Tender For Construction Of 220 Kv Gis Substation Ghansali
Tender Overview
Project Description
Construction Of 220 Kv Gis Substation Ghansali
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 03-Sep-2024 | Corrigendum1 | BOQ | 25-Sep-2024 |
| 2 | 04-Sep-2024 | Corrigendum1 | Technical Bid | 25-Sep-2024 |
BOQ
| Sl. No. | Item Description |
| 1 | Construction of 220/33 KV GIS Substation Ghansali |
| 2 | Part-A (Supply of Material ) |
| 3 | Power Transformer |
| 4 | 10 MVA, 220/33KV, Single phase Transformer including Bushing, accessories, first filling of oil and Fibre Optic Temperature Measurement System. |
| 5 | Online DGA Multigas Type for above Transformers. |
| 6 | Nitrogen Injection Fire Prevention & Extingusihing System for above transformers. |
| 7 | Oil Storage Tank |
| 8 | Oil sampling Bottle |
| 9 | Station Transformer |
| 10 | 630KVA, 33/0.433KV, Three phase transformer includign bushing, accessories and first filling of oil. |
| 11 | 245kV GIS Equipments |
| 12 | 245kV, 3Ph SF6 Gas Insulated Transformer Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, two Bus-Bar disconnectors one with grounding switch and one without grounding switch, one disconnector with safety grounding switch, high speed fault acing grounding switch, SF6 gas monitoring system for complete bay, LCC, three 1-phase SF6 ducts and SF6/Air Interface to connect to 220/33kV, 10MVA 1Ph Transformers and accessories with GIS etc. to complete Transformer Bay Module. |
| 13 | 245KV, 3Ph SF6 gas Insulated Feeder Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, two bus-bar disconnectors one with grounding switch and one without grounding switch, line disconnector with safety grounding switch, high speed fault acting grounding switch, SF6 gas monitoring system for complete bay, LCC, SF6/Cable Termination and accessories with GIS etc. to complete feeder bay module. |
| 14 | 245KV, 3Ph SF6 gas Insulated, metal enclosed Bus Bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus-bar set shall be complete with voltage transformer complete with safety grounding switch. |
| 15 | 245KV, 3Ph SF6 gas Insulated Bus Coupler Bay Module comprising of SF6 gas insulated Circuit Breaker, Current Transformer, two disconnectors with safety grounding switches, SF6 gas monitoring system for complete bay, LCC etc. |
| 16 | 245kV AIS Equipments |
| 17 | 245kV CVT |
| 18 | Junction box for above 245kV CVT |
| 19 | 245 kV Lightning Arrester with counter and leakage meter |
| 20 | 245 kV BPI |
| 21 | Miscellaneous Materials (Insulators Strings / Disc Insulators, Hardwares, Aluminium Tube / Conductor, Bus-Bar materials, Cable Trays, Clamps, Connector including equipments connectors and all accessories etc. |
| 22 | 36KV GIS Equipments |
| 23 | 36KV, SF6 gas Insulated Feeder Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformers, Potential Transformers, Lightning Arresters, two bus-bar disconnectors one withgrounding switch & one without grounding switch, SF6 gas monitoring system for complete bay, control & protection along with associated equipment. Cable termination and accessories with GIS etc. for 33kV outgoing Line feeder bay module. |
| 24 | 36KV, SF6 gas insulated Bus Coupler bay module comprising of SF6 gas insulated circuit breaker, current transformer, two numbers of disconnectors with earthing switch, SF6 gas monitoring system for complete bay, control & protection along with associated equipment. etc. |
| 25 | 36KV,SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker, current transformer, Lightning Arresters, two bus-bar disconnectors one with grounding switch & one without grounding switch, SF6 gas monitoring system for complete bay, with cable termination, control & protection along with associated equipments. |
| 26 | 36KV, 3-phase or single phase encapsulated unit, SF6 gas insulated, metal enclosed bus-bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus-bar set shall be complete with voltage transformers with safety grounging switch. |
| 27 | 36KV, SF6 gas insulated feeder bay module each comprising of SF6 gas insulated circuit breaker, current transformers, Potential Transformers, Lightning Arresters, two bus-bar disconnectors with grounding switch, SF6 gas monitoring system for complete bay, Cable termination and accessories with GIS etc. suitable for 630 KVA 33/0.433kV station transformer, control units, control and protection along with associated equipment. |
| 28 | 36KV AIS Equipments |
| 29 | 33kV BPI |
| 30 | 33kV Lightning Arrester |
| 31 | 33 kV Air Break Switch |
| 32 | Miscellaneous Materials (Insulators Strings / Disc Insulators, Hardwares, Aluminium Tube / Conductor, Bus-Bar materials, Cable Trays, Clamps, Connector including equipments connectors and all accessories etc. |
| 33 | Complete Substation Automation System including hardware and software for the substation & remote control stations alongwith associated equipments as per Technical Specifications. |
| 34 | Bay Control Units |
| 35 | 220kV System |
| 36 | 33kV System |
| 37 | Online Monitoring, Data Acquisitionand ABT Analysis System |
| 38 | ABT meters 0.2s Cl with TCP/IP, Optical Communication Port |
| 39 | Industrial Grade Network Switch -8 Port, unmanaged |
| 40 | UPS 2 KVA online with 30 Min back up on 100% load |
| 41 | DCU & Accessories |
| 42 | Workstation : Application & Database server |
| 43 | Database -Microsoft SQL Server 2016 Standard Edition |
| 44 | MS office - Standard edition |
| 45 | MacAfee Virus Scan Enterprise Desktop Edition - Per Year |
| 46 | Local Energy Monitoring Software - Professional edition |
| 47 | Lan cable ( average one roll per S/S 300 Meters) |
| 48 | PVC conduit Pipe - 3/4\" |
| 49 | Enclosure for Lan Switch |
| 50 | 4G/5G Data enable SIM |
| 51 | 220 KV Control and Relay Panel |
| 52 | Circuit Breaker Control Panel |
| 53 | With Auto Reclose |
| 54 | Without Auto Reclose |
| 55 | Line Protection Panel (Main 1+Main 2) |
| 56 | Bus Bar Protection Panel |
| 57 | 220kV bus bar protection panel for Main-1 and Main-2 |
| 58 | Transformer Protection Panel (HV side) |
| 59 | PLCC for 220KV Line feeder |
| 60 | Line Traps |
| 61 | 2000A, 0.5 mH, 40 kA |
| 62 | Coupling device ( Phase to Phase ) |
| 63 | HF Cable |
| 64 | Carrier Equipment |
| 65 | for Speech + Protection 1 & 2 |
| 66 | for Speech + Data |
| 67 | Protection Coupler |
| 68 | Time synchronisation equipment |
| 69 | Testing & Maintenance Equipment |
| 70 | Insulation Tester Meter 15kV Multirange (Motorized) |
| 71 | Thermo Vision Camera |
| 72 | Automatic Capacitor and Tan Delta measuring kit |
| 73 | Digital Multi Meter |
| 74 | Leakage Tester (Tong type) |
| 75 | Selective Level Meter |
| 76 | Signal Generator |
| 77 | Micro-ohm meter |
| 78 | Gapless zinc oxide LA tester |
| 79 | Oil BDV Kit 0-100 KV |
| 80 | Gas Evacuating and refilling Plant for 220kV GIS |
| 81 | Winding resistance meter |
| 82 | Gas Leakge Monitor |
| 83 | Circuit Breaker Analyser |
| 84 | Portable Partial dischange monitoring system |
| 85 | Dew Point Meter |
| 86 | Battery Earth Fault Locator |
| 87 | Primary Injection Set 1000 Amp |
| 88 | Relay Test Kit |
| 89 | Gas Mask |
| 90 | D-Spanner set (Insulated), Ring-Spanner set (Insulated) & Torque Wrench set. Each set shall be a complete set including all standard sizes. |
| 91 | Insulating Gloves & Helmets |
| 92 | Hydraulic Ladder Battery Operated (Rechargable) upto 300kg capacity & 10 Mtrs height |
| 93 | Spliced ladders 5mtr. & 10mtr. |
| 94 | Spliced ladders 20mtr. |
| 95 | Polyamide or Braided white nylon ropes 12mm, 14mm & 20mm of each type |
| 96 | Rubber mat in Control room, Battery Room & LT Panel Room etc. as per Site requirements |
| 97 | Shock treatment chart & artificial respiratory system |
| 98 | First-aid box complete with first filling of required medicines, instruments and tools |
| 99 | Danger / Man on line / Break-Down boards of appropriate size |
| 100 | Rain coat, Gum boot and Safety Harness Belt with adequate straps |
| 101 | Air-conditioner |
| 102 | Split AC (capacity-2T) maximum star rating |
| 103 | Ventillation system for 220kV & 33kV GIS Hall |
| 104 | Miscellaneous items |
| 105 | Air Curtain for Control Room Building |
| 106 | Interactive Screen for Control Room Building |
| 107 | LT Switchboard |
| 108 | 415V Main Switchboard |
| 109 | 415V ACDB |
| 110 | MLDB |
| 111 | ELDB |
| 112 | NLP |
| 113 | ELP |
| 114 | 220V DCDB |
| 115 | 48V DCDB |
| 116 | Batteries |
| 117 | 220V, 500AH |
| 118 | 48V, 300AH |
| 119 | Battery charger system |
| 120 | 220V, 100Amps Float Cum Boost Charger |
| 121 | 48V, 60Amps Float Cum Boost Charger |
| 122 | 250KVA, 440V DG set alongwith AMF Control Panel |
| 123 | Fire Prevention & Extinguishing System |
| 124 | Fire Detection and Alarm System for 220 kV & 33 kV GIS hall, Control Room Building |
| 125 | CO2 Type Fire Extinguisher 9 kgs |
| 126 | CO2 Type Fire Extinguisher 4.5 kgs |
| 127 | Mechanical Foam Type Fire Extinguisher 9 Ltrs |
| 128 | Bucket Stand (including 4 Buckets with sand fill) |
| 129 | Illumination sytem |
| 130 | 33kV GIS Room / Control Room / Store Room / Offices llumination (LED Type Lights) |
| 131 | LED Lights for Switchyard Lighting with complete fittings, Junction Box & mounting accessories |
| 132 | Solar light system for street light (LED Type Lights) with Pole and other mounting accessories |
| 133 | LED Lights for 220kV GIS, High Bay type with complete fittings |
| 134 | 1.1kV Armoured Power Cables (AL) and aromoured Controlcables (Copper) alongwith multidiameter moulded cable sealing, Lugs, Glands and straight joints, etc. |
| 135 | Power cables Aluminium (XLPE) |
| 136 | 3.5cx300 Sq.mm |
| 137 | Power cable Aluminium (PVC) |
| 138 | 3.5cx70Sq.mm |
| 139 | 3.5cx35Sq.mm |
| 140 | 4cx16 Sq.mm |
| 141 | 4cx6 Sq.mm |
| 142 | Control cable Copper (PVC) |
| 143 | 2Cx2.5Sq.mm |
| 144 | 4Cx2.5Sq.mm |
| 145 | 6Cx2.5Sq.mm |
| 146 | 10Cx2.5Sq.mm |
| 147 | 220 kV and 33 kVPower Cable and accessories |
| 148 | 220kV XLPECopper Power cables of size 1 X 1200 sq.mm. |
| 149 | 220kV Indoor termination kit suitable for 1 X 1200 sq.mm. Cable (3 Nos.) |
| 150 | 220kV Outdoor termination kit suitable for 1 X 1200 sq.mm. Cable (3 Nos.) |
| 151 | 33kV XLPE Copper Power cables of size 1 X 630 sq.mm. |
| 152 | 33kV Indoor Termination kit suitable for 1 x 630 sq.mm. Cable (3 Nos.) |
| 153 | 33kV outdoor termination kit suitable for 1 x 630 sq.mm. Cable (3 Nos.) |
| 154 | 33kV XLPE Copper Power Cablefor Auxiliary transformer of size 1 X 185 sq.mm. |
| 155 | 33kV Indoor Termination kit suitable for 1 x 185 sq.mm. Cable (3Nos.) |
| 156 | 33kV Outdoor Termination kit suitable for 1 x 185 sq.mm. Cable (3Nos.) |
| 157 | Grounding/Earthing system |
| 158 | 40mm MS rod for earthmat |
| 159 | 40mm MS 03 metre Electrodes |
| 160 | 40mm 03 meter deep driven pipe electrode (treated pit) |
| 161 | GS and MS Flats 75 x 12mm size |
| 162 | GS and MS Flats 50 x 6mm size |
| 163 | Steel structure |
| 164 | Lattice Structure |
| 165 | Pipe Structure |
| 166 | EOT Crane |
| 167 | EOT Crane for 220kV GIS Room |
| 168 | Moveable ladder of suitable capacity for 220 KV & 33 KV GIS Room |
| 169 | SDH/MUX EQUIPMENT |
| 170 | Steel Cabinet with all internal wiring/terminations/MDF and arrangement for dual 48/50V Power supply input |
| 171 | SDH (STM-4 upgradable upto STM-16)/MUX base 19\" equipment rack (incl. front cover, cable tray, common cards such as redundant CPU) with arrangement for dual input power supply. |
| 172 | OLTE - 4 Port STM-1 (155 Mbps) Card excluding SFPs |
| 173 | SFP module to support upto 50 km |
| 174 | Optical Amplifier/Booster equipment |
| 175 | OFC Patch Cords - (Set of 12 Nos.) |
| 176 | Ethernet over SDH (STM-4 upgradable upto STM-16) transport card (with eight 10/100/1000BaseT interfaces) |
| 177 | Minimum 8 Port E1 interface card |
| 178 | Minimum 8 Port 4w E&M Interface card |
| 179 | Minimum 12 Port FXO interface card |
| 180 | Minimum 10 Port FXS interface card |
| 181 | Minimum 4 Port programmable data interface card |
| 182 | Integrated Teleprotection card (4 Commands each) |
| 183 | Engineering Order Wire Phone |
| 184 | Optical Fibre Cable for above OPGW communication |
| 185 | Mandatory spares as per list indicated in section \"Mandatory Spares\" of Technical Specifications for following items: |
| 186 | 220/33kV Transformer |
| 187 | 245kV GIS CB |
| 188 | 245kV VT GIS Type (3 Nos) |
| 189 | 245kV CT GIS Type (3 Nos) |
| 190 | 216kV Surge Arrestor (3 Nos) |
| 191 | 245kV Isolators & ES GIS Type |
| 192 | 36kV GIS Type CB |
| 193 | 36kV GIS Type CT (3 Nos) |
| 194 | 36KV VT GIS Type (3 Nos) |
| 195 | 36KV Surge Arrestor AIS Type (3 Nos) |
| 196 | 36KV Isolators & ES GIS Type (3Nos.) |
| 197 | llumination system |
| 198 | Optic fibre cable |
| 199 | Fire fighting |
| 200 | Battery |
| 201 | Battery Charger |
| 202 | Relay & Protection Panels |
| 203 | Substation Automation |
| 204 | LT Switchgear |
| 205 | Common spares, for maintenance purpose |
| 206 | DG Set |
| 207 | 220 KV CVT Outdoor Type (3 Nos) |
| 208 | 220 KV LA Outdoor Type (3 Nos) |
| 209 | 220kV Indoor Termination kit suitable for above 1x1200sq. mm cable (1No.) |
| 210 | 220kV Outdoor Termination kit suitable for above 1x1200sq. mm cable (1No.) |
| 211 | 33kV Indoor Termination kit suitable for above 1x630sq. mm cable and for 1x185 sq. mm cable (1No.) |
| 212 | 33kV Outdoor Termination kit suitable for above 1x630sq. mm cable and for 1x185 sq. mm cable (1No.) |
| 213 | Support for Operation and Maintenance (O&M) of Substation, Trouble shooting and familarization of PTCUL staff with the installed system for a period of06 (Six) Months by deploying adequate number (Minimum 02) of qualified persons round the clock. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender