DTC meter & other)0.4572x0.6096x2+0.4572x.04x2+0.6096x0.4x2=1.41 sq.mtr. waight of [email protected]/sq.mtr. i.e 1.41 sq.mtrx19.61kg=27.65 Kgs. Total waight 28.86+27.65= 56.51 Kgs.) |
| 101 | Supplying anderectingLT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 , 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measure & display trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF events, instantaneous parameters of rating 1/5 A with display in absence of power completewithzeroadjustment&testcertificatefrom manufacturer erected on providedM.S. box and connected to CTs. |
| 102 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core95sq. mm. aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 103 | Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ ( (11 MTRS. / POLESUCH 2 POLES) |
| 104 | Supplying and erecting V cross arm with ISM channel of75x40x6mmfor 11kV HT OH line with arrangement to fix insulator at 45mm from the end & horizontal distance between insulators 1220mm bent at angle of 60 degree keeping base 305mm and the total vertical height ofV cross arm as 460mm, and fixed on pole with MS clamp of 80x10 mm, nut bolts, washers complete as per specification no. OH-PL/VCA |
| 105 | Supplying and erecting 75x40 x6mm with 4.4mm thick web and 7.3mm thick flangechannel (top pin) with clamp of suitable length so as to maintain vertical clearance of 1065mm for 11kV, 1320mm for 22kV between insulators for erection of top pin insulators complete as per specification no. OH-PL/VCA |
| 106 | Supplying and erecting bracket for guarding ofHT OH Line, made from channel iron 1600mm in length and 65x65x6mm thickerected on pole as per specification no. OH-PL/VCA |
| 107 | Supplying & erecting end poleD. P. Structure for 11/0.415 kV, 63 kVA Transformer with R.S.J. Pole 2 Nos. of size 100 x 116 mm x 11 Mtr. Longwith suitable Distribution Box of C.R.C.A. Sheet 16 SWGwith 4 Pole MCCB 100 Amps as incomer & 6 Nos. 63 Amps Kitkat / MCCB for out going circuits. Transformer D.P. Structure includes the A. B. Switch 200 Amps, D.O. fuse Set & L.A. Set. 2 Nos. Top channel of size 100mmx 50 mmfor erection of A.B. Switch & 2 Nos. Basechannel of size 100 mm x50 x mm for erecting Transformer. Channelof size 75 x40 mm for erecting D.O. Fuse Set, L.A., A.B. Switch handle etc. Angle of size 50 x 50 x6 mm for erecting Distribution Box , Transformer Belt etc.as per drawing (min. 124 Kg. iron work)with necessary clamps, Nut-bolts. V cross arm, top clip, insulators etc. complete with caution board & barbed wire. D.P. Structure shall be erected in c.c. foundation complete. |
| 108 | Supplying and erecting ACSR conductor of size 6/1-3.60 mm complete. (Ferret) (171.3 kg/km) as per specification No. OH-CON/ACSR |
| 109 | Providing and fixing GI earthing stud with necessary materials . |
| 110 | Supplying and erecting porcelain disc type insulator 45KN with necessary hardware suitable for 11kV line, complete as per specification no. OH-INS/DI |
| 111 | Supplying and erecting porcelain pin type insulator with GI pin suitable for 11kV line, complete asper specification no. OH-INS/PN |
| 112 | Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6 mm., straining screws,G.l. stay wire 7/8 SWG, G.l. stay rod 20mmx1.8m length and poleclamps duly erected in provided cement concrete foundation complete. |
| 113 | Supplying and erecting guarding lace for HT OH line with 8SWG G.l. wire to protect the HT OH line with binding wire of 20SWG G.l. wire for 75mm section on either side. |
| 114 | Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results asper specification no. EA-EP |
| 115 | Providingpipetype earthing with 40mm. dia. G.I. pipe or 20 mm dia. G.I. Rodcomplete with all materials testing and recording the results as per specification no. EA-EP |
| 116 | Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete.(8 swg g.i wire @0.102kg/mtr 120x2= 240mtrs. X 2% sag= 244.80 say 245 mtrs. So 245mtrs.x0.102kg= 24.99 say 25 kgs.) |
| 117 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clampsfixed on wall painted with insulating and non-corrosive bond with requiredjointsAs per specification no. EA-EP. (25x3mm flat @0.59kg/mtr. 22 mtrs. 12.98 say 13 kgs.) |
| 118 | Supplying, installing, testing & commissioning of3 phase, 11/0.433 kV, 50 Hz.,63 kVA, Mineral oil immersed and naturally cooledoutdoor type, aluminium wound without gas cushioning hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 40℃ by thermometer in oil and 45℃ by the resistance methodin winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off load +2.5 to -5 in steps of2.5%, having 4 number of tap positions, with standard accessories complete with test certificate with losses below 340 Watts at 50% load, 1140 Watts at 100% load as per IS:1180 (part 1) : 2014, with necessary permissions of Electrical Inspector, as per specification no SS- TR-SL |
| 119 | Supplyinganderecting hard drawn coppersolidwire no. 0to 6SWG complete erected for connections on H.T. sides.(0.1668kg/mtr. So for 18 mtrs. 0.1668x6=1.00 kg. ) |
| 120 | Supplyinganderectingextrathick alkathene pipe 10 mm dia. erected to enclosebareconductor wires complete.. (use shall be restricted to H.T.) |
| 121 | Supplying & erecting barbed wire two ply with 12 SWG ply and 12 SWG barb with a gap between two bars of 75 mm. firmly fixed on provided angle supports with necessary materials complete. (6.044 meters/kg.).( Per pole 3.5 Kgs. So for 2 poles 3.5 Kg x 2 pole= 7.0 Kgs |
| 122 | Providing printed instruction chart for treating persons suffering from electric shock,printedinEnglish & Marathi and duly laminated complete. |
| 123 | Makingcement concrete foundation including excavation(60 x 60) cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal,45 cm x 45 cm x 45 cm /45 cm dia. x 45 cm. height plinth duly plastered, with necessary curing and finishing complete. (for above 9 m poles) |
| 124 | Making cement concrete foundation including excavation(60x 60x 150) cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metalwith necessary curing and finishing complete.(for stay). |
| 125 | Lum Sum provision for 3 phase energy meter towards M.S.E.D.Co. Ltd. |
| 126 | Add 18% For GST |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy