| 1 | Wiring for light pt/ fan pt/ Ex-fan pt/ call bell point with 1.5 sq mm FRLSPVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit , with modular switch, modular plate suitable size GI box and earthing the point with 1.5 sq mm FRLSPVC insulated copper conductor single core cableas required (Group- B). |
| 2 | Rewiring for light pt/ fan pt/ Ex-fan pt/ call bell point with 1.5 sq mm FRLSPVC insulated copper conductor single core cable in existing surface / recessed Steel/ PVC conduit , and earthing the point with 1.5 sq mm FRLSPVC insulated copper conductor single core cableincluding dismanteling as required (Group- B). |
| 3 | supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box / wooden block including connection etc as required. |
| 4 | Wiring for circuit/sub main wiring along with earth wire with the 2x1.5 sq mm + 1x1.5 sq mm earth wire size of PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. |
| 5 | Wiring for circuit / sub main wiring along with earth wire with the following sizeof FRLSPVC insulated copper conductor, single core cable in surface / recessed medium class PVCconduitas required. 2x4 Sq mm + 1x4 Sq mm earth wire. |
| 6 | S/F suitable size GI box with modular plate and cover in front on surface or in recess , including P/F 6 pin 5/6 & 15/16 amps modular socket out let and 15/16 amps modular switch ,connections Etc. as required. |
| 7 | Supplying and fixing 20 amps , 240V, SPN industrial type socket outlet with 2 pole and earth metal enclosed plug top alongwith 20 amps \"C\" curve SP MCB in sheet steel enclosure on surface or in recess metal cover for the socket outlet and complete with connection testing and commissioning etc as reqd . |
| 8 | Supplying and fixing 8 Way double door Single pole and neutral sheet steel MCB DB 240 Volts on surface/recess complete with tinned copper bus bar, neutral bus bar , earth bar , din bar, interconnection, powder painted including earthing etc as required. ( But without MCB / RCCB / ISOLATOR ) . |
| 9 | Supplying and fixing 6 Way Double door Single pole and neutral sheet steel MCB DB 240 Volts on surface/recess complete with tinned copper bus bar, neutral bus bar , earth bar , din bar, interconnection, powder painted including earthing etc as required. ( But without MCB / RCCB / ISOLATOR ) . |
| 10 | S/F 5 Amp to 32 Amp rating , 240/415 VOLTS \" C \" curve , MCB suitable for inductive load of single poles in the existing MCB DB complete with connection , testing and commissioning etc as reqd . |
| 11 | S/F 63 Amp rating , double pole 240 V, Isolator in the existing MCB DB complete with connection , testing and commissioning etc as reqd . |
| 12 | Earthing with GI earth pipe 4.5mtr long , 40mm dia including accessories and providing masonary enclosure with cover plate having locking arrangements and watering pipe etc.with charcoal / coke and salt as reqd. |
| 13 | Providing and laying earth connection from eath electrode with6 SWG dia GI wire in 15 mm dia GI pipe from earth electrode i/c connection with GI thimble excavation and re- filling as required . |
| 14 | SupplyingInstallation, testing and commissioning of20 watts LED batten 4\" long, basic all purpose surface and wall mounted LED batten with polycorbonate housing & integrated electronic driver complete with all accessories i.e connection etc. as required. Make : Phillips/ Crompton / Havells / Bajaj / Syska. |
| 15 | SupplyingInstallation, testing and commissioning of 10 W LED bulk head, IP 66, 240 V, 50 HZ designed with beautiful aesthetics using new generation technology in LED to enliven your outdoor and indoor areas in perfect synchronization with functionality and aesthetics. Family of bulkhead Lights designed to complement the geometry of the area with modern design complete with all accessories i.e ready to use directly on ceiling / wall, including connection with 3 x 1.5 sq.mm, FRLS PVC insulated copper conductor, single core cable and earthing etc. as required. Make : Phillips/ Crompton/ Bajaj/ Havells /Syska. |
| 16 | Providing and fixing of300 mm exhaust fan, heavy duty, metal body suitable for single phase, with louver shutterin the existing opening, including connection, making good the damage etc. as required making make - Havells/ Crompton/ Usha / Bajaj/ Orient. |
| 17 | Providing and fixing of 20 Wattthree color CCT change with the help of a simple toggle switch2 feet LED batten6500 k, mirror light suitable for surface wall , including connections, testing complete etc. as required.make Bajaj/ Philips/Crompton / Havells / Syska etc as required. |
| 18 | Supply installation testing and cmmissioning of 45 W LED street light fitting at 230 V , 50 HZ AC with high power LED , Pressure die cast aluminium IP66 protection along with electronic driver with 1.5 sq mm copper wire etc as reqd . MakeBajaj and equebalent make Havells / Philips/Crompton / Syska etc as required. |
| 19 | Supplying and fixing 25 Ltrs Capacity, 2 KW power saving water heater (Gyser), on the existing wall including hose pipe with nuts &rubber washers and making connections etc. as required, make of Havells/ Usha/ Crompton/ Bajaj. |
| 20 | Suppying and fixing 3 mm thick phenolic laminated sheet cover in front of MS switch box i/c making hole and metal screw etc. as required. |