| 2 | RAW JUICE PUMP VFD PANEL (90KW HEAVY DUTY) with juice stabilization:Application- Raw JuiceWith complete Panel as per attached specificationsInstallation & Commissioning of Panel, VFD Model:ACS880-01-246A-3+P944Including Automatic Control of RPM according to the loadAnd complete interlocking with Inter Rack Carriers & MillComplete system should be communicate with existingACFC PLC System.1 MAIN INCOMER , 1. MCCB Microprocessor based 315A 1, 2. SEMICONDUCTOR FUSE 315A 3, 3. HRC FUSE 2A WITH BASE 3, 4. PHASE INDICATION 230VAC1, 5. VOLTMETER 0 - 500V AC 1, 6. VOLTAGE SELECTOR SWITCH1, 7. DOOR LIMIT SWITCH 1, 8. PANEL LAMP 1, 9. THERMOSTATE 1, 10. SPACE HEATER1, 11. MCB 10A, DP FOR CONTROL 2, 12. CONTROL TRANSFORMER 500VA, 415V/0..240V AC 1, 13. ACS880-01-246A-3+P944-ABB make 1, 14. AUX. CONTACTOR6, 15. READY/RUN/TRIP 3, 16. START/STOP/SPEED INC./DECPUSH BUTTON 417 LOCAL/REMOTE SWITCH 1, 18. EMG. STOP PB 1, 19. SIGNAL ISOLATOR DUEL CHANNEL 2, 20. SIGNAL ISOLATOR SINGLE CHANNEL 1, 21. CONTROL TERMINAL 50, 22. PLC System-ABB Make for Close loop control including supply of JUICE TANK LEVEL(Hydrostatic Type 3 Inch –Emerson)&Interlocking with ACFC ,Raw Juice Flow Meter , PLC Controller –PM564 & IO Cards (8AI, 8AO,8DI,8DO ETH ,RS485 Modbus), PANEL PLC System shall be communicate with Exiting PLC System, Including 7 inch Touch Panel with eth-ABB Make, Complete Programming modification if required of existing system shall be in vendor scope. 1Set, 23. POWER TERMINAL 32. PANELLING , 1. PANEL 800x2000x600 (or Suitable dimention) 1, 2. WIRING & ACCESSORIES 1, 3. BUSBAR Cu 1 |