Emergent Repairing Of Burned H.T Main Gear With Supply Of Materials And Dehydration Of Transformer, L.T. Obc Panel Servicing, Repairing & Winding Of 65 Hp Motor Including Electrical Wiring Works Of Renovated Raw House At Sewerage Treatment Plant (Bstp)By
Tender Overview
Project Description
Emergent repairing of burned H.T main Gear with supply of materials and Dehydration of Transformer, L.T. OBC Panel servicing, repairing & winding of 65 HP motor including electrical wiring works of renovated raw house at Sewerage Treatment plant (BSTP)by Central Mechanical Division under UD&MA deparment
BOQ
| Sl. No. | Item Description |
| 1 | Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit \"FR\" (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box and mending good the damages to original finish. |
| 2 | On Board |
| 3 | Average run 4.5 mtr |
| 4 | Average run 6 mtr |
| 5 | Distribution wiring in 1.1 KV single core stranded \"FR\" PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit \"FR\" (Precision make) incl. necy. fittings as required. |
| 6 | 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 7 | Supply & Fixing 240 V 16 A Piano key type switch (Brand approved by EIC) on GI Modular type switch board having top cover plate and making necessary connections as required. |
| 8 | Supply TMC501 Conventional industrial batten Philips LED tube. Model no:- 501 P 1xT-LED 22W P3241 |
| 9 | Supply and fixing of approved make 1200 mm high speed ceiling fan (ISI marked) of following sizes having double ball bearing complete with standared down rod, canopy, hanging shackle, Aluminium blades, without regulator, A.C. 230-250 volts. USHA MAKE |
| 10 | Supply and fixing of approved make 300 mm sweep exhaust fan heavy duty with mounting frame, blades AC 230-250 USHA/Approved make |
| 11 | Supplying and fixing 4-way double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. Legrand Make |
| 12 | Supplying and fixing 63 A FP 240/415 V MCB Isolator on din rail of existing DBs and necessary connection.Make Legrand |
| 13 | Supplying and fixing 6-32 A 240/415 V SPN MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection.Make Simens |
| 14 | Dismantling steel tubular/Rail/Strut embedded in CC foundation incl. excavation, filling of holes, restoring surface, loading at site and delivering, unloading, sorting, stacking properly at any place as per direction upto a lead of 1.6 km. |
| 15 | Erection of Minipole of height 3.25 mtr to 5.0 mtr. in C.C Foundation 0.46 m * 0.46 m * 0.9 mtr depth of 1:3:6 cement concrete with hard jhama metal / stone chips including muffing of 0.3 m * 0.3 m * 0.3 m painting the pole with 2 coats of Aluminium paint over a coat red oxide. |
| 16 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:By ISI-Medium GI pipe. |
| 17 | Supplying of 1.1 KV grade XLPE insulated aluminium armored conductor of following cables. Gloster/KEI/ finolex make |
| 18 | 2 core 10 sq. mm. armoured |
| 19 | 4 core 10 sq. mm. armoured |
| 20 | 4 core 35 sq. mm. armoured |
| 21 | Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. |
| 22 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. |
| 23 | Supplying and fixing of different types of LED lamps (9W)Make: Philips, 9.0 Watt, Base B22/E27, 825 Lm |
| 24 | Supply and fixingof smart bright essential street light (68 Watt) complete with all accessories to be fixed/projected from the wall of the building or on pole incl. making holes providing clamping arrangement with 1.5 sq.mm PVC insulated single core copper wire and making connection. Make :- Philips/Panasonic/Bajaj/Crompton |
| 25 | Supply and fixingof smart bright essential street light (30 Watt) complete with all accessories to be fixed/projected from the wall of the building or on pole incl. making holes providing clamping arrangement with 1.5 sq.mm PVC insulated single core copper wire and making connection. Make :- Philips/Panasonic/Bajaj/Crompton |
| 26 | Supply and fixingof greenline V2 street light (120 Watt) complete with all accessories to be fixed/projected from the wall of the building or on pole incl. making holes providing clamping arrangement with 1.5 sq.mm PVC insulated single core copper wire and making connection. Make :- Philips/Panasonic/Bajaj/Crompton |
| 27 | Dehydration & filtration of power tranformer oil to raise the dielectric strength to the value specified in IS including submission of test result. The cost includs man, machinary, tools & plant hire charges to complete the at site as per direction of EIC. |
| 28 | Opening the transformer breather and refitting the same after changing the silica gel including the supply of necessary gasket and silica gel. |
| 29 | Servicingand overhauling of 400 AMPS, 11KV VCB dismantling the rack from the housing, opening the components, necessary cleaning of the components, cabonised portion, changing of rubber gasket, defective parts, cleaning of all mechanism parts and lubricating the mechanism, opening of C.T & P.T\"s, busber spout assemble cleaning the same and insulated properly by supply of C.T.C etc. and refitting all the parts to its original position by making all relevant electrical connection, panel wiring etc, for satisfactory & operation |
| 30 | Servicing, cleaning and testing, calibration of following relay for 11 KV panel. |
| 31 | For Incomer Feeder:-- Each relay set consists of following relays MICOM P110 /122/127/ 1 NO. CGL 14N/C - 1 NO VAX31 - 1 NO, VAA-33 -1 NO VAMP-31 - 1 NO, VAJH-13 - 1 NO. |
| 32 | Dismantling, servicing, cleaning, testing, re-fitting and calibration of each feeder consists of over current- 02 Nos,under voltage 02 Nos, over voltage - 02 Nos (VDG 13 - 02 Nos, VDG 11 - 02 Nos, VDG 14 - 01 No & VDG 31 - 01 No for 11 KVP.T. Feeder. |
| 33 | Complete servicing and heat varnishing of 415V, 3Ph L.T. Sq. cage induction motor after cleaning the stator and heating it up periodically and vernishing by Dr. Beck\"s graded insulating vernishing to obtain stable IR value, cleaning up the rotor, including heating for demoisturisation, lacker coating on the surface of rotor stampings, cleaning and RO priming on the end shield covers, bearing housing and complete the necessary repairing work as per direction of EIC.upto 75 KW LT Sq. cage IM |
| 34 | GST@18% on total amount |
| 35 | CESS@1% on total amount |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender