Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 20-09-2024 | Date | Date | 23-10-2024 |
| Sl. No. | Item Description |
| 1 | (A) ELECTRIFICATION WORKS Dismentling / disconnection and taking down old unserviceable LT control panel board outdoor type of any size with bus bar any capacity and deposited to MES store yard and taken on charge in salvage ledger complete all as specified and directed by Engr-in-charge(Note : (i) Earth work excavation will be measured and paid seperately under relevant items.(ii) All old unserviceable LT panel board & UG Cables shall be taken on charge and enter in demolition / salvage register in \"KG\" and attach the same page of salvage register with each RAR. If any serviceable cable obtained from the trench the same will be reused under respective items of BOQ.(iii) Transportation cost of LT panel & LT UG Cables, channels & angles etc from site to storeyard of AGE (U) W/S-III will be treated included in quoted unit rate.(iv) Old u/s angle iron posts & channels will be dismentled safely and deposites in storeyard under salvage / demolition ledger in \"KG\" and RV attached with each RAR. |
| 2 | Supply installation, commissioning and testing of LT panel board, outdoor type, floor mounted, dust and vermin proof, CPRI approved factory made , fabricated out of 3.15 mm thick CRCA sheet suitable for accommodate the following accessories and for 3 phase 415 volts 50 Hz, AC supply, bus bar chamber with aluminium bus bar of 800 Amp rating for 3 phase and 4 wire system duly insulated with heat shrinkable sleeved as per colour code, supported on epoxy insulators-01 set common earth bus bar of suitable size at bottom in side panel board with two earth terminals out side panel board, cable alley, cable glands with independent plates at bottom and pron for ventilation, angle iron frame of four legs of 50x50x6mm thick angle iron, 2 ft long grouted on PCC foundation of height not less than 30 cm from the ground level, grouting properly and of suitable size to accommodate the items mentioned belowand having seperate compartment /chambers for cable gallery busbar, switch gear etc complete panel board painted with powder coating in siemens grey colour including providing danger notice plate with marking of skull & bones by efflorescent paint etc complete all as specified and directed approved & comprising as under:- |
| 3 | Incomingi)MCCB TPN, 600A, , breaking capacity 50 KA-01 NosOut Goingi)MCCB TP, 400A, , breaking capacity 50 KA-02 Nosii) Digital type voltmeter (0-500 Volts) -01 Noiii)Copper wound CTs with CTR 30/5-(Set of 3)-01 setiv) Indicator Lamps(LED type) for motor ON/OFF indication-01 set(Note:- (i) Contractor will submit drawings of LT Panel of approved make to EIC for approval of GE(ii) Excavation and earth work shall be measured and paid seprately under respective items.(iii) Make of MCCB shall be of same make as per CA. |
| 4 | Supply installation, commissioning and testing LT panel board, outdoor type, floor mounted, dust and vermin proof, CPRI approved factory made , fabricated out of 3.15 mm thick CRCA sheet suitable for accommodate the following accessories and for 3 phase 415 volts 50 Hz, AC supply, bus bar chamber with aluminium bus bar of 600 amp rating for 3 phase and 4 wire system duly insulated with heat shrinkable sleeved as per colour code, supported on epoxy insulators-01 set common earth bus bar of suitable size at bottom in side panel board with two earth terminals out side panel board, cable alley, cable glands with independent plates at bottom and provn of ventilation angle iron frame of four legs of 50x50x6mm thick angle iron, 2 ft long grouted on PCC foundation of height not less than 30 cm from the ground level, grouting properly and of suitable size to accommodate the items mentioned belowand having seperate compartment /chambers for cable gallery busbar, switch gear etc and complete panel board painted with powder coating in siemens grey colour complete all as specified and directed approved & comprising as under:- |
| 5 | Incomingi)MCCB TPN, 400 Amps, breaking capacity 50 KA-01 NoOut Goingi) MCCB TP 160 Amps,breaking capacity 25 KA :- 03 Nosii) Digital type voltmeter (0-500 Volts) -01 Noiii) Copper wound CTs with CTR 30/5-(Set of 3)-01 setiv) Indicator Lamps(LED type) for motor ON/OFF indication-01 set(Note:- (i) Contractor will submit drawings of LT Panel of approved make to EIC for approval of GE(ii) Excavation and earth work shall be measured and paid seprately under respective items.(iii) Make of MCCB shall be of same make as per CA. |
| 6 | Supply and fixing in replacement, installation, testing and commissioning of feeder pillar box ,outdoor type cubical shape,three phase, 4 wire, Al bus bar for phases and neutral made out of CRCA sheet 3.15 mm thick, factory fabricated, CPRI approved, powder coated, dust and vermin proof, provn for ventilation, angle iron frame of four legs of 50x50x6mm thick angle iron, 2 ft long grouted on PCC foundation of height not less than 30 cm from the ground level, grouting properly and of suitable size to accommodate the items mentioned belowand having separate compartment /chambers for cable gallery busbar, switch gear etc complete all as specified and comprising of following including necessary cable connections to the MCCBs, voltmeter, Ammeter and cable lugs etc and complete panel board painted with powdercoating in siemens grey colour including providing danger notice plate with marking of skull & bones by efflorescent paint etc complete all as specified and directed approved & comprising as under:- |
| 7 | (a) Aluminiumbus bar with PVC sleeve suitable for 200 amps for Phase & 200 Amp for Neutral- 01Set.(b) Voltmeter,digital type 0- 500 volt,with selector switch - 01 set (c) Ammeter Digital type 0-100Amps, with selector switch and CT\"-1set(d) Phase indicating lamps LED type ( Red , Yellow, Blue) 01 set(e) Incoming : MCCB100 Amp 3 pole 25 KA with adjustable thermal and fixed magnetic release -01 No(f) Outgoing : MCCB63 Amp 3 pole 16 KA with adjustable thermal and fixed magnetic release -02 Nos(g) FASD StarterML 1.5 FASD with MS sheet enclosure-01 No(h) Analog time switch -01 No (j) Single phase preventer-01 No(k) Phase sequence corrector for complete three phase system - 01 Set(Note:- (i) Contractor will submit drawings of LT Panel of approved make to EIC for approval of GE(ii) Excavation and earth work shall be measured and paid seprately under respective items.(iii) Make of MCCB shall be of same make as per CA. |
| 8 | S&F in replacement 3 pole power contactor ML-12, 300 Amps coil voltage 415 volts, 50 HZcomplete all as specified and as directed. |
| 9 | S&F in replacement 3 pole power contactor ML-6, 110 Amps coil voltage 415 volts, 50 HZcomplete all as specified and as directed. |
| 10 | S&F in replacement 3 pole power contactor ML-4, 70 Amps coil voltage 415 volts, 50 HZcomplete all as specified and as directed. |
| 11 | S&F in replacement 3 pole power contactor ML-3, 40 Amps coil voltage 415 volts, 50 HZcomplete all as specified and as directed. |
| 12 | S&F in replacement 3 pole power contactor ML-1.5, 25 Amps coil voltage 415 volts, 50 HZcomplete all as specified and as directed.(Note for ser item No 5 to 9 :- Old U/s material power contactor obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV Iron Scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 13 | Supply and fixing in replacement of star delta starter type ML-1.5/MN complete all as specified and as directed. |
| 14 | Supply and fixing in replacement of star delta starter type ML-2/MN complete all as specified and as directed (Note for ser item No 10 to 11 :- Old U/s material star delta starter obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV Iron Scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 15 | Supply and fixingof Post Top pole light fittingLED Type of size 1x45 watt with IP 65 protection,Resistant to impact and corrosion, moon light effect and eficient light distrbution complete with including GI pipe bracket made out of GI pipe 1.5m long of 40mm dia light grade including flat iron 50x3mm clamps etc with all fitting & fixtures etc and taking down of existing light fittings from site and deposited to store complete all as specified and as directed.(Note :- Old U/s material light fitting obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV Iron Scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 16 | S&F MCB single pole 5 to 32 Amps,240V,10 KA, rating with thermal magnetic protection unit in replacement complete all as specified and as directed.(Note :- Old U/s material MCB obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV Iron Scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 17 | S&F of LT Junction box for street lights, Sheet Moulding Compound (SMC), hinged door type and locking arrangenment, off white colour of size 139 x 119 x 70 mm (internal dimension) comprising of 02 Nos aluminium busbar of adequate capacity including suitable size MS clamps and taking down of exisiting unserviceable junction box complete all as specified and as directed.(Note :- Old U/s material obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 18 | M&LPCC 1:4:8 type D2 using 40mm graded crushed stone aggregate as in foundation complete all as specified and as directed. |
| 19 | M&LPCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate as in copings including use and waste of from work complete all as specified and as directed. |
| 20 | Supply and fixing of LED flood light 70 watt 230 volts AC outdoor type in replacement of with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant with driver and lamp complete all as specified and directed.(Note :- Old U/s material flood light obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV Iron Scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 21 | Supply and fixing LED flood light 120 watt 230 volts AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant with driver and lamp complete all as specified and directed.(Note :- Old U/s material flood light obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV Iron Scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 22 | S&F LED tube light fittings with single tube mounting box type suitable for 1x20 watt complete prewired with 3 mtr flexible wire including taking out unserviceable tube light fittings and depositing to MES store yard complete all as specified and directed by Engineer-in-charge.(Note :- Old U/s material light fitting obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV Iron Scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 23 | (B) EXTERNAL WATER SUPPLY WORKSSupply only MS Pipe heavy duty Class \"C\" of following bores and confirming to lS 3589 including taking down of existing pipe and rubber or fibre board gasket complete all as specified and directed by Engr-in -charge.(a) 200 mm bore |
| 24 | (b) 250 mm bore |
| 25 | (c) 300 mm bore |
| 26 | (d) 600 mm bore |
| 27 | (e) 900 mm bore |
| 28 | Supply only nut bolts and washers of suitable sizeas per site requirement used for fixing of MS Pipe etc including taking out of old unserviceable nut & bolts, washers for depositing in MES store yard complete all as specified and directed.(Note :- Old U/s material nut, bolts & washers obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 29 | M&L for making of MS Pipe header 900 mm dia with reducer 600 mm dia (MS pipe 900mn dia, 600mm dia, 300mm dia, 250mm dia and 200mm dia shall be measured and paid seperately under ser item No 20, 20.01 to 20.04 aboves) arrangement all as required at site including cutting , welding and finishingof pipe in pieces of 3 mtr each with flanged ends closed with dead plate not less than 20mm thickincluding provision of following incoming & outgoing connection of MS pipe suction and delivery pipe lines and applying two coats of rust proof synthetic enamel paint over one coat of red oxide primer and all T & P like JCB & Hydra and highly skilled trademan required at site to fix the header over brick work plateform of required height with PCC bed block made in PCC (1:2:4) type B-I using 20mm graded crushed stone aggregate complete all as specified and directed by Engineer-in-Charge and taking out oldrusted MS header 900 mm bore including flange & fittings etc with reducer 600mm dia and depositing to MES store yard and taken on charge in salvage ledger :- (Location : Nodal Point-I Pump House) |
| 30 | (a) MS pipe class \"C\" heavy duty 300mm dia as incoming of length 450mm: 04 Nos(b) MS pipe class \"C\" heavy duty 250mm dia as outgoing of length 450mm : 14 Nos(c) M.S flange 300 mm bore 8 mm thick : 10 Nos(d) M.S flange 250 mm bore 8 mm thick : 06 Nos(e) M.S flange 200mm bore 8 mm thick : 03 Nos(f) M.S flange 600 mm bore 15 mm thick : 01No(g) M.S flange 900 mm bore 15 mm thick : 10 Nos(h) Dummy plate of size 900 mm dia , 20mm thick-02 Nos(j) Sockets / bends of required dia as per site complete all as specified and directed.(Note:- (i) Excavation and earth work shall be measured and paid seprately under respective items.(ii) Old U/s material header 900mm dia main pipe with all connected pipes and reducers with flanges / bends with fitting obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in weight (KG) shall be taken into account and attach with RAR/F Bill.(iii) Transporation cost of header upto storeyard / work shop shall be included in quoted unit rate.(iv) Cost of opening of old unserviceable sluice valve, NRV and butterfly valve not included in quoted unit rate. New valves shall be measured and paid seperately. |
| 31 | Supply, fixing, in replacement of cast Iron Sluice Valve 600 mm dia class-1, ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body,Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete with nuts, bolts, washers and rubber gasket including jointing and testing complete all as specified and directed.(Note:- Old U/s material sluice valve obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in number (EACH) shall be taken into account and attach with RAR/F Bill). |
| 32 | Supply, fixing, in replacement of cast Iron butter fly Valve 600 mm dia class-1, ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body,Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete with nuts, bolts, washers and rubber gasket including jointing and testing complete all as specified and directed.(Note:- Old U/s material butter fly valve obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in number (EACH) shall be taken into account and attach with RAR/F Bill). |
| 33 | Supply, fixing, in replacement of cast Iron non return valve of size 300mm bore with GM sheet PN 1.0 ISI Marked including flanged joints complete all as specified and directed.(Note:- Old U/s material non return valve obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in number (EACH) shall be taken into account and attach with RAR/F Bill). |
| 34 | M&L Painting of LT Panel after complete removing of old paint by painted surfaces by removers or burning off blow lamps and cleaning with scrapers, any number of coats, any width or girth from the existing MS Base frame ofCentrifugal Motor and Pumps of Cap of 15 HP to upto 40 HP and Painting of LT Panel by applying two coat of syenthetic enamel paint over a coat of red oxide primer including spot welding on rusted portion of steel surface complete all as specified and directed |
| 35 | Excvation in trenches not exc. 1.5 mtr wideand not exc 1.5 mtr deep for pipe line in soft/loose soil, getting out and levelling of bottom surface as required complete all as specified and as directed. |
| 36 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick complete all as specified and as directed. |
| 37 | Removing excavated material to a distance not exc 50 m and depositing where directed not exc 1.5 meters above the starting point complete all as specified and as directed. |
| 38 | Supply & laying cable LT XLPEinsultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade including providing CI route indicator of following size including taking down the cable existing from site and providing route indicator complete all as specified and directed:-(Note:- (i) Excavation and earth work shall be measured and paid seprately under respective items.(ii) Old U/s material cable obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of aluminium scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) (a) 25 sqmm 3 1/2 core |
| 39 | (b) 35 sqmm 3 1/3 core |
| 40 | (c) 50 sqmm 3 1/2 core |
| 41 | (d) 120 sqmm 3 1/2 core |
| 42 | S&F in replacement HDPE DWC pipe of size 55 mm outer dia including fittings lead in trenches / walls /roof complete all as specified and directed |
| 43 | S & F in replacement HDPE DWC pipe of size 110 mm outer dia including fittings lead in trenches / walls /roof complete all as specified and directed.(Note for ser item no 31 & 32 :- (i) Excavation and earth work shall be measured and paid seprately under respective items.(ii) Old U/s material HDPE DWC pipe obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of PVC scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 44 | M&L earthing complete with galvanised steel earth plate electrode 60x60 cmx 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below nominal ground level) with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanised iron strip 32x6 mm as earthing lead by mean of bolts, nuts, check nuts and washer of galvanised iron or steel all as shown in Electrical plate No-3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed.(Note:- (i) GI strip 32x6 mm upto 7.5 RM shall be included in quoted unit rate and if extra required the same shall be measured and paid seperately under respective items.(ii) Excavation and earth work shall be measured and paid seprately under respective items.(iii) Old U/s material steel plate & GI strip obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 45 | S&F GI Strip 32 x 6 mm earth continuty (measured beyond 7.5 Rm length from earth test pits) including necessary connection, nuts, bolts, washers complete all as specified and directed |
| 46 | (C) FIRE FIGHTING WORKSupply and fixing in replacement cotton synthentic fabric circular woven jacketted rubberised fabric fire hose RRL 15 Mtrs long with coupling stainless Steel 63 mm size male and female instantenous type complete all as specified and directed.(Note:- Old U/s material obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 47 | Supply and fixing in replacement instaneous type copper alloy (gun metal) branch pipe 63 mm dia of suitable length fitted with 16 mm dia nozzle complete all as specified and directed |
| 48 | Supply and fixing in replacement water delivery Thermoplastic rubber (first aid hose) as per IS 12585, 25 mm dia 30 mtr length to with stand 10 kg per Sqcm working pressure fitted with gunmetal nozzle and shut off valve complete all as specified and directed |
| 49 | Supply, fixing, jointing and testing in replacement of Bourdon type pressure gauge with gun metal Isolation cock and copper ‘U’ Tube.having calibration of 0-14 Kg/cm2 and 100 mm dial including taking out unserviceable pressure gauge complete all as specified and directed |
| 50 | Supply and fixing in replacement Fire hose real drum suitable for 20 mm dia rubber hose pipe upto 30 mtr length complete all as specified and directed. |
| 51 | Supply & Fixingin replacement nozzle 20 mm dia gun metal with shut off valve suitable for rubber hose complete all as specified and directed |
| 52 | Supply and fixing in replacementmanual call point break glass type enclosed in aluminium cast alloy body of 3 mm thickness complete with chain and harmer and incl inscriber in case of fired break glass complete all as specified and directed |
| 53 | Supply and fixing in replacement Single outlet 63mm dia stainless steel hydrant landing valve type \"A\" (single head outlet)with coupling and chain confirming to IS 5290 complete with nuts, bolts, washers and rubber gasket etc complete all as specified and directed.(Note for ser item No 36 to 42 :- Old U/s material obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 54 | Supply and fixing in replacement air cushion tank with air relief valve 200mm made out of 6 mm thick MS sheet of suitable size complete with 25 mm dia gun metal gate valve and 20 mm dia GI drain pipe one meter long with 20 mm dia gate valve with necessary MS clamps etc including painting with two coat of syenthetic enamel paint and taking out old/UNSV items and depositing to MES store yard complete all as per specified and directed.(Note:- Old U/s material tank obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 55 | Supplying &fixing in replacement gun metal gate valves with iron wheel head,screwed both ends for iron pipe, ISI Marked, as per IS: 778of sizes 25 mm dia complete all as specified and directed.(Note:- Old U/s material gate valve obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 56 | Supply and fixing in replacement 2 way fire brigade hydrant including nuts, bolts, washer and rubber flanges etccomplete all as specified and directed.(Note:- Old U/s material hydrant obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of in weight (EACH) shall be taken into account and attach with RAR/F Bill) |
| 57 | Supply and fixing in replacment weather proof standerd fire hose box made out of 18 SWG gauge MS sheet of MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard for external use alongwith door opening and lock including painting with two coat of syenthetic enamel paint over a coat of red oxide primer complete all as specified and directed.(Note:- Old U/s material fire hose box obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 58 | Supply and fixing fire hydrant post/stand post made out of 80 mm dia MS Pipe heavy duty class \"C\" both ends flanged 1.5 mtr height including taking down post complete all as specified and directed.(Note:- Old U/s material obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 59 | Supply, fixing, in replacement cast Iron Sluice Valve 100 mm dia class-1, ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body,Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete with nuts, bolts, washers and rubber gasket including jointing and testing complete all as specified and directed |
| 60 | Supply, fixing, in replacement cast Iron Sluice Valve 150 mm dia class-1, ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body,Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete with nuts, bolts, washers and rubber gasket including jointing and testing complete all as specified and directed.(Note for ser item No 48 & 49:- Old U/s material sluice valve obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of in number (EACH) shall be taken into account and attach with RAR/F Bill) |
| 61 | Material and labour for copper/aluminium point wiring (light, fan, bell, independent or power) including complete fittings such as switches, ceiling roses, pendents, regulators, sockets etc and making good disturbed surfaces of wall, floor & ceiling etc. 1.5 Sqmm FRLS type PVC insulated and sheathed cable with copper conductor 1100 Volts grade, multistranded alongwith earth wire 1.5sqmm PVC insulated and sheathed copper wire FRLS type in 25mm dia PVC conduits with PVC fittings such as tee, bend & socket etc including M.S. sunken box dolly earth connected including taking down worn out wires etc complete all as specified and directed.(Note:- Old U/s material point wiring obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of point wiring including fittings in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 62 | Supply and fixing in replacement electrically operated Electronic syren of suitable size painted with two coat of syethetic enamel paint over a coat of red oxide primer complete with suitable transformer complete all as specified and directed.(Note:- Old U/s material obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 63 | Supply and fixing in replacement electrically operated Electronic Hooterenclosed in MS enclosures of suitable size painted with two coat of syenthetic enamaled paint red coloured over a coat of red oxide primer complete with suitable transformer complete all as specified and directed.(Note:- Old U/s material obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 64 | M&L prepration of painting to existing steel surface for fire cabinet box with one coat primer and two coat of synthetic enamel paint including scratching old paint complete all as specified and directed |
| 65 | M&L welding work for existing door, hinges, handels and locking arrangement complete all as specified and directed (Note:- Each butt weld not exe 2cm shall be measured and paid as one unit.) |
| 66 | M&L fire glass including writing work on glassas word fire complete all as specified and directed. |
| 67 | Supply and fixing in replacement MS Pipe heavy duty class C of size 100 mm boreheavy grade including necessary nut and bolts with washers required at site condition complete all as specified and directed. |
| 68 | Supply and laying in replacement of MS Pipes \"Heavy grade\" class \"C\" with all fittings as required at site laid in floors or fixed to walls and ceilings including welding as required at site and removing old rusted pipe of size 150mm bore complete all as specified and directed.(Note for ser item No 56 to 57:- Old U/s material MS pipe obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |
| 69 | Supply and fixing in replacement flanges duly welded on ends of MS pipe, flange size not less than 20 mm thick incl nuts and bolts and washer etc reqd at site complete all as specified and directed of following sizes:-(a) 100 mm bore |
| 70 | (b) 150 mm bore |
| 71 | Supply and fixing in replacement MCCB TPN 400 Amp thermal release range with adjustable setting breaking capacity 36KA complete all as specified and directed |
| 72 | Supply and fixing in replacement MCCB TP 200 Amp thermal release range with adjustable setting breaking capacity 36KAcomplete all as specified and directed. |
| 73 | Supply and fixing in replacement MCCB TPN 160 Amp thermal release range with adjustable setting breaking capacity 36 KAcomplete all as specified and directed.(Note for ser item No 59 to 61:- Old U/s material MCCB obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill) |