| 1 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 2 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 3 | Supplying and laying of 63 mm dia (OD-63 mm & ID-51 mm nominal) sizeDWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required |
| 4 | Supplying & installation of 7 mtr longG I Octagonal Pole Fabricated Part as per Dimension :- Top Dia-70 mm , Bottom Dia-130 mm ( section Length -7000 mm) Thickness -3 mm Base Plate -220 mm X 220 mm X 12 mm , Foundation Bolt -M20mm X 700 mm x 4 nos \" J \" Type bolt including construction of RCC foundation base 1:3:6 ( 1 Cement : 3 coarse sand : 6Graded Stone) aggregate 40 MM Nominal Size ( minimum CC volume 0.66 cum, reinforcement weight 20 KG). MakeNezone /Jindal/ TATA/ Bansal/ Hindustan |
| 5 | Supplying & fixing of 150 watt LED flood fitting high purity integrated IP66 lens diffuser lumaire with aluminium Die Cast housing having high efficiency & better thermal management with high energy saving ,efficiency 120 Lm/watt on existing pole, including wiring with 3 x 2.5 Sqmm (from looping box to LED fitting), PVC insulated & PVC sheathed multi core, copper condoctor cable & making connection of LED flood light fitting etc. as required of makeWipro Vega/ LF40Cat part No. LF40-192-060-57-HE or equivalent/ higher specification of Havells/Philips/Crompton including 5KV internal & 10 KV external SPD system. (Fittings will be warranted for 5 years from the date of installation neccessary certificate in this regard will be provided by the contractor through authorized dealer / stockist from whom it was procured) |
| 6 | Supplying and fixinglighting bracket made of 1.2 mtr long MS channel of size 75mmx40mm( type SMC 75 ) welded with 80 mm dia, 30 cm long B class MS pipe and having suitable size holes at suitable places on the top of bracket for fixing 04 Nos 150 watt LED flood light ( taken at item at Srl No. 11 of this schedule), on GI octagonalpole etc. as required i/c primer and painting of bracket etc as required as per the direction of engineer in charge |
| 7 | Supplying and Laying of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 kv grade of following sizein the existingmetal pipe/ open as required. Conf. to IS:7098 part - I of make Havells / Polycab / Plaza / Kalinga /KEI etc. a) 4 X 16 sqmm |
| 8 | b)3.5 X 25 sqmm |
| 9 | c)3.5 X 70 sqmm |
| 10 | Supplying & fixing ofGate light in aluminum die cast with modern artistic design and white PC diffuser suitable with LED lampetc. as required including making connection etc. as required . , including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc as required CROMPTON /PHILIPS/HAVELLS /WIPRO / BAJAJ |
| 11 | S/ITC of outdoor type feeder piller, Single door made out of 18 SWG CRCA sheet of size 450 mm x 300 mm x 300 mm deep having 160 amps, 04 nos insulated aluminium bus bars and to accommodate following accessories, front door openable & angle iron frame of size 450 mm x 300 mm with 600 mm long legs made out of 40 mm x 40 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, arrangement for incoming / outgoing cabling / cable termination, earthing, locking, interconnection etc. as required. |
| 12 | S/ITC of outdoor type feeder piller, double door made out of 16 SWG CRCA sheet of size 1600 mm x 1500 mm x 350 mm deep having 200 amps, 04 nos insulated aluminium bus bars and to accommodate following accessories, front & back door openable and P & F of internal connection with suitable size of cu wires,& angle iron frame of size 1600 mm x 350 mm with 600 mm long legs made out of 50 mm x 50 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, arrangement for incoming / outgoing cabling / cable termination, earthing, locking, interconnection etc. as required including providing and fixing following switch gears and accessories. (i) 160 Amps, 4 pole, 415 volts, 50 Hz SDFU make L&T code SK95570 = 02, (ii) 63 Amps, 4 pole, 415 volts, 50 Hz SDFU make L&T code L&T cat. No. SK95651 = 04 Nos, (iii) 160 Amp change over switch disconnector type- C01-100 manual open executed make L& Tpart No.CO21600OOOO = 01 No, (iv) MCB [8536] 10KAC Curve SP 63 Amp C curve, 240 V, 50 Hz make L&T BB10630C = 04 Nos, (v) RYB LED indicator 415V make L&T=03 Nos |
| 13 | Add GST @18% on DSR\"22 instead of 12% ( Multiplication Factor = 0.0633 on total of item Srl No. 01 to 03 ) |
| 14 | Add 1% Labour Cess |