| 1 | Wiring for light point / exhaust fan point with (P+N+E) 3X1.5 sq.mm FRLS-H PVC insulated multi strand copper conductor single core cable insurface/ recessed Conduits. The job includingcost of conduits wire (6/8 points per circuit)in 2.5sq.mm (with 1 X 2.5 Sq.mm) for earth Multistrand Copper wire from switch board to D.B complete (Havells/ Polycab/ AnchorMake ) including cost of conduits with other accessories llke bends. Deep junction Boxes, Surface junctions etc to be laid in wall/ ceiling (Slab) complete, with 01 No. of 6 Amp Modular Switch, Modualar Plate. Coverin from. Modular Blanking plate wherever required & suitable GI box etc ISO/ IEC Certified Havells/ Legrand/ Panasonic/ Anchor, Rooma/ Plus/ Schiender Make & shall be approved before execution of work by competent authority. |
| 2 | Wiring forCeiling fan point with (P+N+E) 3 x 1.5 sq.mm FRLS-H PVC insulated multi strand copper conductor single core cable insurface/ recessed Conduits. ( Havels/ Polycab/ Anchor/ Make) including cost of conduits with other accessories llke bends. Deep junction Boxes, Surface junctions etc to be laid inceilingcomplete,complete with01 No. of 6 Amp Modular Switch, Two Module Stepped Type Electonic Fan Regulator, Modular Plate. Cover in front, & suitable G.I box etc ISO/ IEC Certified Havels/ Legrand/ Panasonic/ Anchor/ Rooma Plus/ Schneider Make and shall be approved before execution of work. |
| 3 | Wiring forPower Plug with (P+N+E) 3 x 4 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in existing surface. recessed Conduits. ( Havels/ Polycab/ Anchor/ Make) including cost of conduits with other accessories like bends etc complete to be laid in wall and finishing the surface to its oringinal shape by cement mortar plastering /with 01 No. of 16 Amp, Modular Switch , Modular 01 No. of 3-Pin 16 AMp Socket, Modular plate, cover in front,Modular blanking plate where required and suitable GI box etc ISO/ IEC Certified Havels/ Legrand/ Panasonic/ Anchor/ Rooma Plus/ Schneider Make and shall be approved before esecution of work |
| 4 | Wiring for6Amp Plug ( Computer) with(P+N+E) 3 x 2.5 sq.mm FRLS PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit ( Havels/ Polycab/ Anchor/ Make) including cost of conduits with other accessories like bends etc complete to be laid in wall and finishing the surface to its oringinal shape by cement mortar plastering / with 02 No. of 06 Amp, Modular Switch ,02 No. Modular 6 Amp of 5-PinSocket, Modular plate, cover , Modular blanking plate where required and suitable GI box etc ISO/ IEC Certified Havels/ Legrand/ Panasonic/ Anchor/ Rooma Plus/ Schneider Make and shall be approved before esecution of work |
| 5 | Wiring for Sub mainwiring along with earthWire with the following Sizes of FRLSPVC insulatedcopper conductor, single core Cable in surface/Recessed medium class PVC conduit ( Havels/ Polycab/ Anchor/ Make) including cost of conduits with other accessories like bend etc complete to be laid in wall ceiling , (Slab) and shall be approved befor execution of work. |
| 6 | 2 x 10 sq. mm + 1 x 10 sq. mm (P+N+E)for Power point sub main in one run from Main Panel to Distribution Boards. |
| 7 | 2 x 6 sq. mm + 1 x 6 sq. mm ( P+N+E) for Lighting/ Invertersub main from Main panel to Distribution board. |
| 8 | Supply/ Fixing/ Testing and Commissioning of 5Amp to 32Amp Rating. 240v.*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB , DBComplete with Connections. (Havels/ L&T/ Siemens/ Legrand/ ABB/ Scheinder Make). |
| 9 | Supply/ Fixing/ Testing and Commissioning of following rating, Doublepole, (P+N) 240 V, C* Curve 10K, Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (Havels/ L&T/Seimens/ Legrand/ABB/ Scheinder Make) |
| 10 | 40Amp. |
| 11 | 63Amp. |
| 12 | Supplying and Fixing of MCB 8-way (4+18) horizontal typed, sheet steel, Double door, Distribution board, TPN 240V/415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, [powder painted including earthing etc as required. (Havels/ L&T/Seimens/ Legrand/ABB/ Scheinder Make) |
| 13 | ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER Rod EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value .Supplying, Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No. bagsalso having Earth pit chamber (300mm x 300mm) withman- hole cover for the above. Including cost of 2OMM Wide copper strip as requiredin one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through Weather proof PVC Pipe completejob |
| 14 | Supply, Installation, Testing and commissioning of 18W+.LEDSurface mounted light luminary fittingsRound shape with minimum system lumen efficacy of 100lm/W with Pressure Die cast Aluminium Heat Sink and P.I > 0.95. THD< 10% .CCT 5700K. CRI 80. The LED with Useful life of 50000 Hrs at L.70., The input voltage range shall be 150V to 270V. The Fixture should have In-built Surge Protection of 2kV Certification:- LM79 & LM80 test report should be from govt approved In-house NABI. lab/ government of India authorised lab. THe job includes AMC reckoned from date of successful commissioning) of lighting fixtures for a period of Two years, which includes replacement of fixtures of Philips/ Havels/ Wipro/ Jaguar/ H.G make. |
| 15 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, ceiling fan with 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, Power Factor not less than 0.9 Service value,including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, etc.complete as required. USHA/HAVELLS/ Polycab/ Luker/ USAMake. |
| 16 | Supply, Installation, Testing and Commissioning ofwall mounted cubical1-PHASE + Neutral Distribution Panel fabricated of 16 gauge sheet steel with 200Amp 1-phase neutral (PN) Al. BUS BAR sets, the panel should have standing dust & vermin proof with gasket lockable door of 16 gauge sheet steel. The Panel should be painted with Electro static powder coated colour, Seimens grey structural with proper chemical pre-treatment with film thickness 35-40 Microns. dully fitted on wall with D-Fast Geyser Bolts & nuts Voltmeter, Phase-indicators etc also having 125Amp DP MCCB of Havels / Legrand / Scheinder or L&T Make with adequate kA Breaking Capacity Make C-Curve complete Job. |
| 17 | Supply/ Installation / Testing and Commisssioning of ABC type Fire Extinguisher 4.Kg. Capacity ISI Mark (IS: 15683) and dully certified. |
| 18 | Supply, Laying, Testing and Commissioning of 50 sq.mm. 2-Core Steelarmoured Cable Al. Cable XLPE/ PVC insulated and sheathed duly to be laid underground through DWC High Density Poly ethlene Pipe having Corrugation on Outer wall and Plain surface innder wall Conforming to IS:14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cables Main Service Line from Nearby L.T pole to Panel. |
| 19 | Supply/ Laying of 25/32mm Dia PVC Conduit of Standard Make with other accessories like bends etc complete to be laid in wall for downs and finishing the surgace to its original shape by cement mortar plastering/ Wall Putty/ Paint etc. |