| 1 | S&F energy efficient LED street light fitting, 90W, input voltage 230VAC, 50Hz with ingress protection IP 65, CRI >70, PF>0.9, minimum 25000 burning hours,LM-80, lumen efficacy ≥100 lumen/watt, THD> 20, CRCA housingincluding all fixing arrengment like clamps, nuts, bolts, washers, 90W LED lamp with all accessories pre-wired and connecting with twin core twisted flexible copper conductor cable with all necessary staging, etc. for fixing at any locations including taking down the old unserviceable fittings complete all as specified and directed |
| 2 | Supply and Laying LT underground cable XLPE insulated and sheathed armoured cable 1100 volts 4 core 16 Sqmm aluminium conductor in trenches/poles and connecting with all accessories complete all as specified and directed |
| 3 | Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m depth, for foundation, laying/taking out pipe/cable etc. or for shafts, wells, cesspits, manholes, pier holes etc not exceeding 10Sqm on plan & not exceeding 1.5 mtr in depth and getting out loose/soft soil for laying of under ground cable complete all as specified and directed. |
| 4 | Returning filling in including spreading, levelling and well ramming in layers not exc 25cm in thick each in soft/loose type of soil complete all as specified and directed |
| 5 | Removal of excavated/surplus soil to a distance not exceeding 50mtr and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified. |
| 6 | M&L for sand cushioning to cable with a layer of sand 8cm deep before laying the cable and 15cm deep after laying the cable (punned down to 18cm depth after laying and stretching of cable) complete all as specified and directedNote: Punned down thickness of 18cm shall be measured for payment purpose only. |
| 7 | Supply and laying burnt brick of size 230x115x75mm for protection of cable, laying in trenches complete all as specified and directed |
| 8 | M&L for Making bore to road/cement path/hard standing for inserting GI pipe 40mmboth end socketed for passing armoured cable incl making good the disturbed surface complete all as specified and directed |
| 9 | S&F GI tubing of 40mm dia light grade at road crossing for protection cable as per site requirement and sealing the pipe both ends with sealing compound complete all as specified and directed |
| 10 | S&F security light bracket with 40mm bore GI tubing, light grade, cut and bent to shape required, 1.2m long fixed with including bends, flat iron clamp made of FI 40x6mm, nuts, bolts, washers, etc. duly painted with two coats of synthetic enamel paint over a coat of red oride zinc chrome primer complete all as specified and directed |
| 11 | S&F junction box thermoplastic polycarbonate enclosure, shock proof, IP66 (weather, rust, dust, water and vibration proof, outdoor type, internally embedded gasket with provision for all side cable entry through glands of size 295x195x100mm with 4Nos. aluminium bus bar of size 25x6mm, 8Nos. terminals with andincluding 01No. 10Amp MCB 10kA duly mounted fixed with MS clamps fabricated out of FI 40x3mm of required shape and size and fied at any location complete all as specified and directed |
| 12 | S&F PVC insulated copper conductor cable, 3 core 1.5sqmm, served with inner sheathing of PVC tape and overall PVC sheathed, 1100V grade heavy duty in connections with PVC conduit for providing connection to street lights from pole boxes complete all as specified and directed |
| 13 | S&F automatic street light Timer switch for automatic switching of street lights, 8kW, single phase, based on LUX level of natural light, infrared sensor based on nature switch along with contactor 40A, MCB SP for input and output 63A, wiring for main load with 3 core 16sqmm copper cable duly fixed to pole/wall, mounted on enclosure made out of rust proof, electric shock proof, termite proof and FR grade SMC junction box of protection class IP 54 fixed at any location complete all as specified and as directed |
| 14 | Taking down the existing PCC poles of any type including struts complete including making good the disturbed surface complete all as specified and directed |
| 15 | S&F steel tubular swaged poles of any type 410 SP-31 (9.0 meter long) complete with CI base plate and finial including foundation and coping complete all as specified and directed |
| 16 | S&F energy efficient LED flood light fitting, 250W, input voltage 230VAC, 50Hz with ingress protection IP 65, CRI >70, PF>0.9, minimum 25000 burning hours,LM-80, lumen efficacy ≥100 lumen/watt, THD> 20, CRCA housingincluding all fixing arrengment like clamps, nuts, bolts, washers, 250W LED lamp with all accessories pre-wired and connecting with twin core twisted flexible copper conductor cable with all necessary staging, etc. for fixing at any locations including taking down the old unserviceable fittings complete all as specified and directed |
| 17 | M&L for taking down by manual / motorised handle high mast light fittings at 15 to 20m height and refixing after necessary repairs including all necessary staging, etc. for cleaning of perplex covers, etc., tightening of loose connections on poles / walls, and replacing worn out minor parts, etc. and making the fitting functional complete all as specified and as directedNote: Quoted rate shall be deemed to be inclusive of any minor spares / parts replaced for functioning. |
| 18 | M&L for taking out burnt winding of 3 phase power tool electric motorof high mast fittings from any position, rewinding with super enamelled copper wire of existing size/gauge and varnishing, providing insulating paper and sleeves, etc. and testing for proper functioning on reinstating complete all as specified and as directedNote: Quoted rate shall be deemed to be inclusive of any minor spares / parts replaced for successful functionality of the motor |
| 19 | S&F steel wire hemp rope 8mm dia by taking out damaged rope and other minor parts suitable for high mast fittings15-20m high, like \"D\" clamps, nuts, bolts, washers, etc. replacing as needed and making the installation serviceable and testing for proper functioning on reinstating complete all as specified and as directedNote: Quoted rate shall be deemed to be inclusive of any necessities, T&P, etc. required forworking at 15-20m heights, etc. |