| 1 | Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete including all fittings and fixtures such as switches, pendant, lamp holder, socket outlet, etc and removing unserviceable materials from site of work and making good disturbed surfaces of walls, floors with cement mortar and white/colour wash to match with existing surfaces etccomplete all as specified and as directed by the Engineer-in-Charge. |
| 2 | Material and labour for point wiring with 1.50 Sqmm single core PVC insulated , unsheathed cable FRLS-H, 1100 volt grade ISI marked with multi stranded copper conductor drawn through and including medium grade, ISI marked, PVC conduit not less than 20 mm dia with accessories, concealed on wall/ceiling surfaces and including provision of 1.50 Sqmm single core PVC insulated , unsheathed cable FRLS-H, 1100 volt grade, ISI marked with multi stranded copper conductorgreen colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including mild steel sunken box or pressed steel terminal boxes modular type of size/modules as required at site with earth dolly(boxesshall be galvanised or painted with two coats of anti corrosive paint over a coat of red oxide primer bothinternally and externally) including provision of new covered plate over sunken box for housing themodular switches , modular socket outlets,modularfan regulators etc.for one light/fan/exhaust fan/bell point controlledby one way switch,complete all as specified and as directedby Engineer-in-Charge. Note :-a) .All chases will be cut by chase cutter only b) Switch, socket outlet and fan regulators to be measured and paid forseparately . |
| 3 | Description all as per serial item No.02 here-in-before but for One 3 pin, 6 Amps, socket outlet controlled by one switch on independent board,complete all as specified and as directedby Engineer-in-Charge. |
| 4 | Description all as per serial item No.02 here-in-before but for One 3 pin 6 Amps socket outlet controlled by one switch on same board,complete all as specified and as directedby Engineer-in-Charge. |
| 5 | Description all as per serial item No.02 here-in-before but for one socket outlet 16 Amp with 2.50 sq mm PVC insulated, unsheathedcable FRLS-H, 1100 volt grade ISI marked with multi stranded copper conductor along with 2.50 sqmm PVC insulated , unsheathed cable green colour FRLS-H, 1100 volt grade, ISI marked with multi stranded copperwire as earth continuity conductor connected to common earth dolly complete all as specified and as directed by the Engineer-in-Charge. |
| 6 | Description all as per srl item No 02 here-in-before but for one socket outlet 16 Amp with 4.00 sq mm PVC insulated, unsheathedcable FRLS-H, 1100 volt grade ISI marked with multi stranded copper conductor along with 4.00 sqmm PVC insulated , unsheathed cable green colour FRLS-H, 1100 volt grade ISI marked with multi stranded copperwire as earth continuity conductor connected to common earth dolly complete all as specified and as directed by the Engineer-in-Charge. |
| 7 | Supply and fixing of modular switch 1 module, single pole, one way 6 Amps flush type, 230 voltscomplete all as specified and as directedby Engineer-in-Charge. |
| 8 | Supply and fixing of modular switch 1 module, single pole, one way 16 Amps flush type, 230 voltscomplete all as specified and as directedby Engineer-in-Charge. |
| 9 | Supplyand fixing of modular bell push 6 Amp, 1 way, 1 module, 230 volts complete all as specified and as directed by the Engineer-in-Charge. |
| 10 | Supply and fixing of modular socket outlet2/3 pin combined,6 Amp, one way, two module, 230 voltscomplete all as specified and as directedby Engineer-in-Charge. |
| 11 | Supply and fixing ofmodular socket outlet3/3 pin combined, (6pin), 6/16 Amp, one way, two module, 230 voltscomplete all as specified and as directedby Engineer-in-Charge. |
| 12 | Supplyand fixingas in repairelectronic Fan regulator modular 100 watt, 1 module, 230 volts , 50 Hz, AC supply suitable for ceiling fan any type/make/sweep complete all as specified and as directed by the Engineer-in-Charge. |
| 13 | Supply and fixing in repair calling bell ding dong 230 volt, complete all as specified and as directed by the Engineer-in-Charge. |
| 14 | Supply and fixing ceiling rose surface type 2/3 terminalpolycarbonate, isolated body complete all as specified and as directed by the Engineer-in-Charge. |
| 15 | Supply and fixing lamp holder, PVC/polycarbonate type with back plate suitable for batten fittings, complete all as specified and as directedby Engineer-in-Charge. |
| 16 | Supplyand fixingin replacement LED lamp 9 wattthreaded/pin end, warm/cool lamp type as per site requirement suitable for fixing on existing batten/angular holderscompleteall as specified and as directed by the Engineer-in-Charge. |
| 17 | Supply and fixing in replacement LED lamp 12 wattthreaded/pin end, warm/cool lamp type as per site requirement suitable for fixing on existing batten/angular holderscompleteall as specified and as directed by the Engineer-in-Charge. |
| 18 | Supply and fixing in repairLED batten fitting 10-12 watt, 2 feet, aluminium housing with electronic drivercool/warm typeindustrial model complete,connecting with copper conductor flexible cablefrom ceiling rose to connector of the light complete all as specified and as directed by the Engineer-in-Charge. Cat part No. LUMILINE+ BS10WLED865PCSS of make Havells or equivalent in make given in Appx \"B\". |
| 19 | Supply and fixing in repairLED batten fitting 18-20 watt, 4 feet, aluminium housing with electronic drivercool/warm typeindustrial model complete,connecting with copper conductor flexible cablefrom ceiling rose to connector of the light complete all as specified and as directed by the Engineer-in-Charge. Cat part No. LUMILINEPLUSNEOBS20WLED830SPCSSIND of make Havells or equivalent in make given in Appx \"B\". |
| 20 | Supply and fixing in repair, LED surface mounted bulk head luminaries 8-10 watt with min 800 lumen, industrial model, IP 65, aluminium housing, surge protection including driver and LED lamp, etc. complete with all accessories, connecting with copper conductor flexible cable from ceiling rose to connector of the light complete all as specified and as directed by the Engineer-in-Charge. Cat part No. HEXAFT10WLED857SSYMBOPC of make Havells or equivalent in Wipro/Philips/Crompton/Bajaj. |
| 21 | Supply and fixing in repair,9/12 watt LED light fitting wall mounting fixture (sketch type) including B-22 LED lamp compact and energy efficient epoxy powder coated luminaire and connecting with copper conductor flexible cablefrom ceiling rose to connector of the light complete including removing unserviceable light fittingscomplete all as specified and as directed by the Engineer-in-Charge. Cat part No. HLWB-01-B22 of make Halonix or equivalent in make given in Appx \"B\". |
| 22 | Supply and fixingrecess mounting LED 15/18 watt cool/warm type circular down lighter/ COB panelwith PVC housing, 240 volt, 50HZ, AC supplycompletewithall accessories internally pre wiredincluding connecting with 3 coreflexible copper conductor from ceiling rose to connector of the light, including disconnecting and taking down existing old unserviceable fittingcomplete all as specified and as directed by the Engr-in-charge. Cat part No.EDGEPRONEORDDLR15WLED840S of make Havells or equivalentin make given in Appx \"B\". |
| 23 | Supply and fixingrecess mounting LED 5/8 watt cool/warm typecircular down lighter/ COB panelwith PVC housing, 240 volt, 50HZ, AC supplycompletewithall accessories internally pre wiredincluding connecting with 3 coreflexible copper conductor from ceiling rose to connector of the light, including disconnecting and taking down existing old unserviceable fittingcomplete all as specified and as directed by the Engr-in-charge. Cat part No. INTEGRAHEDLR7WLED857S of make Havells or equivalentin make given in Appx \"B\". |
| 24 | Supply and fixing in repair,LED Bldg Security Light Fittings of capacity 20 -25 watt made up of die castaluminiumhousing with black epoxy powder coating with cover heat resistance glass safety input voltage range 170 to 270 volts, industrial model with IP-65 protection and other connected accessories including electronic driver and making electrical connection, complete all as specified and as directed by the Engineer-in-Charge.Cat part No.ENDURASUNDOWNSL25WLED765PASYBOTGIHD of make Havells or equivalentin make given in Appx \"B\". |
| 25 | Supply and fixing in repair, service bracket of mild steel pipe 25 mm bore medium grade of length 0.70 mtr fixed to wall with two clamps made of 20 x 3 mm mild steel flat minimum 15cm long, 4 nos 8mm dia bolts with nuts and washer and suitable reducer for connecting fitting to GI pipe as required at site includingtwo coats ofsynthetic enamel paintoverone coat of red oxide primer on mild steel work complete all as specified and as directed by the Engineer-in-Charge. |
| 26 | Supply and fixingLED flat panel 2\" x 2\" size fully difused surface/ recess mounted fitting (grid/ gypsum type)36-40 watt , 5700K,warm/cool whitewith powder coating and CRCA front cover including framewith provision ofPVC flexible copper conductor cable from ceiling rose to light fitting as in repair complete all as specified and as directed by the Engr-in-charge.Cat part No.VENUSNEO2X2PLR36WLED857G2 of make Havells or equivalentin make given in Appx \"B\". |
| 27 | Supply & fixingLED Flood lights, 100 watt, IP-66, aluminum die cast housing with unique lens system and toughened glasswith gasket240 volt, 50Hz, AC supplycompletewithall accessories internally pre wiredincluding connecting with flexible copper conductorto connector of the light with necessary fixing arrangements, including disconnecting and taking down existing old unserviceable fittingcomplete all as specified and as directed by the Engr-in-charge. Cat part No. JETAIRISEFL100WLED757ARWBLTG of make Havells or equivalentin make given in Appx \"B\". |
| 28 | S & FLED Bollard 8-10 watt, IP-65 , 6500 K luminaire made ofpressure die castaluminium housing and clear glass , 240 volt, 50HZ, AC supply , completewithall accessories including electronic driver,internally pre wiredincluding connecting withthree core flexible copper conductor cable from Electric Supply Source to connector of the light as in repaircomplete all as specified and as directed by the Engineer-in-Charge.Cat part NoBAMBOOBLS8WLED830PSYMTOPC of make Havells or equivalentin make given in Appx \"B\". |
| 29 | S & FLED post top luminaire IP-65 made of pressure die-cast aluminium housing & clear glass 240 volt, 50HZ, AC supply completewithall accessories,suitable and including B22 LED lamp 15 watt, internally pre wiredincluding provision of 3 core PVC flexible copper conductor from electric supply source to connector of the light, including disconnecting and taking down existing light fitting and removing old unserviceable fitting complete all as specified and as directed by the Engr-in-charge.Cat part No. HLPT-04-B22 of make Halonix or equivalentin make given in Appx \"B\". |
| 30 | S & F LED high bay/medium bay luminaire 100 watt, IP-65,indoor type input voltage range 120-270 volts including electronic driver, provision of 3 core copperconductor cable 1.5 Sqmm size from connector/ceiling rose to fitting with fixing arrangement as per site requirement/conditions and including removing old unserviceable fittingcomplete all as specified and as directed by the Engr-in-charge.Cat part No. SAUCERGENXPROHBP100WLED757P60DBOLTG of make Havells or equivalentin make given in Appx \"B\". |
| 31 | S&F LED 22 watt integrated batten fitting with inbuilt lithium ion battery with minimum 4 hour back upincluding removing of unservicable light fitting complete all as specified and as directed by the Engineer-in-Charge.Cat part No.LED INVERTER BATTENHLB-08-22-CW-INV of make Halonix or equivalentin make given in Appx \"B\". |
| 32 | Supplyand fixingLED lamp Invertor technology 9 watt with 4 hour power back up with efficiency more than 100 lumen per watt,Lithium ion batterycomplete all as specified and as directed by the Engineer-in-Charge.Cat part No.LED INVERTER LIGHT 10 W B22 CW IP of make Halonix or equivalentin make given in Appx \"B\". |
| 33 | S&F single pole and neutral enclosure with a two pin and earth plug and socket 20 Amp complete with and including one single pole MCB.20 Amp, 10 KA \"B\" curve including removing old unserviceable enclosure complete all as specified and as directed by the Engr-in-charge.Cat part No.811955 of make Indo Asian or equivalentin make given in Appx \"B\". |
| 34 | Supply and fixing as in repair PCB unit suitable for BLDC ceiling fan of 1200mm sweep single phase, 240 volts of make crompton, Halonix, Havells etc complete all as specified and as directed by the Engr-in-charge.Note : PCB unit will be replaced by concerned OEM only. |
| 35 | Supply and fixas in repair modular PVC sheet/cover plate 3 way suitable for fixing switch/socket/fan regulators etc on existing MS boxes of any make as per site requirement including removing unserviceable items, complete all as specified and as directed by the Engr-in-charge. |
| 36 | Supply and fixas in repair modular PVC sheet/ cover plate 4 way suitable for fixing switch/socket/fan regulators etc on existing MS boxes of any make as per site requirement including removing unserviceable items, complete all as specified and as directed by the Engr-in-charge. |
| 37 | Supply and fixas in repair modular PVC sheet / cover plate 6 way suitable for fixing switch/socket/fan regulators etc on existing MS boxes of any make as per site requirement including removing unserviceable items, complete all as specified and as directed by the Engr-in-charge. |
| 38 | Supply and fixas in repair modular PVC sheet / cover plate 8 way suitable for fixing switch/socket/fan regulators etc on existing MS boxes of any make as per site requirement including removing unserviceable items, complete all as specified and as directed by the Engr-in-charge. |
| 39 | Supply and fixas in repair modular PVC sheet / cover plate 12 way suitable for fixing switch/socket/fan regulators etc on existing MS boxes of any make as per site requirement including removing unserviceable items, complete all as specified and as directed by the Engr-in-charge. |
| 40 | Supply and fixing GI/MS (terminal boxes) rectangular block with earth dolly duly painted internally and externally with two coats of anti corrosive paint over a coat of redoxide including provision of new 3 modular cover plate over sunken box fixed with brass screw and cup washer for mounting, modular switches, sockets outlets, fan regulator etc. complete all as specified and as directed by the Engr-in-charge. |
| 41 | All as per above item No. 40 but new 4 module cover plate complete all as specified and as directed by the Engr-in-charge. |
| 42 | All as per above item No. 40 but new 6 module cover plate complete all as specified and as directed by the Engr-in-charge. |
| 43 | All as per above item No. 40 but new 8 module cover plate complete all as specified and as directed by the Engr-in-charge. |
| 44 | All as per above item No. 40 but new 12 module cover plate complete all as specified and as directed by the Engr-in-charge. |
| 45 | All as per above item No. 40 but new 1 module cover plate complete all as specified and as directed by the Engr-in-charge. |
| 46 | Supplying and fixing in repair Thermoplastics IP 65 MCB distribution board 2 way in accordance with IEC 60670-24 which should be shock proof and double insulated. IP65 in accordance with IEC 60529 (EN 60529), weather proof, Corrosion free, Acid & Chemical Resistant, temperature resistance, Made of material Polycarbonate for Lid part andPS (polystyrene) for Base with transparent lid, sealable. halogen & Silicone free recyclable material, .The gasket material shall be Polyurethane, while the gasket shall be internally embedded.The enclosure is Consisting PE and N FIXCONNECT® terminal with provision for cable entry through top, bottom and sides. The impact strength of enclosure i.e. the Degree of Protection against Mechanical load shall be in accordance with IEC 62262 forIK 08 (5 Joule).And Enclosure should withstand Glow wire test at 750°C in accordance with IEC 60695-2-11 flame retardant, Self Extinguishing, UL subject 94,V-2. Color: Grey, RAL 7035.Suitable for indoor installation and outdoor installation, protected against weather influences complete all as specified and directed by Engineer-in-Charge. |
| 47 | Supply and fixing GI \"D\" clamp heavy duty superior quality and nut and bolts with locking arrangement complete all as specified and as directed by the Engr-in-charge. |
| 48 | Supply and fixing GIfan rod 600mm long heavy duty withsuperior quality and nut and bolts with locking arrangement complete all as specified and as directed by the Engr-in-charge. |
| 49 | Disconnectingelectric/water supply connection, taking down carefully geyser of any capacity,deposting to MES store yard for repair and refixing the same after repair at desired location complete all as specifed and directed by Engr-in-Charge. |
| 50 | Supply & replacing inner tank made from 1mm thick stainless steel sheet for geyser of 25 Ltr capacity including taking out old unserviceable inner tankof any description complete all as specified and as directed by the Engr-in-charge. |
| 51 | Supply and fixing mild steel powder coated outer body of water storage heater (Geyser) suitable for 25 Ltr capacity as in repaircomplete all as specified and as directed by the Engr-in-charge. |
| 52 | S & fixing heating elementcup or triangle type of 2 KW as required at site for geyser of any make and any descriptions including taking out old unserviceable heating elements complete all as specified and as directed by the Engr-in-charge. |
| 53 | S & F thermostat switch for geyser of any type ISI marked including taking out old unserviceable thermostat switch complete all as specified and as directed by the Engr-in-charge. |
| 54 | S & F geyser inner tank assembly suitable for geyser capacity of 25 Ltr including taking out old unserviceable tank assembly complete all as specified and as directed by the Engr-in-charge. |
| 55 | Supply and fixing in repair, heating element, 2 KW, having inbuilt thermostat as required at site for geyser of any make and descriptions complete, all as specified and as directed by the Engineer-in-Charge. |
| 56 | S&F brass chromium plated non return valve 15mm bore with air lock release arrangementincluding taking out old unserviceable non return valve, complete all as specified and as directed by the Engr-in-charge. |
| 57 | S & replacing metal clad socket & top as per existingsocket and topincluding taking out old unserviceable metal clad socket top, complete all as specified and as directed by the Engr-in-charge. |
| 58 | S & F in replacement flexible cable PVC insulated and sheathed,3 core, circular multi stranded copper conductor of 1.50 Sqmmincluding removing unserviceable cable, complete all as specified and as directed by the Engr-in-charge. |
| 59 | S&F brass connection pipe 450mm longhaving wire mesh coating over it with brass nuts and washers suitable for connecting geysers inlet and outlet with GI tubings including taking out old unserviceableconnections of any description all as specified and as directed by Engr-in-charge. |
| 60 | S&Ftop plug 15 Amp, 3 pin including taking out old unserviceable plug top complete all as specified and as directed by the Engr-in-charge. |
| 61 | S&F indicating lamp green/red in colour 230 volts as per existing makeincluding removing unserviceable items,complete all as specified and as directed by the Engr-in-charge. |
| 62 | Supply and fix MCB SP, 6-32 Amps, 240 volt,10 KA ,\"B\" curve as per site requirement including removing old unserviceable MCB complete all as specified and as directed by the Engineer-in-Charge. |
| 63 | Supply and fix MCB SPN 32 Amps, 240 volt,10 KA ,\"B\" curve as per site requirement including removing old unserviceable MCB complete all as specified and as directed by the Engineer-in-Charge. |
| 64 | Supply and fix MCB SPN, 63 Amps, 240 volt,10 KA ,\"C\" curve as per site requirement including removing old unserviceable MCB complete all as specified and as directed by the Engineer-in-Charge. |
| 65 | S & F in repairMCB four pole and neutral 415 Volts, 63-100 Amps, 16 KA, 50 Hz thermal adjustable type complete all as specified and directed by the Eng-in-charge. |
| 66 | Supply and fix MCB SP, 40-63 Amps, 240 volt,10 KA ,\"B\" curve as per site requirement including removing old unserviceable MCB complete all as specified and as directed by the Engineer-in-Charge. |
| 67 | Supply and fix sheet metal enclosureVertical triple pole & neutral(VTPN) IP-54 with MCCB 100 Amp, 16 KA, 415 volts, 4 way with 200 Amp rated bus bar flush /surface mounting double door duly grouted in solid block wall or on wooden board in and includinglugs/thimbles duly crimped for connectionincluding making smooth the disturbed surface including removing old unserviceable enclosure complete all as specified and as directed by the Engr-in-charge. Cat part No.811882 of make Indo Asian or equivalentin make given in Appx \"B\". |
| 68 | Supply and fix sheet metal enclosuretriple pole & neutral(TPN) IP-54 with MCB 63 Amp, 16 KA, 415 volts, 4 way with 200 Amp rated bus bar flush /surface mounting double door duly grouted in solid block wall or on wooden board in and includinglugs/thimbles duly crimped for connectionincluding making smooth the disturbed surface including removing old unserviceable enclosure complete all as specified and as directed by the Engr-in-charge. Cat part No.811856 of make Indo Asian or equivalentin make given in Appx \"B\". |
| 69 | Supply and fix sheet metal MCB DB SPN 4 way with 200 Amps rated bus bar single pole and neutral withdouble door IP-54 fixed on wall duly grouted in solid block wall or on wooden board in and including copper lugs/thimbles duly crimped for connection, including making smooth the disturbed surfaces including removing old unserviceable enclosure complete all as specified and as directed by the Engr-in-charge. Cat part No.811824 of make Indo Asian or equivalentin make given in Appx \"B\". |
| 70 | Supply and fix sheet metal MCB DB SPN8 way with 200 Amps rated bus bar single pole and neutral withdouble door IP-54 fixed on wall duly grouted in solid block wall or on wooden board in and including copper lugs/thimbles duly crimped for connection, including making smooth the disturbed surfaces including removing old unserviceable enclosure complete all as specified and as directed by the Engr-in-charge. Cat part No.811825 of make Indo Asian or equivalentin make given in Appx \"B\". |
| 71 | Supply and fix sheet metal MCB DB SPN 12 way with 200 Amps rated bus bar single pole and neutral withdouble door IP-54 fixed on wall duly grouted in solid block wall or on wooden board in and including copper lugs/thimbles duly crimped for connection, including making smooth the disturbed surfaces including removing old unserviceable enclosure complete all as specified and as directed by the Engr-in-charge. Cat part No.811828 of make Indo Asian or equivalentin make given in Appx \"B\". |
| 72 | Supply and fixing as in repair,MCCB, 4 pole, 63 Amp, 415 Volts, 16 KA , fixedtype including fixing arrangement, complete all as specified and as directed by the Engineer-in-Charge. |
| 73 | Supply and fixing as in repair,MCCB, 4 pole, 100 Amp, 415 Volts, 16 KA , fixedtype including fixing arrangement, complete all as specified and as directed by the Engineer-in-Charge. |
| 74 | S & laying as in repair sub main wiring with two run of 4 sqmm PVC insulated , unsheathed cable FRLS-H,1100 volts grade ISI marked with multi stranded copper conductor and one run of 4 sqmm PVC insulated , unsheathed cable FRLS-H, 1100 volt grade ISI markedmulti stranded copper conductor as earth continuty conductor connected to common earth dolly including concealed on wall/ceiling surfaces in and including PVC conduit medium gradeISI marked of adequate size for housing the wires complete all as specified and as directed by the Engineer-in-Charge.Note: (i) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.(ii) Three runs of cable and one run of PVC conduit shall be measured and paid as one unit length. |
| 75 | S & laying as in repair sub main wiring with two run of 6 sqmm PVC insulated , unsheathed cable FRLS-H,1100 volts grade ISI marked with multi stranded copper conductor and one run of 6 sqmm PVC insulated , unsheathed cable FRLS-H, 1100 volt grade ISI markedmulti stranded copper conductor as earth continuty conductor connected to common earth dolly including concealed on wall/ceiling surfaces in and includingPVC conduit medium gradeISI marked of adequate size for housing the wires complete all as specified and as directed by the Engineer-in-Charge.Note: (i) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.(ii) Three runs of cable and one run of PVC conduit shall be measured and paid as one unit length. |
| 76 | S & laying as in repair sub main wiring with four run of 10 sqmm PVC insulated , unsheathed cable FRLS-H,1100 volts grade ISI marked with multi stranded copper conductor and one run of 10 sqmm PVC insulated , unsheathed cable FRLS-H, 1100 volt grade ISI markedmulti stranded copper conductor as earth continuty conductor connected to common earth dolly including concealed on wall/ceiling surfaces in and includingPVC conduit medium gradeISI marked of adequate size for housing the wires complete all as specified and as directed by the Engineer-in-Charge.Note: (i) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.(ii) Four runs of cable and one run of PVC conduit shall be measured and paid as one unit length. |
| 77 | Supply and laying or fixing or passing through pipe 1100 volts grade heavy duty 2 core, 6 sq mm nominal cross section cable with PVC insulated aluminium conductormultistranded served with an inner sheathing of PVC tape and overall PVC sheathed in service connection, including disconnecting and taking down old U/S existingcable complete all as specified and as directed by the Engineer-in-Charge. |
| 78 | Supply and laying or fixing or passing through pipe 1100 volts grade heavy duty 2 core, 10 sq mm nominal cross section cable with PVC insulated aluminium conductormultistranded served with an inner sheathing of PVC tape and overall PVC sheathed in service connection, including disconnecting and taking down old U/S existingcable complete all as specified and as directed by the Engineer-in-Charge. |
| 79 | Material & labourfor earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5mtr below the normal ground level connected to galvanised earthstrip 25 x 3mm thickby means of bolts, nuts, check nuts and washers of galvanised iron.Earth stripprotected by GI pipe 32mm bore(medium grade) and connected to earthing test pointas directed and as specified and shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 40 cm x 40cm x 5cm reinforced with 8mm dia TMT bars @ 15cm c/cboth ways with one handle for liftingmade out of 8mm dia bar, funnel, wire mesh, 20mm dia GI pipe medium grade for watering, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil and testingas in repair complete all as directed by Engineer-in-Charge and earth testing on completion . |
| 80 | Material & labourfor earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5mtr below the normal ground level connected to galvanised earthwire 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron.Earth wire protected by GI pipe 15mm bore(medium grade) and connected to earthing test pointas directed and as specified and shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 40 cm x 40cm x 5cm reinforced with 8mm dia TMT bars @ 15cm c/cboth ways with one handle for liftingmade out of 8mm dia bar, funnel, wire mesh, 20mm dia GI pipe medium grade for watering, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil and testingas in repair complete all as directed by Engineer-in-Charge and earth testing on completion . |
| 81 | Supply only flexible cable PVC flat insulated and sheathed,2 core, circular multi stranded copper conductor of 1.5 Sqmmincluding removing unserviceable cable, complete all as specified and as directed by the Engr-in-charge. |
| 82 | Note:-Amount of credit ofRs. 1,11,047.40 for retrieved materials is mentioned in Schedule of Credit Page No. 83 & 84 of tender documents in pdf form which will be deducted offline while acceptance of tender. |