| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group-B |
| 2 | Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 3 | Supply, installation, testing and commissioning of 10 WattWatt mountedLED Bulkhead luminairecomplete with all accessories and electronic driver, directly on ceiling / wall, including connections etc. as required. Make havells/Crompton/ Syska/Surya |
| 4 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator)4 way , Double door |
| 5 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator)6 way , Double door |
| 6 | Providing and fixing 25 mm X 3 mm copper strip on surface or in recess for connections etc. as required. |
| 7 | Supplying and laying 5 core 10.0 sqmmunarmouredcopper cable in 25 mm medium classPVC pipeon surface etc as requiredmake KEI/Havells/ RR kable |
| 8 | Supplying and laying 3 core 6.0 sqmmunarmouredcopper cable in 25 mm medium classPVC pipeon surface etc as requiredmake KEI/Havells/ RR kable |
| 9 | SITC of otdoor typecubical joint box made of 2mm thick CRCA sheet of size not less than 760(w) x 750 (h) x 400(d) MM suitable for 415 Volt, 3 phase 50 hz power supply complete with hinged doors, having locking arrangement and providing detachable gland plate of thickness 3mm at the bottom, earth bar/ stud, cable alley, Aluminium busbar of suitable size as per CPWD norms as required.. All sheet metal parts separately chemically treated with 7 tank treatment process and the panel shall be finished with powder coating in Siemens Grey shade RAL 7032 and supplied with suitable pedastal of 50mm x 50 mm x 5 mm angle iron frame with 4 Nos 600mm long legs with suitable apron all around. The Panel Shall beembeded in 1:3:6 cement concrete foundation of required shape and size 30 cms below ground levelincluding finishing etc as required as per direction of engg-in-charge. (Make of panel - CPRI approved only) (Drawing will be approved from department before fabrication)The provision of following switchgear should be incorporated in panel (a) Incommer= (i) 125 Amp 4 Pole MCCB-01 No |
| 10 | Supply installation testing and commissioning of 125A, 36kA breaking capacity Four Pole MCCB having Ics = 100%Icu with thermal magnetic based releases,interconnections with suitable size aluminium bus bar, suitable size spreader link assembly etc complete as required as per direction of enggineer-in-charge. make : Legrand/ Schnieder / Siemens/ABB/L&T |
| 11 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\"curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required.Single pole |
| 12 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\"curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required.Double pole |
| 13 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\"curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required.Triple pole and neutral |
| 14 | Supplying and fixing single pole blanking plate in the existingMCB DB complete etc. as required. |
| 15 | Providing and fixing 01 meter, 25 mm X 3 mm copper strip on surface including with making 10 Nos 12 mm drill holes on stripand02 Nos PVC saddles etc.as required. |