| 1 | xx |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell pointwith 1.5 sq.mm FRLS PVC insulated copper conductor singlecore cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthingthe point with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable etc. as required.Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit as required. Make-L&T/Finolex/Polycab2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 4 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | 2 X6sq. mm + 1 X 6 sq. mm earth wire |
| 6 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 7 | 4 X 10sq. mm + 2 X 6 sq. mm earth wire |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 10 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 11 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 12 | Double Pole32/40 A MCB |
| 13 | FP MCB 63 A Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 14 | 2 /4Way Enclosure Metal Box |
| 15 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)8 way (4 + 24), Double door |
| 16 | Supplying, installing, testing and commissioning of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains complete with TPN disconnector FSU and HRC fuses, connections, earthing etc. as required.100 A TPN |
| 17 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 18 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metrebelow ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of brassnut bolt & spring washer spaced at 50mm) |
| 19 | Supplying ,fixing Connecting & Testing ,20W LED batten Make-Philipse/Syska/Wipro/CG |
| 20 | Supplying and fixing of 230VAC 1Ph. 1400mm dia Ceiling Fan (High Speed).(Make: Usha / Crompton / Bajaj ) |
| 21 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required |
| 22 | Supplying,Cutting of huck , painting and fixing ofMS Down down conduit forinstallation of ceiling fan upto 5 to 8 feet |
| 23 | Supply & Installation of 36 W 2X2 pure LEDfalse ceiling Surface LightMake-Phillipse/Wipro/CG/Polycab |
| 24 | Supplying and fixing of 230VAC 1Ph.450 mm ,900 rpm Wall Fan Make-ORIENT/CG/USHA/Bajaj |
| 25 | Supplying and fixing of 230VAC 1Ph. 450 mm exhaust Fanwith sweep feature. ( Make: Usha / ORIENT / CG) |