| 1 | Disconnecting all electric connections and taking down old existing LT panel including MCCB of any size and Supply, installation, testingand commissioning of outdoor type KIOSK panel board suitable for 3 phase 4 wire 415 V, 50 Hz andtested at CPRI for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating in approved shared having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 40x40x6 mm base frame factory fabricated with front openable, double door system lockable/ open able. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted onstand having zine coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 54. Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPNcopperbus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. |
| 2 | The TPN bus bar shall be insulated with colour coded heat shrinkable sleave.All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs of suitable length including PCC (1:3:6) type C-2 as in foundation of suitable size (30 cmbelow ground level & 40 cm above ground level) including necessary excavation and earth work complete all as specified and directed by Engr in charge. NOTE: (Rate of earthwork and PCC are deemed to be inclusive in this item.embedded in PCC foundation of size as required in cement mortar 1:6 and plastering the same in cement mortar 1:6 finished even and smooth without using extra cement complete all as specified and as directed)Make-L&T/ LEGRAND/STANDARD |
| 3 | INCOMING(a) MCCB 4 pole315 A50 KA 415 Volts - 1 No.(b) IntelligentAC digital display three phaseLCD ammeter0 to 500A and voltmeter 0 to 500V with CT.(c)Indication lamp RYB set of 03 -01 No.(d)Digital timer switch.OUTGOING(a)MCCB 4 pole 100 Amps 25 KA 415 Volt - 5 Nos. |
| 4 | Disconnecting all electric connections and taking down old existing LT panel including MCCB of any size and Supply, installation, testingand commissioning of outdoor type KIOSK panel board suitable for 3 phase 4 wire 415 V, 50 Hz andtested at CPRI for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating in approved shared having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 40x40x6 mm base frame factory fabricated with front openable, double door system lockable/ open able. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted onstand having zine coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 54. Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPNcopperbus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. |
| 5 | The TPN bus bar shall be insulated with colour coded heat shrinkable sleave.All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs of suitable length including PCC (1:3:6) type C-2 as in foundation of suitable size (30 cmbelow ground level & 40 cm above ground level) including necessary excavation and earth work complete all as specified and directed by Engr in charge. NOTE: (Rate of earthwork and PCC are deemed to be inclusive in this item.embedded in PCC foundation of size as required in cement mortar 1:6 and plastering the same in cement mortar 1:6 finished even and smooth without using extra cement complete all as specified and as directed)Make-L&T/ LEGRAND/STANDARD |
| 6 | INCOMING(a) MCCB 4 pole315 A50 KA 415 Volts - 1 No.(b) IntelligentAC digital display three phaseLCD ammeter0 to 500A and voltmeter 0 to 500V with CT.(c)Indication lamp RYB set of 03 -01 No.(d)Digital timer switch.OUTGOING(a)MCCB 4 pole 100 Amps 25 KA 415 Volt - 6 Nos.(b)MCB TPN 3 pole 32A 16KA 415 Volt - 3Nos. |
| 7 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core complete all as specified.Make- POLYCAB/HAVELLS/GLOSTER/ FINOLEX/RPG/CCI/KEI |
| 8 | All as per item No 3 above but but size 35 sqmm 3.5 core. |
| 9 | All as per item No 3 above but size 50 sqmm 3.5 core. |
| 10 | All as per item No 3 above but size 70 sqmm 3.5 core. |
| 11 | All as per item No 3 abovebut size 185 sqmm 3.5 core. |
| 12 | Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying of cables etc getting out and forming bottom surface to required gradient complete all as specified and directed |
| 13 | Supply, laying riddled earth soil conformed IS-1255, cushioning to cables with a layer of riddle earth soil 15cm deep before laying the cable and 8 cm depth after laying of cable, complete all as specified. |
| 14 | Brick protection cover on cable with sub class \"B\" brick,laid dry and flat adjacent to each other complete all as specified and directed. |
| 15 | Returning filling including spreading levelling watering and well ramming to excavated soil in layers not exc 25 cmthick each complete all as specified. |
| 16 | Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5m above the starting point in soils complete all as specified. |
| 17 | Supply & Fix DLP U PVC adaptable trunking of size 195 x 50 mm complete with trunking accessories viz cover joints, clips, internal/ external angles, partition/flat junctions and branches complete all as specified and directed.Make- LEGRAND/ SIEMENS/ L&T |
| 18 | Taking out old earthing and Supply and fixing in repair ofEarthing to panel with galvanised steel earth plate electrode60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised earth strip 32 x 6 mm as earthing lead by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead strip protected by GI pipe 80 mm dia light grade and connected to earth test point includingexcavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and directed. |
| 19 | Supply anf Fixing GI pipe light grade 80mm bore for cable protection complete all as specified and directed. |
| 20 | Taking down carefully copper/aluminum sub main wiring of any size including casing and caping / conduit and making good the disturbed surface of walls as directed. |
| 21 | Taking down carefully copper/aluminium point wiring of any type of batten or conduit (Light, Fan, Socket or power) complete removing material from site and making good the disturbed surfaces of walls, roofs etc including two coats of white/colour washing/distempering etc to match the existing complete all as directed. |
| 22 | Taking down carefully main switches DB\"s/ MCB\"sand making good the disturbed surfaces of wallsetc complete all as specified and directed. |
| 23 | Taking down carefully by unscrewing from boards/ outlet boxes, fittings and fixtures such as switches, sockets, ceiling roses, lamp holders, brackets, ceiling fittings, bulk head fittings, tube light fittings and regulators complete all as specified and directed. |
| 24 | M & L point wiring with 1.5 sqmm nominal cross sectional area, single core, 1100 Volts FRLS grade, stranded, PVC insulated, unsheathed copper conductor cable drawn through PVC concealed conduit of suitable size, complete with all PVC conduit accessories/ fittings, brass screws, washers etc, including metal flux boxes of suitable size and modular white plate with frame for mounting modular switches, sockets and regulators etc,including all cutting/chases etc in wallsand including continuousearth wire of size 1.5 Sqmm nominal cross sectional area, single core, PVC insulated copper conductor cable, unsheathed and connected to common earth and earth dolly complete all as specified and directed for One light point /Fanpoint controlled by one switch. |
| 25 | All as per item No 20 above but One 5 Amps socket point on independent board. |
| 26 | All as per item No 20above but wiring complete with 2.5Sqmm for 3 pin 15A socket multipurpose on independent board.Note: 2.5 sqmm for earth wire. |
| 27 | (d)All as per item No.20above but wiring complete with 4Sqmm for AC point.Note: 4 sqmm for earth wire |
| 28 | Supply & fixing modular switch 06 Amps 1 module complete all as specified & directed. |
| 29 | S & F modular socket 06 Amps 2/3 pin, 2 module complete all as specified & directed. |
| 30 | Supply & fixing modular switch 16 Amps 1 modulecomplete all as specified & directed. |
| 31 | S & F modular socket 06/16 Amps 2/3 pin2 modulecomplete all as specified & directed. |
| 32 | M & L for sub main wiring complete with two runs of6 Sqmm single coreFRLS grade PVC insulated unsheathed cable 1100Volt grade multistranded copper conductor drawn through and including PVC conduit and accessories in surface of wall, roofs etc with one run of PVC insulated copper conductor 1x 6Sqmm single core as earth continuity conductor connected with earth dolly and mains complete all as specified and directed. |
| 33 | M & L for sub main wiring complete with two runs of10 Sqmm single coreFRLS grade PVC insulated unsheathed cable 1100Volt grade multistranded copper conductor drawn through and including PVC conduit and accessories in surface of wall, roofs etc with one run of PVC insulated copper conductor 1x 10Sqmm single core as earth continuity conductor connected with earth dolly and mains complete all as specified and directed. |
| 34 | Taking down exhaust fan/wall mounted fan including all fittings and after sevicingFixing only exhaust fan (M.D. supply)/wall mounted fan and connecting up including provision of cable from ceiling rose/connector to fan complete all as specified and diretced. |
| 35 | Taking down ceiling fan including all fittings and after servicing Hanging only ceiling fan (M.D. supply) and connecting up including provision of cable from ceiling rose or connector to fan complete all as specified and directed. |
| 36 | S & F MCB SPN 32Amps, \"C\" series, 240 V complete incl making conections all as specified and directed. |
| 37 | S & F MCB SP 6-32 Amps, \"C\" series, 240 V complete incl making conections all as specified and directed. |
| 38 | S & F MCB DB SPN 8 Way with 200 Amps rated busbar, Double door, 240 volts flush to wall including all cutting etc on wall and making good the disturbed surfaces to match the existing complete all as specified and directed. |
| 39 | S & F MCCB DB Vertical TPN 4 way \"A\" frame,including MCCB TPN 63 Amp breaking capacity 16 KA- 02 nos, double door flush to wall including all cutting etc on wall including making good the disturbed surfaces to match complete all as specified and directed. |
| 40 | S & F MCCB DB Vertical TPN 8 way \"A\" frame,including MCCB TPN 125 Amp breaking capacity 16 KA- 02 nos, double door flush to wall including all cutting etc on wall including making good the disturbed surfaces to match complete all as specified and directed. |
| 41 | Supply and fixingLEDlight fittings 1x20 watts,220V ,PC battentype with driver,holder including LED tube light connecting up with three core flexiable copper conductor cable of suitable size from ceiling rose complete with all accessories complete all as specified &directed by Engineer In charge. |
| 42 | Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V PC batten type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified &directed by Engineer In charge. |
| 43 | S & F electronic fan regulator modular type, 2 module, 120Wincluding complete all as specified and directed. |
| 44 | Fixing only LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. |
| 45 | supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. |
| 46 | Taking down Split/Multi AC unit 1.5/2 Ton capacity/3 ton capacity(indoor and outdoor unit) with voltage stabilizer and AC manager by removing all electrical connections and indoor to outdoor unit gas pipes, nut bolts from HQ bldg and shifting to store for safe custody. After completion of civil work, Refixing/installing Split AC/window AC 1.5/2 Ton with voltage stabilizer at the suitable place by connecting all electrical connections and copper piping with insulation (5/8th x 3/8th and 1/2\" x 1/4\") with nut bolts as per site requirement, testing and commissioning, if any extra cable ,gas pipes, gas filling require at the time of installation the quoted rate is deemed to be included, No extra cost will be paid to contractor complete all as specified and directed by Engr-in-charge. |
| 47 | M&L ceiling rose surface type, 65mm x 50mm three terminals, 3 phase / PVC / polycarbonate isolated body all as specified. |
| 48 | Taking down old GI earth wire and Supply & fixing GI earth wire 4.00 mm dia for interconnecting of earth electrodes all as specified. |
| 49 | Taking down old earthing and Supply and fixing in repair ofEarthing to panel with galvanised steel earth plate electrode60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised earth lead wire 4.0mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead strip protected by GI pipe 40 mm dia light grade and connected to earth test point includingexcavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and directed. |