| Sl. No. | Item Description |
| 1 | Supplying and erecting PVC trunking (PVC casing-n-capping)ofsize25 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 2 | Supplying and erectingHMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG- MA/CC. |
| 3 | Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specificationNo: WG-MA/BW |
| 4 | Supplying and erecting mains with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 5 | Supplying and erecting mains with 2x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 6 | Supplying and erecting mains with 1x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places as per specification No: WG-MA/BW |
| 7 | Supplying and erecting mains with 2x2.5 sq.mmFRLSH copper PVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 8 | Supplying and erecting mains with 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 9 | Point wiring for light/fan/bell in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire with flush type switch and required accessories as per specification No: WG-PW/SW |
| 10 | Point wiring for light/bell/exhaust fan in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthingand requiredaccessories as per specification No: WG- PW/SW. |
| 11 | Point wiring for independent plug in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E ) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG- PW/SW |
| 12 | Supplying and erecting single pole and neutral distributionboard (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB |
| 13 | Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAhLithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty. |
| 14 | Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete. |
| 15 | Supplying and erectingmodular type switch 16Aduly erected on provided plate and boxwith wiring connections complete. |
| 16 | Supplying and erectingmodular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete. |
| 17 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected. |
| 18 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 95sq. mm. aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 19 | Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL(mainincoming cable to main fire panel). |
| 20 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU(for booster Pump) |
| 21 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 22 | Supplying & laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 23 | Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW- SWR/MCCB. Note : For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. Hence 18563 X 20%= 3712.60/- |
| 24 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 146 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete. |
| 25 | Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 100 mm height comprising all required standard accessories. |
| 26 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories. |
| 27 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 400 mm width & 100 mm height comprising all required standard accessories. |
| 28 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing. |
| 29 | Supplying and erecting GI strip of required size used for earthing on wall and/or any otherpurpose with necessary GI clampsfixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/m x 60 m=60 kg) |
| 30 | Supplying, installation, testing and commissioning ofmain fire pump(MFP / EP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 75kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levellingcomplete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, asper specification no. FF- MFP/SSC/EP |
| 31 | Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 110 to 90 m head driven by electric motor415 volts, 3 phase 50 Hz, AC supply of 11 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, asper specification no. FF-MFP/JP |
| 32 | Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat ofprimer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP |
| 33 | Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by 110 HP or suitable HP capacity diesel engine at required working speed suitable for automatic operation and consisting of following :(a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520.(b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine , exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP |
| 34 | Supplying, erecting, testing & commissioning of fire pump control panel (FCP) of cubical construction, floor mounted type, fabricated from minimum 2 mm thick CRCA sheet, compartmentalised with hinged lockable doors, with enclosure protection class IP54, duly powder coated or painted with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003), cable alley, interconnection with suitable size solid copper busbar strip of adequate size for all power connections having switchgears and accessories, mountings and internal wiring with adequate size copper conductor cable, earth terminals, numbering etc. complete in all respect, suitable for satisfactory operation of main fire pump and jockey (pressurisation) pumps (1working+1standby) with necessary accessories, wiring & cabling along with allied accessories with following incoming and outgoings, suitable for automatic & manual operation on 415V, 3 phase, 50Hz ac supply as per specificationsthe capacity of electric motor driven pump are as followsa. Main fire pump(MFP) having capacity of 22kW 1no (1 working)b. Jockey pump(JP) capacity of suitable capacity 2 nos(1 working +1 standby, alternate run per start in auto mode)comprises of the following features & switchgears:1. Main incomer FP SFU having rotary handle with HRC fuses of suitable rating.2. Electrolytic grade copper strips for busbar of suitable sizes for main incomer andbranches to motor SFU\"s, starters & outgoing terminals with necessary accessories like stainless steel nut bolts with spring washers for connections, mounted on required no of epoxy or porcelain support insulators of suitable ratings etc.3. Individual pump TPN SFU having rotary handlewith HRC fuses of suitable rating.)4. Digital voltmeter & ammeter & RYB indicating lamps & push buttons & SPP, O/L & phase reversal protection with emergency stop switch.5. TPN SPD 100kA Type 1 +2 tested.6. Required pressure transducer with pressure indication on panel with cabling required for monitoring & automatic operation of fire pumps.7. System controller to control operation of main electric fire pump, jockey (pressurization) pumps in sequence with interlocking for operation of pumps as per specification with automatic/manual operation with selector switch & alternate run of standby Pumps consisting of relays, timers. sensors, annunciation window for fault indication, complete as per specification.8.Suitable capacity electric motor starters for all individual pumps with necessary push buttons & indications.9. Siren of required capacity to be activated when main pump starts & allied accessories as per requirements of local CFO or as directed by engineer in charge.10. Danger board as per IS.11. Spare HRC fuses minimum 2nos of each individual rating with required bakelite fuse holder for main & jockey fire pumps MFP=(1working), JP = (1working+1standby, |
| 35 | For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic.....for 5.5/ 7.5 kW centrifugal type booster pump 1no(5working) , add Rs….... |
| 36 | Supplying anderecting100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) forpositive suction complete asper specification no. FF-VL/ELS ( 2 nos for jockey pump + 5 nos for booster pump=7 Nos. |
| 37 | Supplying anderecting200 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, screen of SS end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) forpositive suction complete as per specification no. FF- VL/ELS ( 1 nos main pump+1 nos for sprinkler pump+ 1 for disel pump= 3 Nos). |
| 38 | Supplyinganderecting100mm dia.cast iron double flange sluice valve complete with PN16 pressure rating, asper specification no. FF-VL/SV |
| 39 | Supplyinganderecting200mm dia.cast iron double flange sluice valve complete with PN16 pressure rating, asper specification no. FF-VL/SV |
| 40 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, asper specification no. FF-VL/BFV |
| 41 | Supplying & erecting cast iron double flange butterfly valve of size 75/80 mm dia. complete asper specification no. FF-VL/BFV |
| 42 | Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete asper specification no. FF-VL/BFV |
| 43 | Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete asper specification no. FF-VL/BFV |
| 44 | Supplying & erecting cast iron double flange butterfly valve of size 200 mm dia. Complete asper specification no. FF-VL/BFV |
| 45 | Supplying and erecting cast iron double flange ball type NRV of size 75mm/80 mm diacomplete asper specification no. FF- VL/NRV |
| 46 | Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV |
| 47 | Supplying and erecting cast iron double flange ball type NRV of size 150 mm dia complete as per specification no. FF-VL/NRV |
| 48 | Supplying and erecting cast iron double flange ball type NRV of size 200 mm dia complete as per specification no. FF-VL/NRV |
| 49 | Supplying&erectinggunmetal gatevalve of size25 mmdia complete asper specification no. FF-VL/GV |
| 50 | Supplying and installing air vessel of 300 mm dia1.5min heightM.S.tank installed inside pump house / on terrace complete as per specification no. FF-FFA/ACT(1 nos for hydrant + 1 nos for sprinkler= 2 nos). |
| 51 | Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete asper specification no.FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos. |
| 52 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc.complete asper specification no. FF-FFA/PG |
| 53 | Supplying and erecting12/15 mm dia pressureswitchwith provided isolation valve,G.I. nipple, elbow, etc complete asper specification no. FF-FFA/PS |
| 54 | Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables up tovoltage level1.1Kv cable complete as per specification No. CW-EXN-CTR |
| 55 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps(1.2x 1.2 x0.8)= 1.15 x 5= 5.76 cum for overhead tank foundation (1.8 x 1.8 x 0.3)=0.972 x 5=4.86 cum total(6.9+5.82)= 10.62 Cu-M. For Hydrant Line Pedastal of size 1.2 m X 0.6 m X 0.6 m =0.432 cum per pedastal , total terrace overhead ring line length 720 m /pedastal support will be at 4 m each ,hence total qty would be - 720/4 = 180 Nos ,so 180 X 0.432 = 77.76 cum( pump foundation 10.62 cum + Pedastal 77.76 cum = 88.38 cum total) |
| 56 | Supply, Instalation, testing of zinc aluminite fire water storage tank having capacity 50 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC). |
| 57 | Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthe position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached). |
| 58 | Supplying anderectingstainless steel single outlet hydrant valve fitted with necessary accessories complete asper specification no. FF-VL/HV. |
| 59 | Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose)along with necessary accessories complete asper specification no. FF-FFA/HV |
| 60 | Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m inlength, fitted with necessary accessories complete as per specification no. FF-FFA/RRL |
| 61 | Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzlecomplete as per specifications no. FF-FFA/NZ |
| 62 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant). |
| 63 | Supplying and erecting M.S./CRCA cabinet for housing single hydrant valveof size ( 400 x 400 x 400)mm or hose pipe box of size ( 600 x 600 x 200)mmmade from min. 1.5 mm thick CRCA sheet with angle iron work of min. of size (25 x 25 x 4) mmhaving front doors with viewing glass of size (200x150) mmandlockingarrangement with necessary fixingmaterialsuch as rubber biddingetc. dulypainted in post box red colour( Code 538 of IS 5) |
| 64 | Carrying out core cutting of size 3\" to 5\" dia x 15\" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. |
| 65 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete asper specification no. FF-PP |
| 66 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete asper specification no. FF-PP |
| 67 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete asper specification no. FF-PP |
| 68 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete asper specification no. FF-PP |
| 69 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete asper specification no. FF-PP |
| 70 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete asper specification no. FF-PP |
| 71 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 200 mm dia with necessary fittings complete asper specification no. FF-PP |
| 72 | Supplying&erectinggun metal gatevalve of size20 mmdia complete asper specification no. FF-VL/GV |
| 73 | Supplying&erectinggunmetal gatevalve of size25 mmdia complete asper specification no. FF-VL/GV |
| 74 | Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessary fittings as per specifications having 1000mm long with UL/FM |
| 75 | Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½\") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR. |
| 76 | Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½\") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS |
| 77 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Approx 780 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 780 =780 Nos) |
| 78 | Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 8 loop capacity and capable of supporting upto 250 devices and detectorsper loop,with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, IS 2189: 2008, EN 54 & VDS / FM/UL8 |
| 79 | Supplying, installing, testing and commissioning ofrepeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approvedwith 3 years equipment replacement warranty FF-AFAS/RP |
| 80 | Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or ULApproved with 3 years equipment replacement warranty FF-AFAS/SD |
| 81 | Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area\"s etc. with 3 years equipment replacement warrantyIS : 2175 - 1988 reaffirmed 2000,IS 15908:2021standards FF-AFAS/SD. |
| 82 | Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with \"Break Glass\" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listedwith 3 years equipment replacementwarrantyFF-AFAS/MCP. |
| 83 | Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays,EN 54 or UL Listed FF- AFAS/CRM |
| 84 | Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming toIS 5051Part 2 (Sec 1 to 3) : 1982 Reed relaysFF-AFAS/MM |
| 85 | Supplying, installing, testing and commissioning of addressable fire isolator module complete as required.EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM |
| 86 | Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage rangeEN 54, conforming to IS 2189: 2008, IS 15908:2021standards with 3 years equipment replacement warranty FF-AFAS/SSH. |
| 87 | Supplying, installing, testing and commissioningFR, XLPE armouredcable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete asper specification no. CB-LT/CU |
| 88 | Supplying, installing, testing and commissioningFR, XLPE armouredcable 8 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete asper specification no.CB-LT/CU |
| 89 | Supplying, Installing, Testing & Commissioning of Microprocessor based system 6 zone controller complete with capacity upto 16 Zone designed as per tender specifications for Zone wise Announcement can connect upto 2 call station upto 255 messages to be stored with 12 input points for trigger points for EVAC compliment IFC 60489. Routers with 3 EMG inputs contacts and 6 volume contacts shall have a superviosry features dual tone controls for speech & music processor with relays for activating pre recorded fire alarm messages it shall be rack mountable. |
| 90 | Supplying, Installing, Testing & Commissioning of Announcement Console/Call Station shall be designed for 6 Zone Call Station with Expansion Keypads of At least 2 Additional Zones and Capable of Integration with at least 8 such keypads should be selected. |
| 91 | Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230VoltsA.C. / 12VoltsD.C. supply complete asper specification no. FF- PA/AFR |
| 92 | Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete asper specification no. FF-PA/SOC |
| 93 | Supplying and fixing 42 U floormount server rack (Dimension-DxWxH – 800x1000x2070mm) as per specification No. WG-NAS/RAK |
| 94 | Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete asper specification no.FF- PA/MIC |
| 95 | Supplying, erecting, testing and commissioningrust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete. |
| 96 | Supplying, erecting, testing and commissioning of 2 core shielded sound cable complete asper specification no.FF- PA/MCC |
| 97 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x6 mm. M. S. flat with nut & bolts routed in wall complete. |
| 98 | Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire. extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class ofFIRE complete. |
| 99 | Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete. |
| 100 | Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories ) (Non CSR Approved by S.E.Office ,mumbaivide T.Sletterno- 108Date- 13/01/2022 ) |
| 101 | Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4\" x 3\" x 3\"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x340 33 Hinged Metal Fire Door 120 min fire Rated(Non-Csr) |
| 102 | Supply installation testing and commissioning of Fire Curtains with Galvanized MS powder coated head top box of suitable size, Powder coated side guides (100mm x 50 mm) and bottom bars with Gravity fail safe DC motors one per roller for curtain up operation with standard battery back-up fixed into 76/88 mm steel rollers with FAB690PU fabric must be according to DIN EN 13501-1 and stainless steel reinforced glass fibre with fire-retardant aluminum pigmented polyurethane coating, with its control panel and all installation assemblies & accessories required to complete the installation. The operation shall be suitable for dedicated 230 volts UPS, 50 Hz AC supply. Complete system tested in accordance with EN 1634-1 and EN 12101-1 (foar minimum 120 minutes integrity & tested at 1000°C) with CE certificate from European Notified Body. Both test reports EN 1634-1 & EN 12101-1 must be according to the requirement of particular project, if single roller curtain is there then single roller certificates and double roller curtain is there than double roller certificates must be submitted accordingly. The fire curtain must be according to Classification of Fire Resistance Performance in Accordance with EN 13501-2: 2016. The manufacturer’s valid EN certification for oversized fire curtains according to EN 15269-11 covering the sizes of offered fire curtains as per BOQ, should be available. Each Fire Curtain shall have independent control Panel suitable for 230V AC supply, provision to integrate with Fire signal, and battery backup. The emergency retract switch shall be provided on both sides of curtain. The Fire curtain shall reset automatically when fire control panel is reset. Fabric and all components sourced from the original manufacturer who has valid type test certificate of the fire curtain and third-party quality surveillance audit as per above standards including oversize certification according to applicable EN standards. The scope also includes fabrication, supply and installation of closed MS sections corner supports for fixing side channels, design suitable for stability and integrity with two hours fire rating, wherever required for full height of Fire curtain, as per approved design, duly finished with powder coating of finish matching toside channels of fire curtains.All the required test / certificates must be less than 5 Years validity. No mirror certificates allowedInstallation: The fire curtain has fixing options to suit all types of ceiling configurations and can be integrated into either a suspended or a solid ceiling. It remains hidden until required. Upon receiving a signal from the fire detection system or on loss of power with the gravity fail safe system, the curtain automatically unwinds to its operational position. |
| 103 | Supplying and erecting PVC trunking (PVC casing-n-capping)ofsize25 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 104 | Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 105 | Supplying and erectingmodular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete. |
| 106 | Supplying and erectingmodular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete. |
| 107 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3module duly erected. |
| 108 | Carrying out core cutting of size 3\" to 5\" dia x 15\" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. |
| 109 | Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthe position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached). |
| 110 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU(for booster Pump) |
| 111 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nosmain fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing. |
| 112 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/m x 40 m=0 kg) |
| 113 | Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat ofprimer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP |
| 114 | For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic.....for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add Rs….... |
| 115 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm diawith necessary fittings complete asper specification no. FF-PP |
| 116 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete asper specification no. FF-PP |
| 117 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete asper specification no. FF-PP |
| 118 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete asper specification no. FF-PP |
| 119 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete asper specification no. FF-PP |
| 120 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete asper specification no. FF-PP |
| 121 | Supplying anderecting100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR(open area Ratio) forpositive suction complete asper specification no. FF-VL/ELS |
| 122 | Supplyinganderecting100mm dia.cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV |
| 123 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size completewith PN16 pressure rating, asper specification no. FF-VL/BFV |
| 124 | Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, asperspecification no. FF-VL/BFV |
| 125 | Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete asper specification no. FF-VL/BFV |
| 126 | Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. completeasper specification no. FF-VL/BFV |
| 127 | Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete asper specification no. FF-VL/NRV |
| 128 | Supplying&erectinggunmetal gatevalveof size25 mmdia complete asper specification no. FF-VL/GV |
| 129 | Supplying anderectingstainless steel single outlethydrantvalve fitted with necessaryaccessories complete asper specification no. FF-VL/HV. |
| 130 | Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene(Polyhose)along with necessary accessories complete asper specification no. FF-FFA/HV |
| 131 | Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m inlength, fitted with necessary accessories complete asper specification no. FF-FFA/RRL |
| 132 | Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as perspecifications no. FF-FFA/NZ |
| 133 | Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete asper specification no.FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos. |
| 134 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve,erected with provided G.I. pipe, elbow etc. complete asper specification no. FF-FFA/PG |
| 135 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at everysingle outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant). |
| 136 | Supplying and erecting M.S./CRCA cabinet for housingFloorHydrant valve,hosepipe, hosereeland branch pipe(size 1000 x 736 x 736 mm.) made from 16 SWG sheetand angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8\"x6\") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe). |
| 137 | Supplying, installing, testing and commissioning ofmicro processor based intelligent addressable main fire alarm panel, central processing unit with the 8 loop capacity and capable of supporting upto 250 devices and detectorsper loop,with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, IS 2189: 2008, EN 54 & VDS / FM/UL864(10th edition)with 3 years replacement warranty FF-AFAS/CP |
| 138 | Supplying, installing, testing and commissioning ofrepeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 orUL approvedwith 3 years equipment replacement warranty FF-AFAS/RP |
| 139 | Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or ULApproved with 3 years equipment replacement warranty FF-AFAS/SD |
| 140 | Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area\"s etc. with 3 years equipment replacement warrantyIS : 2175 - 1988 reaffirmed 2000,IS 15908:2021standards FF-AFAS/SD. |
| 141 | Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with \"Break Glass\" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listedwith 3 years equipment replacementwarrantyFF-AFAS/MCP. |
| 142 | Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays,EN 54 or UL Listed FF-AFAS/CRM |
| 143 | Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacementwarranty conforming toIS 5051Part 2 (Sec 1 to 3) : 1982 Reed relaysFF-AFAS/MM |
| 144 | Supplying, installing, testing and commissioning of addressable fire isolator module complete as required.EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM |
| 145 | Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage rangeEN 54, conforming to IS 2189: 2008, IS 15908:2021standards with 3 years equipment replacement warranty FF-AFAS/SSH. |
| 146 | Supplying, installing, testing and commissioningFR, XLPE armouredcable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete asper specification no. CB-LT/CU |
| 147 | Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230VoltsA.C. / 12VoltsD.C. supply complete asper specification no. FF- PA/AFR |
| 148 | Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete asper specification no. FF-PA/SOC |
| 149 | Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to+55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete asper specification no.FF- PA/MIC |
| 150 | Supplying, erecting, testing and commissioningrust free microphone floor stand of chrome plating/powder coating orS.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete. |
| 151 | Supplying, erecting, testing and commissioning of 2 core shielded cable complete asper specification no.FF- PA/MCC |
| 152 | Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessaryfittings as per specifications having 1000mm long with UL/FM |
| 153 | Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½\") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflectordisc of conventional construction complete as per specification no. FF-SPR. |
| 154 | Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½\") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS |
| 155 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in |
| 156 | Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete. |
| 157 | Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class ofFIRE complete. |
| 158 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 186 =38 Nos) |
| 159 | Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables up tovoltage level1.1Kv cable complete as per specification No. CW-EXN-CTR |
| 160 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total (6.9+5.82)= 12.72 Cu-M |
| 161 | Supplying and erecting of fire Exit & Eire Exinguisher signlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories |
| 162 | Supply, Installation, testing of zinc aluminite fire water storage tank having capacity 20 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion, excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC). |
| 163 | Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4\" x 3\" x 3\"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated |
| 164 | Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 165 | Supplying and erectingHMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG- MA/CC. |
| 166 | Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 167 | Supplying and erecting mains with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specificationNo: WG-MA/BW |
| 168 | Supplying and erecting mains with 2x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places as per specification No: WG-MA/BW |
| 169 | Supplying and erecting mains with 1x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as perspecification No: WG-MA/BW |
| 170 | Supplying and erecting mains with 2x2.5 sq.mmFRLSH copper PVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 171 | Supplying and erecting mains with 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 172 | Point wiring for light/fan/bell in 20 mmFRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire withflush type switch and requiredaccessories as per specification No: WG-PW/SW |
| 173 | Point wiring for light/bell/exhaust fan in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and requiredaccessories as per specification No: WG- PW/SW. |
| 174 | Point wiring for independent plug in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E ) FRLSH grade copper wire, modular type switch,earthing and required accessories as per specification No: WG-PW/SW |
| 175 | Supplying and erecting single pole and neutral distributionboard (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB |
| 176 | Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAhLithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty. |
| 177 | Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades,wire mesh, duly erected, complete. |
| 178 | Supplying and erectingmodular type switch 16Aduly erected on provided plate and boxwith wiring connections complete. |
| 179 | Supplying and erectingmodular type 3 pin 6 / 16Amultisocket with safety shutter,dulyerected on provided plate and box with wiring connections complete. |
| 180 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3module duly erected. |
| 181 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 95sq.mm. aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 182 | Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeasper specification no. CB-LT/AL(main incoming cable to main fire panel). |
| 183 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid inprovided trench/ pipeas per specification no. CB-LT/CU(for booster Pump) |
| 184 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 185 | Supplying & laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 186 | Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW- SWR/MCCB. Note : For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. Hence 18563 X 20%= 3712.60/- |
| 187 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 146 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete. |
| 188 | Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mmwidth & 100 mm height comprising all required standard accessories. |
| 189 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories. |
| 190 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 400 mmwidth & 100 mm height comprising all required standard accessories. |
| 191 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel enginepump).= total 6 nos of earthing. |
| 192 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As perspecification no EA-EP.(25x5) (1kg/m x 60 m=60 kg) |
| 193 | Supplying, installation, testing and commissioning ofmain fire pump(MFP / EP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 75kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levellingcomplete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, asper specification no. FF- MFP/SSC/EP |
| 194 | Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 110 to 90 m head driven by electric motor415 volts, 3 phase 50 Hz, AC supply of 11 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat ofprimer (ISC code 536 as per IS 2932 of 2003) complete, asper specification no. FF-MFP/JP |
| 195 | Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat ofprimer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP |
| 196 | Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by 110 HP or suitable HP capacity diesel engine at required working speed suitable for automatic operation and consisting of following :(a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520.(b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine , exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP |
| 197 | Supplying, erecting, testing & commissioning of fire pump control panel (FCP) of cubical construction, floor mounted type, fabricated from minimum 2 mm thick CRCA sheet, compartmentalised with hinged lockable doors, with enclosure protection class IP54, duly powder coated or painted with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003), cable alley, interconnection with suitable size solid copper busbar strip of adequate size for all power connections having switchgears and accessories, mountings and internal wiring with adequate size copper conductor cable, earth terminals, numbering etc. complete in all respect, suitable for satisfactory operation of main fire pump and jockey (pressurisation) pumps (1working+1standby) with necessary accessories, wiring & cabling along with allied accessories with following incoming and outgoings, suitable for automatic & manual operation on 415V, 3 phase, 50Hz ac supply as per specificationsthe capacity of electric motor driven pump are as followsa. Main fire pump(MFP) having capacity of 22kW 1no (1 working)b. Jockey pump(JP) capacity of suitable capacity 2 nos(1 working +1 standby, alternate run per start in auto mode)comprises of the following features & switchgears:1. Main incomer FP SFU having rotary handle with HRC fuses of suitable rating.2. Electrolytic grade copper strips for busbar of suitable sizes for main incomer and branches to motor SFU\"s, starters & outgoing terminals with necessary accessories like stainless steel nut bolts with spring washers for connections, mounted on required no of epoxy or porcelain support insulators of suitable ratings etc.3. Individual pump TPN SFU having rotary handlewith HRC fuses of suitable rating. 4. Digital voltmeter & ammeter & RYB indicating lamps & push buttons & SPP, O/L & phase reversal protection with emergency stop switch.5. TPN SPD 100kA Type 1 +2 tested.6. Required pressure transducer with pressure indication on panel with cabling required for monitoring & automatic operation of fire pumps.7. System controller to control operation of main electric fire pump, jockey (pressurization) pumps in sequence with interlocking for operation of pumps as perspecification with automatic/manual operation with selector switch & alternate run of standby Pumps consisting of relays, timers. sensors, annunciation window for fault indication, complete as per specification.8. Suitable capacity electric motor starters for all individual pumps with necessary push buttons & indications.9.Siren of required capacity to be activated when main pump starts & allied accessories as per requirements of local CFO or as directed by engineer in charge.10.Danger board as per IS.11.Spare HRC fuses minimum 2nos of each individual rating with required bakelite fuse holder for main & jockey fire pumps MFP=(1working), JP = (1working+1standby, alternate run per start in auto mode) complete panel, asper specification no. FF-MFP/ECP . Basic price ( 13-5-1) 182320+(A-5) For main electric motor driven fire hydrant system pump of 75kW capacity & relevant capacity jockey pump add Rs…. 99983 ( For Main pump for 75kw) +(B-6) For main electric motor driven fire sprinkler system pump of 75kW capacity (1Working) & relevant capacity jockey pumps (1working+1standby, alternate run per start in auto mode,add Rs…. 304846 +(D) For addition of standby main diesel engine driven fire pump (1 standby), add as follows in the basic cost of Item no 13-5-1 towards required 12/24 v battery charger and diesel engine starter along with necessary accessories, indicators etc. with necessary interlocking and updation of control logic with interlocking for operation of pumps MFP for main (1working+1standby mode) & jockey fire pumps (1working+1standby, alternate run per start in auto mode) , add Rs.......The control for diesel engine comprises of automatic/manual selector switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode indicating lamp for high/ low Lub. oil pressure, high water temp and engine on indication battery charger suitable for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC voltmeter, and 0-20 A DC ammeter with all standard relays and accessories required for automatic operation of diesel engine with interlocking for operation of main fire pumps Rs68381 Total =655530 |
| 198 | For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic.....for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add Rs….... |
| 199 | Supplying anderecting100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) forpositive suction complete asper specification no. FF-VL/ELS( 2 nos for jockey pump + 2 nos for booster pump=4 Nos. |
| 200 | Supplying anderecting200 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, screen of SS end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete asper specification no. FF- VL/ELS ( 1 nos main pump+1 nos forsprinkler pump+ 1 for disel pump= 3 Nos). |
| 201 | Supplyinganderecting100mm dia.cast iron double flange sluicevalvecompletewith PN16 pressure rating, asper specification no. FF-VL/SV |
| 202 | Supplyinganderecting200mm dia.cast iron double flange sluicevalvecompletewith PN16 pressure rating, asper specification no. FF-VL/SV |
| 203 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, asper specification no. FF-VL/BFV |
| 204 | Supplying & erecting cast iron double flange butterfly valve of size 75/80 mm dia. completeasper specification no. FF-VL/BFV |
| 205 | Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. completeasper specification no. FF-VL/BFV |
| 206 | Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. completeasper specification no. FF-VL/BFV |
| 207 | Supplying & erecting cast iron double flange butterfly valve of size 200 mm dia. completeasper specification no. FF-VL/BFV |
| 208 | Supplying and erecting cast iron double flange ball type NRV of size 75mm/80 mm dia complete asper specification no. FF- VL/NRV |
| 209 | Supplying and erecting cast iron double flangeball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV |
| 210 | Supplying and erecting cast iron double flangeball type NRV of size 150 mm dia complete as per specification no. FF-VL/NRV |
| 211 | Supplying and erecting cast iron double flangeball type NRV of size 200 mm dia complete as per specification no. FF-VL/NRV |
| 212 | Supplying&erectinggunmetal gatevalve of size25 mmdia complete asperspecification no. FF-VL/GV |
| 213 | Supplying and installing air vessel of 300 mm dia1.5min heightM.S.tank installed inside pump house / on terrace complete asper specification no. FF-FFA/ACT(1 nos for hydrant + 1 nos for sprinkler= 2 nos). |
| 214 | Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete asper specification no.FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos. |
| 215 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete asper specification no. FF-FFA/PG |
| 216 | Supplying and erecting12/15 mm dia pressureswitchwith provided isolation valve, G.I. nipple, elbow, etc complete as perspecification no. FF-FFA/PS |
| 217 | Carrying out core cutting of size 3\" to 5\" dia x 15\" length in the C.C./rock/stone wall with the help of specialized core cutting machine inproper manner and finishing the site as original. |
| 218 | Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables uptovoltage level1.1Kv cable complete as per specification No. CW-EXN-CTR |
| 219 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps(1.2x 1.2 x0.8)= 1.15 x 5 = 5.76 cum for overhead tank foundation (1.8 x 1.8 x 0.3)=0.972 x 5=4.86 cum total (6.9+5.82)= 10.62 Cu-M. For Hydrant Line Pedastal of size 1.2 m X 0.6 m X 0.6 m = 0.432 cum per pedastal , total terrace overhead ring line length 720 m /pedastal support will be at 4 m each ,hence total qty would be - 80/4 = 20 Nos ,so 20 X 0.432 = 8.68 cum ( pump foundation 10.62 cum + Pedastal 8.68 cum =19.3 cum total) |
| 220 | Supply,Instlaation,testingzincaluminite fire water storage tank having capacity 20 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC). |
| 221 | Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthe position with necessary materials duly paintedwith one coat of red oxide and two coats of enamelpaint to match theswitchgears or as per directions by the authority ( separate Iron work calculation sheet attached). |
| 222 | Supplying anderectingstainless steel single outlet hydrant valve fitted with necessary accessories complete asper specification no. FF-VL/HV. |
| 223 | Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene(Polyhose)along with necessary accessories complete asper specification no. FF-FFA/HV |
| 224 | Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m inlength, fitted with necessary accessories complete asper specification no. FF-FFA/RRL |
| 225 | Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzlecomplete as per specifications no. FF-FFA/NZ |
| 226 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at everysingle outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant). |
| 227 | Supplying and erecting M.S./CRCA cabinet for housing single hydrant valveof size ( 400 x 400 x 400)mm or hose pipe box of size ( 600 x 600 x 200)mmmade from min. 1.5 mm thick CRCA sheet with angle iron work of min. of size (25 x 25 x 4) mmhaving front doors with viewing glass of size (200x150) mmandlockingarrangement with necessary fixing material such as rubber biddingetc. dulypainted in post box red colour( Code 538 of IS 5) |
| 228 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete asperspecification no. FF-PP |
| 229 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete asperspecification no. FF-PP |
| 230 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete asper specification no. FF-PP |
| 231 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete asper specification no. FF-PP |
| 232 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete asperspecification no. FF-PP |
| 233 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete asper specification no. FF-PP |
| 234 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 200 mm dia with necessary fittings complete asper specification no. FF-PP |
| 235 | Supplying&erectinggunmetal gatevalve of size20 mmdia complete asper specification no. FF-VL/GV |
| 236 | Supplying&erectinggunmetal gatevalve of size25 mmdia complete asper specification no. FF-VL/GV |
| 237 | Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessary fittings as per specifications having 1000mmlong with UL/FM |
| 238 | Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½\") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflectordisc of conventional construction complete as per specification no. FF-SPR. |
| 239 | Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½\") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS |
| 240 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Approx 780 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 30 =30 Nos) |
| 241 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting upto 250 devices and detectorsper loop,with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipmentvia a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021,,IS 2189: 2008, EN 54 & VDS / FM/UL864 (10th edition)with 3 years replacement warranty FF-AFAS/CP. |
| 242 | Supplying, installing, testing and commissioning ofrepeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 orUL approvedwith 3 years equipment replacement warranty FF-AFAS/RP |
| 243 | Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or ULApproved with 3 years equipment replacement warranty FF-AFAS/SD |
| 244 | Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area\"s etc. with 3 years equipment replacement warrantyIS : 2175 - 1988 reaffirmed 2000,IS 15908:2021standards FF-AFAS/SD. |
| 245 | Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with \"Break Glass\" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listedwith 3 years equipment replacement warranty FF-AFAS/MCP. |
| 246 | Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays,EN 54 or UL Listed FF- AFAS/CRM |
| 247 | Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacementwarranty conforming toIS 5051Part 2 (Sec 1 to 3) : 1982 Reed relaysFF-AFAS/MM |
| 248 | Supplying, installing, testing and commissioning of addressable fire isolator module complete as required.EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM |
| 249 | Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage rangeEN 54, conforming to IS 2189: 2008, IS 15908:2021standards with 3 years equipment replacement warranty FF-AFAS/SSH. |
| 250 | Supplying, installing, testing and commissioningFR, XLPE armouredcable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete asper specification no. CB-LT/CU |
| 251 | Supplying, installing, testing and commissioningFR, XLPE armouredcable 8 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete asper specification no.CB-LT/CU |
| 252 | Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230VoltsA.C. / 12VoltsD.C. supply complete asper specification no. FF- PA/AFR |
| 253 | Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete asper specification no. FF-PA/SOC |
| 254 | Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete asper specification no.FF- PA/MIC |
| 255 | Supplying, erecting, testing and commissioningrust free microphone floor stand of chrome plating/powder coating orS.S. material , 500 mm to 1500 mmheight and sturdy mechanism ensuring trouble free movement complete. |
| 256 | Supplying, erecting, testing and commissioning of 2 core shielded sound cable complete asper specification no.FF- PA/MCC |
| 257 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x6 mm. M. S. flat with nut & bolts routed in wall complete. |
| 258 | Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+)55 C kg capacity suitable for A,B,C class of FIRE complete. |
| 259 | Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete. |
| 260 | Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories ) (Non CSRApproved by S.E.Office ,mumbaivide T.S letterno- 108Date- 13/01/2022 ) |
| 261 | Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4\" x 3\" x 3\"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated |
| 262 | Supplying and erecting PVC trunking (PVC casing-n-capping)ofsize25 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 263 | Supplying and erectingHMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG- MA/CC. |
| 264 | Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 265 | Supplying and erecting mains with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 266 | Supplying and erecting mains with 2x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 267 | Supplying and erecting mains with 1x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 268 | Supplying and erecting mains with 2x2.5 sq.mmFRLSH copper PVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 269 | Supplying and erecting mains with 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 270 | Point wiring for light/fan/bell in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire with flush type switch and requiredaccessories as per specification No: WG-PW/SW |
| 271 | Point wiring for light/bell/exhaust fan in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and requiredaccessories as per specification No: WG- PW/SW. |
| 272 | Point wiring for independent plug in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E ) FRLSH grade copper wire, modular type switch,earthing and required accessories as per specification No: WG-PW/SW |
| 273 | Supplying and erecting single pole and neutral distributionboard (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mmthickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB |
| 274 | Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAhLithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty. |
| 275 | Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete. |
| 276 | Supplying and erectingmodular type switch 16Aduly erected on provided plate and boxwith wiring connections complete. |
| 277 | Supplying and erectingmodular type 3 pin 6 / 16Amultisocket with safety shutter,dulyerected on provided plate and box with wiring connections complete. |
| 278 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3module duly erected. |
| 279 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 95sq. mm. aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 280 | Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL(main incoming cable to main fire panel). |
| 281 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU(for booster Pump) |
| 282 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 283 | Supplying & laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 284 | Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW- SWR/MCCB. Note : For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. Hence 18563 X 20%= 3712.60/- |
| 285 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 146 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete. |
| 286 | Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mmwidth & 100 mm height comprising all required standard accessories. |
| 287 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mmwidth & 100 mm height comprising all required standard accessories. |
| 288 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 400 mmwidth & 100 mm height comprising all required standard accessories. |
| 289 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel enginepump).= total 6 nos of earthing. |
| 290 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As perspecification no EA-EP.(25x5) (1kg/m x 60 m=60 kg) |
| 291 | Supplying, installation, testing and commissioning ofmain fire pump(MFP / EP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 75kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levellingcomplete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, asper specification no. FF- MFP/SSC/EP |
| 292 | Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 110 to 90 m head driven by electric motor415 volts, 3 phase 50 Hz, AC supply of 11 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, asper specification no. FF-MFP/JP |
| 293 | Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by 110 HP or suitable HP capacity diesel engine at required working speed suitable for automatic operation and consisting of following :(a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520.(b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine , exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP |
| 294 | Supplying, erecting, testing & commissioning of fire pump control panel (FCP) of cubical construction, floor mounted type, fabricated from minimum 2 mm thick CRCA sheet, compartmentalised with hinged lockable doors, with enclosure protection class IP54, duly powder coated or painted with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003), cable alley, interconnection with suitable size solid copper busbar strip of adequate size for all power connections having switchgears and accessories, mountings and internal wiring with adequate size copper conductor cable, earth terminals, numbering etc. complete in all respect, suitable for satisfactory operation of main fire pump and jockey (pressurisation) pumps (1working+1standby) with necessary accessories, wiring & cabling along with allied accessories with following incoming and outgoings, suitable for automatic & manual operation on 415V, 3 phase, 50Hz ac supply as per specificationsthe capacity of electric motor driven pump are as followsa. Main fire pump(MFP) having capacity of 22kW 1no (1 working)b. Jockey pump(JP) capacity of suitable capacity 2 nos(1 working +1 standby, alternate run per start in auto mode)comprises of the following features & switchgears:1. Main incomer FP SFU having rotary handle with HRC fuses of suitable rating.2. Electrolytic grade copper strips for busbar of suitable sizes for main incomer and branches to motor SFU\"s, starters & outgoing terminals with necessary accessories like stainless steel nut bolts with spring washers for connections, mounted on required no of epoxy or porcelain support insulators of suitable ratings etc.3. Individual pump TPN SFU having rotary handle with HRC fuses of suitable rating.4. Digital voltmeter & ammeter & RYB indicating lamps & push buttons & SPP, O/L & phase reversal protection with emergency stop switch.5. TPN SPD 100kA Type 1 +2 tested.6. Required pressure transducer with pressure indication on panel with cabling required for monitoring & automatic operation of fire pumps.7. System controller to control operation of main electric fire pump, jockey(pressurization) pumps in sequence with interlocking for operation of pumps as per specification with automatic/manual operation with selector switch & alternate run of standby Pumps consisting of relays, timers. sensors, annunciation window for fault indication, complete as per specification.8. Suitable capacity electric motor starters for all individual pumps with necessary push buttons & indications.9.Siren of required capacity to be activated when main pump starts & allied accessories as per requirements of local CFO or as directed by engineer in charge.10.Danger board as per IS.11.Spare HRC fuses minimum 2nos of each individual rating with required bakelite fuse holder for main & jockey fire pumps MFP=(1working), JP = (1working+1standby, alternate run per start in auto mode) complete panel, asper specification no. FF-MFP/ECP . Basic price ( 13-5-1) 182320+(A-5) For main electric motor driven fire hydrant system pump of 75kW capacity & relevant capacity jockey pump add Rs…. 99983 ( For Main pump for 75kw) +(B-6) For main electric motor driven fire sprinkler system pump of 75kW capacity (1Working) & relevant capacity jockey pumps (1working+1standby, alternate run per start in auto mode,add Rs…. 304846 +(D) For addition of standby main diesel engine driven fire pump (1 standby), add as follows in the basic cost of Item no 13-5-1 towards required 12/24 v battery charger and diesel engine starter along with necessary accessories, indicators etc. with necessary interlocking and updation of control logic with interlocking for operation of pumps MFP for main (1working+1standby mode) & jockey fire pumps (1working+1standby, alternate run per start in auto mode) , add Rs.......The control for diesel engine comprises of automatic/manual selector switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode indicating lamp for high/ low Lub. oil pressure, high water temp and engine on indication battery charger suitable for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC voltmeter, and 0-20 A DC ammeter with all standard relays and accessories required for automatic operation of diesel engine with interlocking for operation of main fire pumps |
| 295 | Supplying anderecting100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SSscreen, endconnection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS ( 2 nos for jockey pump + 2 nos for booster pump=4 Nos. |
| 296 | Supplying anderecting200 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, screen of SS end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF- VL/ELS ( 1 nos main pump+1 nos for sprinkler pump+ 1 for disel pump= 3 Nos). |
| 297 | Supplyinganderecting100mm dia.cast iron double flange sluicevalvecomplete with PN16 pressure rating, asperspecification no. FF-VL/SV |
| 298 | Supplyinganderecting150mm dia.cast iron double flange sluicevalvecompletewith PN16 pressure rating, asper specification no. FF-VL/SV |
| 299 | Supplyinganderecting200mm dia.cast iron double flange sluicevalvecompletewith PN16 pressure rating, asper specification no. FF-VL/SV |
| 300 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, asper specification no. FF-VL/BFV |
| 301 | Supplying & erecting cast iron double flange butterfly valve of size 75/80 mm dia. completeasper specification no. FF-VL/BFV |
| 302 | Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. completeasper specification no. FF-VL/BFV |
| 303 | Supplying & erecting cast iron double flangebutterfly valve of size 150 mm dia. complete asper specification no. FF-VL/BFV |
| 304 | Supplying & erecting cast iron double flange butterfly valve of size 200 mm dia. complete asper specification no. FF-VL/BFV |
| 305 | Supplying and erecting cast iron double flange ball type NRV of size 75mm/80 mm dia complete asper specification no. FF- VL/NRV |
| 306 | Supplying and erecting cast iron double flangeball type NRV of size 150 mm dia complete as per specification no. FF-VL/NRV |
| 307 | Supplying and erecting cast iron double flangeball type NRV of size 200 mm dia complete as per specification no. FF-VL/NRV |
| 308 | Supplying&erectinggunmetal gatevalve of size20 mmdia complete asper specification no. FF-VL/GV |
| 309 | Supplying&erectinggunmetal gatevalve of size25 mmdia complete asperspecification no. FF-VL/GV |
| 310 | Supplying and erecting 150 mm dia firebrigade header suitable for supplying water in fire tank complete asper specification no. FF-FA/FBC |
| 311 | Supplying and erecting fire brigade header ( Siamese connection ) of 150 mm dia, for supplying water in fire tank complete asper specification no. FF-FA/FMC |
| 312 | Supplying and installing air vessel of 300 mm dia1.5min heightM.S.tank installed inside pump house / on terrace complete asper specification no. FF-FFA/ACT(1 nos for hydrant + 1 nos for sprinkler= 2 nos). |
| 313 | Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete asper specification no.FF-FFA/ARV. |
| 314 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve,erected with provided G.I. pipe, elbow etc. complete asper specification no. FF-FFA/PG |
| 315 | Supplying and erecting12/15 mm dia pressureswitchwith provided isolation valve,G.I. nipple, elbow, etc complete asperspecification no. FF-FFA/PS |
| 316 | Carrying out core cutting of size 3\" to 5\" dia x 15\" length in the C.C./rock/stone wall with the help of specialized core cutting machine inproper manner and finishing the site as original. |
| 317 | Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3mtr width as per IS for laying provided cables uptovoltage level1.1Kv cable complete as per specification No. CW-EXN-CTR |
| 318 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps(1.2x 1.2 x0.8)= 1.15 x 5= 5.76 cum for overhead tank foundation (1.8 x 1.8 x 0.3)=0.972 x 5=4.86 cum total(6.9+5.82)= 10.62 Cu-M. For Hydrant Line Pedastal of size 1.2 m X 0.6 m X 0.6 m =0.432 cum per pedastal , Total ring line length 2984 m /pedastal support will be at 4 m each,hence total qty would be - 2984/4 = 746 Nos,so 746 X 0.432 = 322.28 cum ( pump foundation 10.62 cum + Pedastal 322.28 cum= 332.9 cum total) |
| 319 | Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthe position with necessary materials duly painted with one coat of red oxide and two coats of enamelpaint to match theswitchgears or as per directions by the authority ( separate Iron work calculation sheet attached). |
| 320 | Supplying anderectingstainless steel single outlet hydrant valve fitted with necessary accessories complete asper specification no. FF-VL/HV. |
| 321 | Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL |
| 322 | Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzlecomplete as per specifications no. FF-FFA/NZ |
| 323 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specificationno. FF-FFA/OP (For Internal Hydrant). |
| 324 | Supplying and erecting M.S./CRCA cabinet for housingFloorHydrant valve,hosepipe, hosereeland branch pipe(size 1000 x 736 x 736 mm.) made from 16 SWG sheetand angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8\"x6\") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) |
| 325 | Supplying and erectingG.I. pipe‘C’ classERW25 mm dia with necessary fittings complete asper specification no. FF-PP |
| 326 | Supplying and erectingG.I. pipe‘C’ classERW50 mm dia with necessary fittings complete asper specification no. FF-PP |
| 327 | Supplying and erecting G.I. pipe ‘C’ classERW75/80 mm dia with necessary fittings complete asper specification no. FF-PP |
| 328 | Supplying and erectingG.I. pipe‘C’ classERW100 mm dia with necessary fittings complete asper specification no. FF-PP |
| 329 | Supplying and erectingG.I. pipe‘C’ class ERW150 mm dia with necessary fittingscomplete asper specification no. FF-PP |
| 330 | Supplying and erectingG.I. pipe‘C’ class ERW200 mm dia with necessary fittingscomplete asper specification no. FF-PP |
| 331 | Providing coating of bitumen paint &4mm thick wrapping for underground 150 mm ringmain of fire fighting system. |
| 332 | Providing coating of bitumen paint & 4mmthick wrapping for underground 200 mm ring main of fire fighting system. |
| 333 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residualopenings shall be closed with filler, as per specification no FF-FRM. |
| 334 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed inwall complete. |
| 335 | Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor-numtber in words &syslem(Fire Exiinguisher& Accessories |
| 336 | Making cement concrete foundation including excavation(60x 60x 150) cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metalwith necessary curing and finishing complete.(for stay). |
| 337 | Supplying and erecting Gas Suppression system (Novec 1230-FK1230 Gas Suppression system with CCOE cylinder one no.32 liter capacity with filled Gas, Electrical,Manual,Nozzle and Gas Release panel with Smoke detector, as per Schedule-CSr No.43 specification. |
| 338 | Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 339 | Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places as per specification No: WG-MA/BW |
| 340 | Supplying and erectingmodular type switch6A / 10A duly erected on provided plate and box with wiring connections complete. |
| 341 | Supplying and erectingmodular type 3 pin 6 / 16Amultisocket with safety shutter,dulyerected on provided plate and box with wiring connections complete. |
| 342 | Supplying and erecting PVC Surface modularswitch box with double mounting plate for 3 module duly erected. |
| 343 | Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthe position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by theauthority ( separate Iron work calculation sheet attached). |
| 344 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU(for booster Pump) |
| 345 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel enginepump).= total 6 nos of earthing. |
| 346 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/m x 40m=40 kg) |
| 347 | Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP |
| 348 | For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic.....for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add Rs….... |
| 349 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete asper specification no. FF-PP |
| 350 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete asper specification no. FF-PP |
| 351 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete asper specification no. FF-PP |
| 352 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete asperspecification no. FF-PP |
| 353 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete asperspecification no. FF-PP |
| 354 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete asper specification no. FF-PP |
| 355 | Supplying anderecting100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suctioncomplete asper specification no. FF-VL/ELS |
| 356 | Supplyinganderecting100mm dia.cast iron double flange sluicevalvecomplete with PN16 pressure rating, asper specification no. FF-VL/SV |
| 357 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, asper specification no. FF-VL/BFV |
| 358 | Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, asper specification no. FF-VL/BFV |
| 359 | Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. completeasper specification no. FF-VL/BFV |
| 360 | Supplying & erecting cast iron double flangebutterfly valve of size 150 mm dia. complete asper specification no. FF-VL/BFV |
| 361 | Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV |
| 362 | Supplying&erectinggunmetal gatevalve of size25 mmdia complete asperspecification no. FF-VL/GV |
| 363 | Supplying anderectingstainless steel single outlet hydrant valve fitted with necessary accessories complete asper specification no. FF-VL/HV. |
| 364 | Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene(Polyhose)along with necessary accessories complete asper specification no. FF-FFA/HV |
| 365 | Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL |
| 366 | Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzlecomplete as per specifications no. FF-FFA/NZ |
| 367 | Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete asper specification no.FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos. |
| 368 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve,erected with provided G.I. pipe, elbow etc. complete asper specification no. FF-FFA/PG |
| 369 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant). |
| 370 | Supplying and erecting M.S./CRCA cabinet for housingFloorHydrant valve,hosepipe, hosereeland branch pipe(size 1000 x 736 x 736 mm.) made from 16 SWG sheetand angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8\"x6\") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe). |
| 371 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting upto 250 devices and detectorsper loop,with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021,,IS 2189: 2008, EN 54 & VDS / FM/UL864(10th edition)with 3 years replacement warranty FF-AFAS/CP. |
| 372 | Supplying, installing, testing and commissioning ofrepeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approvedwith 3 years equipment replacement warranty FF-AFAS/RP |
| 373 | Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or ULApproved with 3 years equipment replacement warranty FF-AFAS/SD |
| 374 | Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area\"s etc. with 3 years equipment replacement warrantyIS : 2175 - 1988 reaffirmed 2000,IS 15908:2021standards FF-AFAS/SD. |
| 375 | Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with \"Break Glass\" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 orUL listedwith 3 years equipment replacement warranty FF-AFAS/MCP. |
| 376 | Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) :1982 reed relays,EN 54 or UL Listed FF- AFAS/CRM |
| 377 | Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming toIS 5051Part 2 (Sec 1 to 3) : 1982 Reed relaysFF-AFAS/MM |
| 378 | Supplying, installing, testing and commissioning of addressable fire isolator module complete as required.EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming toIS5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM |
| 379 | Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage rangeEN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacementwarrantyFF-AFAS/SSH. |
| 380 | Supplying, installing, testing and commissioningFR, XLPE armouredcable 2 core 1.5 sq.mm. copper conductor completeerected on wall/ ceiling complete asper specification no. CB-LT/CU |
| 381 | Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230VoltsA.C. / 12VoltsD.C. supply complete asper specification no. FF- PA/AFR |
| 382 | Supplying, erecting, testing and commissioning15 to 30 Watts soundcolumn or ceiling mounted complete asper specification no. FF-PA/SOC |
| 383 | Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to+55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete asper specification no.FF- PA/MIC |
| 384 | Supplying, erecting, testing and commissioningrust free microphone floor stand of chrome plating/powder coating orS.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete. |
| 385 | Supplying, erecting, testing and commissioning of 2 core shielded cablecomplete asper specification no.FF- PA/MCC |
| 386 | Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessaryfittings as per specifications having 1000mm long with UL/FM |
| 387 | Carrying out core cutting of size 3\" to 5\" dia x 15\" length in the C.C./rock/stone wall with the help of specialized core cutting machine inproper manner and finishing the site as original. |
| 388 | Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½\") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete asper specification no. FF-SPR. |
| 389 | Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½\") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete asper specification no. FF-SPR/SS |
| 390 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 =1 room X 38 =38 Nos) |
| 391 | Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables uptovoltage level1.1Kv cable complete as per specification No. CW-EXN-CTR |
| 392 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total(6.9+5.82)= 12.72 Cu-M |
| 393 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed inwall complete. |
| 394 | Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+)55 C kg capacity suitable for A,B,C class of FIRE complete. |
| 395 | Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories |
| 396 | Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class ofFIRE complete. |
| 397 | Supply, Installation, testing zinc aluminite fire water storage tank having capacity 10 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion, excavation , PCC which can load of tankincluding of 100% water.( for booster pump as per NBC). |
| 398 | Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4\" x 3\" x 3\"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated |
| 399 | Supplying and erecting PVC trunking (PVC casing-n-capping)ofsize25 mm with accessorieson wall/ceiling as perspecification No: WG-MA/CON. |
| 400 | Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places as per specification No: WG-MA/BW |
| 401 | Supplying and erecting modular type switch 6A / 10A duly erected on provided plate andbox with wiring connections complete. |
| 402 | Supplying and erectingmodular type 3 pin 6 / 16Amultisocket with safety shutter,duly erected on provided plate and box with wiringconnections complete. |
| 403 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3module duly erected. |
| 404 | Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthe position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by theauthority ( separate Iron work calculation sheet attached). |
| 405 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid inprovided trench/ pipeas per specification no. CB-LT/CU(for booster Pump) |
| 406 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing. |
| 407 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/mtr x 50 mtr=50 kg) |
| 408 | Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP |
| 409 | For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic.....for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add Rs….... |
| 410 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete asperspecification no. FF-PP |
| 411 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete asper specification no. FF-PP |
| 412 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete asper specification no. FF-PP |
| 413 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete asper specification no. FF-PP |
| 414 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete asper specification no. FF-PP |
| 415 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete asper specification no. FF-PP |
| 416 | Supplying anderecting100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR(open area Ratio) forpositive suction complete asper specification no. FF-VL/ELS |
| 417 | Supplyinganderecting100mm dia.cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV |
| 418 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size completewith PN16 pressure rating, asper specification no. FF-VL/BFV |
| 419 | Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, asperspecification no. FF-VL/BFV |
| 420 | Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete asper specification no. FF-VL/BFV |
| 421 | Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. completeasper specification no. FF-VL/BFV |
| 422 | Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete asper specification no. FF-VL/NRV |
| 423 | Supplying&erectinggunmetal gatevalveof size25 mmdia complete asper specification no. FF-VL/GV |
| 424 | Supplying anderectingstainless steel single outlethydrantvalve fitted with necessaryaccessories complete asper specification no. FF-VL/HV. |
| 425 | Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene(Polyhose)along with necessary accessories complete asper specification no. FF-FFA/HV |
| 426 | Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m inlength, fitted with necessary accessories complete asper specification no. FF-FFA/RRL |
| 427 | Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as perspecifications no. FF-FFA/NZ |
| 428 | Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete asper specification no.FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos. |
| 429 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve,erected with provided G.I. pipe, elbow etc. complete asper specification no. FF-FFA/PG |
| 430 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at everysingle outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant). |
| 431 | Supplying and erecting M.S./CRCA cabinet for housingFloorHydrant valve,hosepipe, hosereeland branch pipe(size 1000 x 736 x 736 mm.) made from 16 SWG sheetand angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8\"x6\") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe). |
| 432 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting upto 250 devices and detectorsper loop,with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021,,IS 2189: 2008, EN 54 & VDS / FM/UL864(10th edition)with 3 years replacement warranty FF-AFAS/CP. |
| 433 | Supplying, installing, testing and commissioning ofrepeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 orUL approvedwith 3 years equipment replacement warranty FF-AFAS/RP |
| 434 | Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or ULApproved with 3 years equipment replacement warranty FF-AFAS/SD |
| 435 | Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area\"s etc. with 3 years equipment replacement warrantyIS : 2175 - 1988 reaffirmed 2000,IS 15908:2021standards FF-AFAS/SD. |
| 436 | Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with \"Break Glass\" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listedwith 3 years equipment replacementwarrantyFF-AFAS/MCP. |
| 437 | Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays,EN 54 or UL Listed FF-AFAS/CRM |
| 438 | Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacementwarranty conforming toIS 5051Part 2 (Sec 1 to 3) : 1982 Reed relaysFF-AFAS/MM |
| 439 | Supplying, installing, testing and commissioning of addressable fire isolator module complete as required.EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM |
| 440 | Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage rangeEN 54, conforming to IS 2189: 2008, IS 15908:2021standards with 3 years equipment replacement warranty FF-AFAS/SSH. |
| 441 | Supplying, installing, testing and commissioningFR, XLPE armouredcable 2 core 1.5 sq.mm. copper conductor completeerected on wall/ ceiling complete asper specification no. CB-LT/CU |
| 442 | Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230VoltsA.C. / 12VoltsD.C.supply complete asper specification no. FF- PA/AFR |
| 443 | Supplying, erecting, testing and commissioning15 to 30 Watts sound column or ceiling mounted complete asperspecification no. FF-PA/SOC |
| 444 | Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to+55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete asper specification no.FF-PA/MIC |
| 445 | Supplying, erecting, testing and commissioningrust free microphone floor stand of chrome plating/powder coating orS.S. material , 500 mm to 1500 mmheight and sturdy mechanism ensuring trouble free movement complete. |
| 446 | Supplying, erecting, testing and commissioning of 2 core shielded cablecomplete asper specification no.FF- PA/MCC |
| 447 | Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessaryfittings as per specifications having 1000mm long with UL/FM |
| 448 | Carrying out core cutting of size 3\" to 5\" dia x 15\" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. |
| 449 | Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½\") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflectordisc of conventional construction complete as per specification no. FF-SPR. |
| 450 | Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½\") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS |
| 451 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 =1 room X 50 =50 Nos) |
| 452 | Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3mtr width as per IS for laying provided cables uptovoltage level1.1Kv cable complete as per specification No. CW-EXN-CTR |
| 453 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total(6.9+5.82)= 12.72 Cu-M |
| 454 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed inwall complete. |
| 455 | Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class ofFIRE complete. |
| 456 | Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class ofFIRE complete. |
| 457 | Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(FireExiinguisher& Accessories ) (Non CSR Approved by S.E.Office ,mumbaivide T.S letterno- 108Date- 13/01/2022 ) |
| 458 | Supply, Installation, testing zinc aluminite fire water storage tank having capacity 10 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion, excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC). |
| 459 | Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4\" x 3\" x 3\"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x340 33 Hinged Metal Fire Door 120 min fire Rated |
| 460 | Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 461 | Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places as per specification No: WG-MA/BW |
| 462 | Supplying and erectingmodular type switch6A / 10A duly erected on provided plate and box with wiring connections complete. |
| 463 | Supplying and erectingmodular type 3 pin 6 / 16Amultisocket with safety shutter,duly erected on provided plate and box with wiringconnections complete. |
| 464 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3module duly erected. |
| 465 | Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthe positionwith necessarymaterialsduly paintedwith one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached). |
| 466 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU(for booster Pump) |
| 467 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing. |
| 468 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As perspecification no EA-EP.(25x5) (1kg/m x 50 m=50 kg) |
| 469 | Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat ofprimer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP |
| 470 | For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic.....for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add |
| 471 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm diawith necessary fittings complete asper specification no. FF-PP |
| 472 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete asperspecification no. FF-PP |
| 473 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete asperspecification no. FF-PP |
| 474 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete asper specification no. FF-PP |
| 475 | Supplying anderecting100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) forpositive suction complete asper specification no. FF-VL/ELS |
| 476 | Supplyinganderecting100mm dia.cast iron double flange sluice valve complete with PN16 pressure rating, asper specification no. FF-VL/SV |
| 477 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, asperspecification no. FF-VL/BFV |
| 478 | Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, asper specification no. FF-VL/BFV |
| 479 | Supplying & erecting cast iron double flangebutterfly valve of size 100 mm dia. complete asper specification no. FF-VL/BFV |
| 480 | Supplying & erecting cast iron double flangebutterfly valve of size 150 mm dia. complete asper specification no. FF-VL/BFV |
| 481 | Supplying and erecting cast iron double flangeball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV |
| 482 | Supplying&erectinggunmetal gatevalveof size25 mmdia complete asper specification no. FF-VL/GV |
| 483 | Supplying anderectingstainless steel single outlethydrantvalve fitted with necessaryaccessories complete asper specification no. FF-VL/HV. |
| 484 | Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene(Polyhose)along with necessary accessories complete asper specification no. FF-FFA/HV |
| 485 | Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m inlength, fitted with necessary accessories complete asper specification no. FF-FFA/RRL |
| 486 | Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as perspecifications no. FF-FFA/NZ |
| 487 | Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete asper specification no.FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos. |
| 488 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve,erected with provided G.I. pipe, elbow etc. complete asper specification no. FF-FFA/PG |
| 489 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at everysingle outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant). |
| 490 | Supplying and erecting M.S./CRCA cabinet for housingFloorHydrant valve,hosepipe, hosereeland branch pipe(size 1000 x 736 x 736 mm.) made from 16 SWG sheetand angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8\"x6\") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe). |
| 491 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting upto 250 devices and detectorsper loop,with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021,,IS 2189: 2008, EN 54 & VDS / FM/UL864(10th edition)with 3 years replacement warranty FF-AFAS/CP. |
| 492 | Supplying, installing, testing and commissioning ofrepeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 orUL approvedwith 3 years equipment replacement warranty FF-AFAS/RP |
| 493 | Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or ULApproved with 3 years equipment replacement warranty FF-AFAS/SD |
| 494 | Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area\"s etc. with 3 years equipment replacement warrantyIS : 2175 - 1988 reaffirmed 2000,IS 15908:2021standards FF-AFAS/SD. |
| 495 | Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with \"Break Glass\" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listedwith 3 years equipment replacement warranty FF-AFAS/MCP. |
| 496 | Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) :1982 reed relays,EN 54 or UL Listed FF- AFAS/CRM |
| 497 | Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or ULListedwith 3 years equipment replacement warranty conforming toIS 5051Part 2 (Sec 1 to 3) : 1982 Reed relaysFF-AFAS/MM |
| 498 | Supplying, installing, testing and commissioning of addressable fire isolator module complete as required.EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM |
| 499 | Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage rangeEN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH. |
| 500 | Supplying, installing, testing and commissioningFR, XLPE armouredcable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete asper specification no. CB-LT/CU |
| 501 | Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230VoltsA.C. / 12VoltsD.C.supply complete asper specification no. FF- PA/AFR |
| 502 | Supplying, erecting, testing and commissioning 15 to 30 Watts soundcolumn or ceiling mounted complete asper specification no. FF-PA/SOC |
| 503 | Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to+55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereojack complete asper specification no.FF- PA/MIC |
| 504 | Supplying, erecting, testing and commissioningrust free microphone floor stand of chrome plating/powder coating orS.S. material , 500 mm to 1500 mmheightand sturdy mechanism ensuring trouble free movement complete. |
| 505 | Supplying, erecting, testing and commissioning of 2 core shielded cable complete asper specification no.FF-PA/MCC |
| 506 | Carrying out core cutting of size 3\" to 5\" dia x 15\" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. |
| 507 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag perroom. Total Set Required ( 300 X 400 X 150 = 1 room X 20 =20Nos) |
| 508 | Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables up tovoltage level1.1Kv cable complete as per specification No. CW-EXN-CTR |
| 509 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total(6.9+5.82)= 12.72 Cu-M |
| 510 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x6 mm. M. S. flat with nut & bolts routed in wall complete. |
| 511 | Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class ofFIRE complete. |
| 512 | Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories ) (Non CSRApproved by S.E.Office ,mumbaivide T.S letterno- 108Date- 13/01/2022 ) |
| 513 | Supply, Installation, testing zinc aluminite fire water storage tank having capacity 10 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion, excavation , PCC which can load of tankincluding of 100% water.( for booster pump as per NBC). |
| 514 | Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4\" x 3\" x 3\"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x340 33 Hinged Metal Fire Door 120 min fire Rated |
| 515 | Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessorieson wall/ceiling as per specification No: WG-MA/CON. |
| 516 | Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 517 | Supplying and erectingmodular type switch6A / 10A duly erected on provided plate and box with wiring connections complete. |
| 518 | Supplying and erectingmodular type 3 pin 6 / 16Amultisocket with safety shutter,duly erected on provided plate and box with wiringconnections complete. |
| 519 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected. |
| 520 | Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthe position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculationsheet attached). |
| 521 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no.CB-LT/CU(for booster Pump) |
| 522 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nosfor main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing. |
| 523 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As perspecification no EA-EP.(25x5) (1kg/mtr x 50 mtr=50 kg) |
| 524 | Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP |
| 525 | For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic.....for 5.5/ 7.5 kW centrifugal type booster pump 2no(2working) , add Rs….... |
| 526 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete asper specification no. FF-PP |
| 527 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete asper specification no. FF-PP |
| 528 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete asper specification no. FF-PP |
| 529 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete asper specification no. FF-PP |
| 530 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete asper specification no. FF-PP |
| 531 | Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete asper specification no. FF-PP |
| 532 | Supplying anderecting100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR(open area Ratio) forpositive suction complete asper specification no. FF-VL/ELS |
| 533 | Supplyinganderecting100mm dia.cast iron double flange sluicevalvecompletewith PN16 pressure rating, asper specification no. FF-VL/SV |
| 534 | Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size completewith PN16 pressure rating, asper specification no. FF-VL/BFV |
| 535 | Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of sizecomplete with PN16 pressure rating, asper specification no. FF-VL/BFV |
| 536 | Supplying & erecting cast iron double flangebutterfly valve of size 100 mm dia. complete asper specification no. FF-VL/BFV |
| 537 | Supplying & erecting cast iron double flangebutterfly valve of size 150 mm dia. complete asper specification no. FF-VL/BFV |
| 538 | Supplying and erecting cast iron double flangeball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV |
| 539 | Supplying&erectinggunmetal gatevalve of size25 mmdia complete asper specification no. FF-VL/GV |
| 540 | Supplying anderectingstainless steel single outlethydrantvalve fitted with necessary accessories complete asper specification no.FF-VL/HV. |
| 541 | Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene(Polyhose)along with necessary accessories complete asper specification no. FF-FFA/HV |
| 542 | Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m inlength, fitted with necessary accessories complete asper specification no. FF-FFA/RRL |
| 543 | Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzlecomplete as per specifications no. FF-FFA/NZ |
| 544 | Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete asper specification no.FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos. |
| 545 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve,erected with provided G.I. pipe, elbow etc. complete asper specification no. FF-FFA/PG |
| 546 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant). |
| 547 | Supplying and erecting M.S./CRCA cabinet for housingFloorHydrant valve,hosepipe, hosereeland branch pipe(size 1000 x 736 x 736 mm.) made from 16 SWG sheetand angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8\"x6\") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe). |
| 548 | Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 8 loop capacity and capable of supporting upto 250 devices and detectorsper loop,with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, IS 2189: 2008, EN 54 & VDS / FM/UL864(10th edition)with 3 years replacement warranty FF-AFAS/CP |
| 549 | Supplying, installing, testing and commissioning ofrepeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 orUL approvedwith 3 years equipment replacement warranty FF-AFAS/RP |
| 550 | Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or ULApproved with 3 years equipment replacement warranty FF-AFAS/SD |
| 551 | Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area\"s etc. with 3 years equipment replacement warrantyIS : 2175 - 1988 reaffirmed 2000,IS 15908:2021standards FF-AFAS/SD. |
| 552 | Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with \"Break Glass\" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listedwith 3 years equipment replacementwarrantyFF-AFAS/MCP. |
| 553 | Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays,EN 54 or UL Listed FF-AFAS/CRM |
| 554 | Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacementwarranty conforming toIS 5051Part 2 (Sec 1 to 3) : 1982 Reed relaysFF-AFAS/MM |
| 555 | Supplying, installing, testing and commissioning of addressable fire isolator module complete as required.EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM |
| 556 | Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage rangeEN 54, conforming to IS 2189: 2008, IS 15908:2021standards with 3 years equipment replacement warranty FF-AFAS/SSH. |
| 557 | Supplying, installing, testing and commissioningFR, XLPE armouredcable 2 core 1.5 sq.mm. copper conductor completeerected on wall/ ceiling complete asper specification no. CB-LT/CU |
| 558 | Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230VoltsA.C. / 12VoltsD.C.supply complete asper specification no. FF- PA/AFR |
| 559 | Supplying, erecting, testing and commissioning15 to 30 Watts sound column or ceiling mounted complete asperspecification no. FF-PA/SOC |
| 560 | Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to+55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete asper specification no.FF-PA/MIC |
| 561 | Supplying, erecting, testing and commissioningrust free microphone floor stand of chrome plating/powder coating orS.S. material , 500 mm to 1500 mmheight and sturdy mechanism ensuring trouble free movement complete. |
| 562 | Supplying, erecting, testing and commissioning of 2 core shielded cablecomplete asper specification no.FF- PA/MCC |
| 563 | Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessaryfittings as per specifications having 1000mm long with UL/FM |
| 564 | Carrying out core cutting of size 3\" to 5\" dia x 15\" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. |
| 565 | Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½\") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflectordisc of conventional construction complete as per specification no. FF-SPR. |
| 566 | Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½\") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS |
| 567 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 =1 room X 160 =160 Nos) |
| 568 | Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3mtr width as per IS for laying provided cables uptovoltage level1.1Kv cable complete as per specification No. CW-EXN-CTR |
| 569 | Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total(6.9+5.82)= 12.72 Cu-M |
| 570 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed inwall complete. |
| 571 | Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable disharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisher operating temperature (-)20 to (+)55 C kg capacity suitable for A,B,C class of FIRE complete. |
| 572 | Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisher operating temperature (-)20 to (+)55 C kg capacity suitable for A,B,C class of FIRE complete. |
| 573 | Supplying and erecting of fire Exit & Eire Exinguisher signlge Indicating the floor- numtber in words &syslem( FireExiinguisher& Accessories ) (Non CSR |
| 574 | Supply, Installation, testing zinc aluminite fire water storage tank having capacity 10 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion, excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC). |
| 575 | Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 1200 x 2100 mm 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4\" x 3\" x 3\"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 HingedMetal Fire Door 1200 x 2100 mm, 120 min fire Rated |
| 576 | Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type 630A Capacity at 40oC ambient temperature Sandwich type Aluminium Conductor tin plated at joints/Aluminium conductor Silver flashed copper bimetal contact having purity not less than 99.6% with suitable for (3L+ N)415V, 50 HzA.C Supply with 100% Neutral+ enclosure as integral earth (PE) with IP 54/55 Protection,36/40KA short circuit rating for 1sec, InsulationClass F (155 C) , casing made of minimum 1.5mm hotdipped / electro Galvanized /Epoxy powder coated steel sheet enclosure having Mechanical strength certification up to IK10 with required shade of paint having overall cross sectional area not more than0.0170 sq. Mtr., complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories with Horizontal / Vertical G.I. Support at required interval with External Double run 50x5mm Aluminium earthingstrip or Internal Integral Earth complete confirming to IEC 61439-6 as per specification |
| 577 | Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type 800A Capacity at 400C ambient temperature Sandwich type Aluminium Conductor tin plated at joints/Aluminium conductor Silver flashed copper bimetal contact having purity not less than 99.6% withsuitable for (3L+ N)415V, 50 Hz A.C Supply with 100% Neutral+ enclosure as integral earth (PE) with IP 54/55 Protection,42/50KA short circuit rating for 1sec, InsulationClass F (155 C) , casing made of minimum 1.5mm hot / electro Galvanized /Epoxy powder coated steel sheet enclosure with required shade of paint having Mechanical strength certification up to IK10 overall cross sectional area not more than 0.0170 sq. Mtr., complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories as per site requirement with Horizontal / Vertical G.I. Support atrequired intervalwithDouble run External Double run 50x5mm Aluminium earthing strip or Internal Integral Earthcomplete confirming to IEC 61439-6 as per specification |
| 578 | Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type 1000A Capacity at 40oC ambient temperature Sandwich type Aluminium Conductor tin plated at joints /Aluminium conductor Silver flashed copper bimetal contact having purity not less than 99.6% withsuitable for (3L+ N) 415V, 50 Hz A.C Supply with 100% Neutral+ enclosure as integral earth (PE) with IP 54/55 Protection,50KA short circuit rating for 1sec,Insulation Class F (155 C) , casing made of minimum 1.5mm hot / electroGalvanized/Epoxy powder coated steel sheetenclosure with required shade of paint having Mechanical strength certification upto IK10,overall cross sectional area not more than0.0170 sq. Mtr., complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories as per site requirement with Horizontal / Vertical G.I. Support at required interval with External Double run 50x5mm Aluminium earthing stripor Internal Integral Earth complete confirmingto IEC 61439-6 as per specification |
| 579 | Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type 1250A Capacity at 40oC ambient temperature Sandwich type Aluminium Conductor tin plated at joints /Aluminium conductor Silver flashed copper bimetal contact having purity not less than 99.6% withsuitable for (3L+ N) 415V, 50 Hz A.C Supply with 100% Neutral+ enclosure as integral earth (PE) with IP 54/55 Protection,65KA short circuit rating for 1sec,Insulation Class F (155 C) ,casing made of minimum 1.5mm hot / electroGalvanized/Epoxy powder coated steel sheetenclosure with required shade of paint having Mechanical strength certification up to IK10 overall cross sectional area not more than 0.0225 sq. Mtr., complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories as per site requirement with Horizontal / Vertical G.I. Support at requiredinterval with External Double run 50x5mm Aluminium earthing strip or Internal Integral Earth complete confirming to IEC 61439-6 as perspecification |
| 580 | Supplying, installing, testing & commissioning of Tap off box with interlock arrangement on existing Air Insulated / Sandwich type bus trunking/ rising mains for 250A to 400A 3 phase 4 wire 415V, 50Hz AC Supply made with 1.5mm thick sheet metal enclosure (IP54/55) duly powder coated with provisionof MCCB( without MCCB) complete as required confirming to IEC 61439-6 as per specification |
| 581 | Providing & erecting 4 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB NOTE |
| 582 | Providing & erecting 4 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW- SWR/MCCB |
| 583 | Supplying, installing, testing and commissioning of Flange end with Adaptor box, as per site requirement suitable for Aluminium 630A 3 phase 4 wire 415V, 50 HzA.C ,36/40kAshort circuit rating for 1 sec Sandwich type Aluminium BBT. with necessary accessories complete |
| 584 | Supplying, installing, testing and commissioning of Flange end with Adaptor box, as per site requirement suitable for 800A 3 phase 4 wire 415V, 50 Hz A.C ,42/50kA short circuit rating for 1 sec Sandwich type Aluminium BBT with necessary accessories completeconfirming to IEC 61439-6 as per specification |
| 585 | Supplying, installing, testing and commissioning of Flange end with Adaptor box, as per site requirement suitable for 1000A 3 phase 4 wire 415V, 50 Hz A.C ,50kAshort circuit rating for 1 sec Sandwich type Aluminium BBT. with necessary accessories completeconfirming to IEC 61439-6 as per specification |
| 586 | Supplying, installing, testing and commissioning of Flange end with Adaptor box, as per site requirement suitable for 1250A 3 phase 4 wire 415V, 50 Hz A.C,65kAshort circuit rating for 1 sec Sandwich type Aluminium BBT. with necessary accessories completeconfirming to IEC 61439-6 as per specification |
| 587 | Supplying, installing & Commissioning Vertical or Horizontal Tee Elbow for Sandwich type Aluminium Compact bus trunking/ rising mains Suitable for 630A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply Made of minimum 1.5mm Thick Galvanised sheet metal enclosure (IP54/55)duly powdercoated with all necessary accessories complete |
| 588 | Supplying, installing & Commissioning Vertical or Horizontal 90 Degree Elbow for Sandwich type Aluminium Compact bus trunking/ rising mains Suitable for 630A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply, 36/40kAshort circuit rating for 1 sec Made of minimum 1.5mm Thick Galvanised sheet metal enclosure (IP54/55)duly powder coated with all necessary accessories complete confirming to IEC 61439-6 as per specification |
| 589 | Supplying, installing & Commissioning of Plug in Points on provided Sandwich type Aluminium Compact bus trunking/ rising mains Suitable for630A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply,,36/40KA short circuit rating for 1sec Made of minimum 1.5mm Thick Galvanised sheet metal enclosure(IP54/55)duly powder coated with all necessary accessories complete. |
| 590 | Supplying, installing & Commissioning of Plug in Points on provided Sandwich type Aluminium Compact bus trunking/ rising mainsSuitable for800A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply,42/50KA short circuit rating for 1sec Made of minimum 1.5mm Thick Galvanised sheet metal enclosure (IP54/55)duly powder coated with all necessary accessories complete. |
| 591 | Supplying, erecting, testing and commissioning of diesel generating set with alternator of 750 kVA output continuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C supply, a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self- regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation+/- 5 %, with performance class G2 and maximum fuel consumption 126.4 Ltr/hr @75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA sheet, sound absorbing material to restrict sound level up to 75 dB at 1.0 m, provided with first filling of oil, diesel not less than 990 Ltr etc. on provided M20 Grade CC Foundation and obtaining necessary approvalfrom Electrical Inspector as per specification no. GEN-DG |
| 592 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq.mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 593 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware. |
| 594 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 200 mm outsidedia, double wall corrugated pipes (DWC)ofHDPE for enclosing cable below ground/road surface, to required depthcomplete. |
| 595 | Providing and fixing reinforced cement concrete cover of size 60 cm x 45 cm withframe over inspection chamber etc. complete of medium duty (100 Kilogram). |
| 596 | Making cement concrete foundationin 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box isincluded) DG -2.5mx3mx0.3=2.25*2=5 |
| 597 | Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions bythe authority. |
| 598 | Hiring charges for supplyingand maintaining temporary 415V, 50cyclesAC generating set250 kVA capacity with voltage regulation+/- 5 %, and complete set enclosed in composite acoustic enclosure to restrict sound level up to 75 dB at 1.0 m, with necessary fuel, mains, switchgears and accessories completewith continuousrunning onload/no load as per requirements complete with self certification. |
| 599 | Hiring charges for supplyingand maintaining temporary 415V, 50cyclesAC generating set250 kVA capacity with voltage regulation+/- 5 %, and complete set enclosed in composite acoustic enclosure to restrict sound level up to 75 dB at 1.0 m, with necessary fuel, mains, switchgears and accessories completewith continuousrunning on load/no load as per requirements complete with self certification. ( for additional 29 daysfor 1 Generator ) Foot note apply |
| 600 | Lumsum provision for the additional fuel (Fuel consumption at 75% load for 250 KVADG set 42.6 Ltr/ hr x 1 nos. Hence total consumption 42.6 Ltr/ hr X additional 6 hours |
| 601 | Providing Services of skilled wireman having valid wireman licence for operation & maintenance of electrical installation for single shift for every day ( 60 Days X 3 Shift X 2Person = 360days) |
| 602 | Supplying, installation and testing of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth withrequired quantity complete, and recording the results Specification no. EA-MOBI |
| 603 | Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted withbituminous paint with joints required. As per specification no. EAEP. |
| 604 | Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. |
| 605 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 2 core 4 sq mm copper conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no.CB-LT/CU |
| 606 | Supply, Installation, Testing and commissioning of Lift Panel requirements ThePanel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.CableEntry From Bottom & Out From Buttom SideOf Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site fromEngineer -in-Charge. feeders with R , Y , B for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO,LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer:250A,4P,MCCB Outgoing Feeders:100A,3P,MCCB -6 NOS,TP MCB ADD -63 A TP MCB-9 nos |
| 607 | Supply, Installation, Testing and commissioning of BEST METER PANEL For Fire requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection-1Nos Outgoing Feeders: Trivector Meter - 1nos |
| 608 | Supply, Installation, Testing and commissioning of Fire Panel Change Over Panelrequirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. ReferElectrical Main Single Line diagrams for panel details. Incomer: 400A,4P, ATS -1nos |
| 609 | Supply, Installation, Testing and commissioning of BEST PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge Panel should be Inspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter440 V50 Hz.-1 NOSBusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter. |
| 610 | Supply, Installation, Testing and commissioning of MAIN LT PANEL North Side Section-1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer:800A ACB- 4 nos , 1250ACB-2 NOS,2000A ACB-1 nosBusbarsRating :2000A,3Phase,50KA,50Hz AL. BusbarMetering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter,Multifuctional Meter. |
| 611 | Supply, Installation, Testing and commissioning of MAIN LT PANEL North Side Section-2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer:800A ACB- 4 nos , 1250ACB-1 NOSBusbarsRating :2000A,3Phase,50KA,50Hz AL. BusbarMetering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter,Multifuctional Meter. |
| 612 | Supply, Installation, Testing and commissioning of MAIN LT PANEL-South Side Section -1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439.Refer Electrical Main Single Line diagrams for panel details.Incomer:800A ACB- 4 nos , 1250ACB-2 NOS 2000ACB-1 NOSBusbarsRating :2000A,3Phase,50KA,50Hz AL. BusbarMetering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter,Multifuctional Meter. |
| 613 | Supply, Installation, Testing and commissioning of MAIN LT PANEL-South Side Section -2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer:800A ACB- 4 nos , 1250ACB-2 NOSBusbarsRating :2000A,3Phase,50KA,50Hz AL. BusbarMetering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter,Multifuctional Meter. |
| 614 | Supply, Installation, Testing and commissioning of BEST PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. R LSIG. The panel should be as per IEC 61439. efer Electrical Main Single Line diagrams for panel details. Incomer:400A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :400A,3Phase,50KA,50Hz AL.Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter. |
| 615 | Supply, Installation, Testing and commissioning of OPTHAL DEPARTMENT DG PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overloadand Short circuit protection- 3Nos |
| 616 | Supply, Installation, Testing and commissioning of OPTHAL DEPARTMENT ATS PANEL-1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz-1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realesewith Overload and Short circuit protection- 1Nos,100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 3Nos,63 A TP MCB-5NOS,32 A DP MCB-6NOS, |
| 617 | Supply, Installation, Testing and commissioning of OPTHAL DEPARTMENT ATS PANEL-2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz-1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 3Nos,100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 3Nos,63 A DP MCB-6NOS, |
| 618 | Supply, Installation, Testing and commissioning of OPD GROUND FLOOR PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place beforedispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer::400A,4P,MCCB with 25KA Breaking Capacity with thermal realesewith Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :400A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 12Nos |
| 619 | Supply, Installation, Testing and commissioning of SKIN DEPARTMENT DGPANEL requirements The PanelShould Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable EntryFrom Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved fromEngineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA BreakingCapacity with thermal realese with Overload and Short circuit protection- 4Nos |
| 620 | Supply, Installation, Testing and commissioning of SKIN DEPARTMENT ATS PANEL-1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz-1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 2Nos,100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 2Nos,63 A TP MCB-10NOS |
| 621 | Supply, Installation, Testing and commissioning of SKIN DEPARTMENT ATS PANEL-2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer:ON LOAD four pole automatic transfer switch, 415V,400A, 50 Hz-1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :400A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 400A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos,100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 3Nos MCB- 10NOS |
| 622 | Supply, Installation, Testing and commissioning of 300 BEDED DOCTORS QUARTERS GROUND FLOOR PANELrequirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved fromEngineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. Refer Electrical Main Single Line diagrams for panel details. Incomer::630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA BreakingCapacity with thermal realese with Overload and Short circuit protection- 8Nos |
| 623 | Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT DG PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturingthe Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO LSIG. The panel should be as per IEC 61439.. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter440 V50 Hz.-1 NOS BusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA BreakingCapacity with thermal realese with Overload and Short circuit protection- 6Nos |
| 624 | Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT ATS PANEL-1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz- 1Nos Trivectormeter 440 V 50 Hz.-1 NOS Busbars Rating :315A,3Phase,50KA,50Hz AL.Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overloadand Short circuit protection- 4Nos |
| 625 | Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT ATS PANEL-2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B PhaseIndicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz- 1Nos Trivector meter 440 V 50 Hz.-1 NOS Busbars Rating :315A,3Phase,50KA,50Hz AL.Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA BreakingCapacity with thermal realese with Overload and Short circuit protection- 5Nos |
| 626 | Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT ATS PANEL-3 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated. Cable Entry From Bottom & Out FromButtom Side Of Panel. The minimum sizes ofsections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour HeatShrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overloadand Short circuit protection- 5Nos |
| 627 | Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT ATS PANEL-4 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected &Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB\"s shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA Breaking Capacity with thermal realesewith Overloadand Short circuit protection- 12Nos |
| 628 | Supplying and erecting 250 kVAr, 440 V 3 phase, 50 Hz., Contactor Logic & Intelligent Relay micro APFC passive filter panel, consisting of suitable steps of APP/MPP type capacitor units with Detuned (harmonic filter) reactors of suitable rating , APFC panel shall be compliance to IEC 61439 and powerqualityIEC 61921 standard as per specification no CP-ED/APFC |
| 629 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories. |
| 630 | Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core50 sq.mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 631 | Supplying, erecting & terminating FR XLPEinsulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core70 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 632 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeasper specification no. CB-LT/AL |
| 633 | Supplying, erecting & terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½core120 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 634 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 150 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 635 | Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 185 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeasper specification no. CB-LT/AL |
| 636 | Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½core240 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeasper specification no. CB-LT/AL |
| 637 | Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 638 | Supplying, erecting& terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq.mm. copper conductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas perspecification no. CB-LT/CU |
| 639 | Supplying, erecting & terminating XLPE insulated unarmoured cable 1100 V. 1 core 50 sq. mm. copper conductor complete erected with provided lugs, laid in provided controlpanel /distribution boards / pipe as per specification no. CB-LT/CU |
| 640 | Providing printed instruction chart for treating persons suffering from electric shock, printed inEnglish & Marathi and duly laminated complete. |
| 641 | Supplying standard first aid box with necessary antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-Aid) adhesive tape for medicinal use, scissors, anti-septic solution, etc. (All abovecontents shall be of standard makes) |
| 642 | Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006having 2 mm thickness up to 3.3 kV |
| 643 | Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modulartype switch, earthing and required accessories as per specification No: WG-PW/SW |
| 644 | Supplying and erecting modular type switch 16A duly erected on provided plate and boxwith wiring connections complete. |
| 645 | Supplying and erecting modular type 3 pin 16A multi socket with safety shutter, dulyerected on provided plate and box with wiring connections complete. |
| 646 | Providing temporary plug point with 3 phase industrial socket having CRCA sheet metal enclosure with 30A, 3 pin plug and earth socket and 30A, 3 pin, plug top with 30A, triple pole MCB, mains, switchgears withcontinuous earth wireup to three days |
| 647 | Supplying and erecting PVC Surface modularswitch box with double mounting plate for 6 module duly erected. |
| 648 | Supplying and erecting mains with 2x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places as per specification No: WG-MA/BW |
| 649 | Supplying and erecting mains with 1x1.5 sq.mm FRLSHcopperPVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places as per specification No: WG-MA/BW |
| 650 | Supplying and erecting mains with 2x2.5 sq.mmFRLSH copper PVC insulated wire laid in provided conduit/trunking/insidepole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 651 | Supplying and erecting mains with 1x2.5 sq.mmFRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW |
| 652 | Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Busbars or any other places. as per specification No: WG-MA/BW |
| 653 | Supplying and erecting mains with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Busbars or any other places. as per specification No: WG-MA/BW |
| 654 | Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. With PVC accessories on wall /ceiling as perspecification No: WG-MA/CON. |
| 655 | Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specificationNo: WG-MA/CON. |
| 656 | Supplying&erectingtriplepoleand neutral distribution board (TPNDB), SP/TP MCBs total 8 ways /24 poles, with door,1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbartype) as per specification no. SW- SWR/MCBDB |
| 657 | Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provideddistribution board as per specification no. SW- SWR/MCB |
| 658 | Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kAin provided distribution board as per specification no. SW-SWR/MCB |
| 659 | Supplying, erecting & commissioning 2 pole RCCB 16/25A, electromagnetic type with 30/100/300 mA sensitivitywithearth leakage trip indicationcomplete as per specification no. SW-RCCB/RCCB |
| 660 | Providing & erecting 4 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specificationno. SW-SWR/MCCB |
| 661 | Providing & erecting 4 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel asper specification no. SW-SWR/MCCB |
| 662 | Supplying & erecting CRCA sheet metal enclosures of 1.2mm thickness with30 A, 3 pin plug & earth socket and 30A, 3 pin plug top with 30A triple pole MCB having ratedshort - circuit breaking capacity (Icn) 10kA complete erected on angle iron / GI frame. |
| 663 | Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAh Lithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty. |
| 664 | Supplying and erecting energy saving ceiling fan 230 V A.C. 50 cycles 1200 mm completeerected in position as per specification no. FG- FN/CF |
| 665 | Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or paintedwith one coat of red lead paint and 2 coats of enamel paint complete. |
| 666 | Dismentling of existing Air Insulated Busbar truncking of 800A with necessary security arrangements from south and north electrical service room with accessories and to kept instore room as per instructions of engineer in charge. |
| 667 | Dismantling of existing fluorescent fittings of any type & size. |
| 668 | Dismantling the existing ceiling fan /exhaust fan / cabin fan / bracket fan complete with accessories, G.I. down rod, frame etc. andmaking the site clear. |
| 669 | Dismantling the existing switchgears, DB, and bus bar of any size completewith/ without board or angle iron frame |
| 670 | Dismantling the existing cables of all types & size above 10 sq mm up to 50 sq.mm. |
| 671 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mmwidth & 75 mm height complete with necessary coupler plates & hardware. |
| 672 | Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick)GI sheet of 300 mm width & 20 mm height complete with necessary hardware. |
| 673 | Supplying and fixing 9U wall mount rack (Dimension-DxWxH – 500x600x500 mm) as per specification No. WG-NAS/RAK |
| 674 | Supplying and fixing 42U floor mount server rack (Dimension-DxWxH – 800x600x1866 mm) as per specificationNo. WG-NAS/RAK |
| 675 | Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no. WG-NAS/PP |
| 676 | Supplying, fixing, and configuring 24 ports with 4 (SFP+) port, ethernet managed switch with web view/CLI, 6KV surge protection on ethernet port and console port for management in provided rack as per specification no. WG-NWC/GBS |
| 677 | Supplying, fixing, and configuring 20 SFP ports + 4 Combo SFP 10/100/1000 Base-T erected in provided rack complete. |
| 678 | Supplying anderectingPVCboxtrunking of size 75x75 mm. with accessories on wall/ceiling as per specification No: WG- MA/BOX. |
| 679 | Supplying and erecting LSZH armoured multimode optical fibre cable with 12 fibres, core dia 50/125 µm (OM3), suitable up to 10 GBPS ethernet distance at 850 nm of wavelength, on wall/ceiling or laid in providedpipe/trench as per specification No. WG- COC/OFC |
| 680 | Supplying and fixing 12 ports light guide unloaded interconnect unit, rack mounted type, with adapter panel for termination of optical fibre cables in provided U rackcomplete as per specification no. WG-NAS/ LIU |
| 681 | Supplying and installingcat-6 cable suitable for networking as per specification no. WG- COC/NC |
| 682 | Supplying and fixing SC/LC type multimode pigtails (OM3) for LIU to terminate OFC in LIU as per specification No. WG-NAS/LIU2 |
| 683 | Supplying and fixing SC/LC type multimode duplex adapter to couple two connectors between OFC &Fibre switch/Fibre module asper specification no. WG-NAS/MMA |
| 684 | Supplying and plugging 3 m fibre patch cord LC-LC MM (50) OM3 LSZH duplexcomplete as per specification no. WG- COC/FPC |
| 685 | Supplying and plugging 3 m fibre patch cord LC-SC MM (50) OM4 LSZH duplexcomplete as per specification no. WG- COC/FPC |
| 686 | Supplying anderectingPVCtrunking (PVC casing-n-capping)ofsize32 mm with accessorieson wall/ceiling as perspecification No: WG-MA/CON. |
| 687 | Supplying, fixing, and configuring 1-port mini-GBIC SX MM fibre transceiver (up to 550m, support 3.3V power) erected inprovided rack complete. |
| 688 | Supplying, fixing, and configuring modularised multi-service router 802.11/a/n/ac unified Wave 2.5 GHz, with RJ- 45 port, supporting 1 to 13 channels for 2.4 GHz, with unified wireless access point complete. |
| 689 | Supplying &erecting 50 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit asperspecification No.WG-TW |
| 690 | Supplying &erecting 100 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit asperspecification No.WG-TW |
| 691 | Supplying & erecting 0.5 mm dia, copper jumper wireas per specification No. WG- TW |
| 692 | Supplying, erecting &commissioning MDF Box 50x50 pairs made from min. 1.5mm thick MS sheet as per specification no. WG-TW |
| 693 | Supplying, erecting &commissioningMDF Box 400x400 pairs made from min. 1.5mm thick MS sheet as per specification no. WG- TW |
| 694 | Supplying, Erecting, Testing and Commissioning of ESE Lightning Arrester, Controlled Early Streamer Emission Air terminal (ESEAT) with following specifications:ESEAT Protection Radius - 107 Mtr. with suitable mast height, with triggering time of 60 micro second as per NFC 17-102 which emits local electrostatic field that develops naturally around the shaft as a thunderstorm begins to gather, The ESEAT air-terminal shall be tested to support a 200kA current (waveform 10/350 μs). Test to be performed in compliance with NFC 17 102 version 2011 The ESEAT Should be able to work in both (positive and negative) lightning polarities.The ESEAT shall be in Strict compliance with the new test guidelines as per \"Annex C\" of the revised NFC 17 102 version 2011(As Amended up to date) for ESE lightning protection system.The ESEAT shall be made of Stainless Steel 304L/316 grade non- corrosive metallic components, Electronic Circuit, Capacitor Bank, Transformer, Amplifier, Sensor etc. to generate the Streamer.The ESEAT to be a fully autonomous system requiring no external power supply. The ESEAT shall be Testable on site, using proprietary testers. The ESEAT should be sustainably designed to mitigate its environmental impact. The ESEAT to be mounted on provided base & support arrangements and installed as per the Technical specifications & General Arrangements Drawing attached complete with testing Warranty: five year from the date of commissioning |
| 695 | Supplying and erecting ISI mark GI pipe 50mm. dia ‘C” class position with accessories complete. Specification no. CW-PLB/GP this item proposed to installed as per the Technical specifications& General ArrangementsDrawingattached complete with testing . |
| 696 | Supplying and erecting ISI mark GI pipe 65mm. dia ‘C” class position with accessories complete. Specification no. CW-PLB/GP.this item proposed to installed as per the Technicalspecifications & General Arrangements Drawingattached complete with testing . |
| 697 | supplying and erecting heavy duty Galvanized mildsteel pole coupler suitable for connecting C class GI pipe size 50 mm.dia& C class GI pipe size 50 mm.dia 65mm dia duly threaded or welded complete with necessary arrangements & erected inposition complete with ensuring electrical conductivitythis item proposed to installed as per the Technicalspecifications & GeneralArrangements Drawingattached complete with testing |
| 698 | Supplying and fixing base for ESEAT cum pole cap duly galvanized with necessary anticorrosive treatment fabricated from mild steel fixed to pole top by means of welding and fixed at position with required size & type threads suitable for mounting ofESEAT with 2nos earth terminals having min.30x6mm cross section 50mm length each towardsdown direction for fixing 2nos down conductors with necessary welded GI nuts & bolts of required size with washer this item proposed to installed as per the Technicalspecifications & General Arrangements Drawingattached complete |
| 699 | Supplying and fixing Pole base plate made up of mild steel having minimum 250mm size and 10mmthick fixed to pole base by welding with min. 4nos triangular cross arms of min 6mm thick welded duly galvanized and fixed at position. With 4nos 20mm dia holes for erection on provided foundationthis item proposed to installed as per the Technical specifications & General ArrangementsDrawing attached complete |
| 700 | Making M- 20 grade reinforced cement concretefoundation byconsidering the safe soil bearing capacity at site as 10 T/sq.mat1.5 m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 9m & 10m high octagonal /conical GI pole). this item proposed to installed as per the Technical specifications& General Arrangements Drawingattached complete with testing . |
| 701 | Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6 mm., straining screws, G.l. stay wire 7/8 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete.this item proposed to installed as per the Technicalspecifications & General Arrangements Drawingattached complete with testing . |
| 702 | Making cement concrete foundation including excavation(60x 60x 150) cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metalwith necessary curing and finishing complete.(for stay). |
| 703 | Supplying and erecting GI sheet 1.6mm (16 SWG) caution board of size 250 x 200 mm duly painted with red oxide and enamel paint in Marathi, Hindi and English erected at position for HV/EHV (11000 Volts) installation with compliance to IS 2551-1982 this item proposed to installed as per the Technical specifications& General Arrangements Drawingattached complete with testing . |
| 704 | Supplying and erecting Contra go up device fabricated from required size mild steel flat of 40x5 mm dult welded with mild steel drooping spikes of min. 200mm long completely galvanized erected onpole with necessary GI nut bolts complete. this item proposed to installed as per the Technicalspecifications& General Arrangements Drawingattached complete |
| 705 | Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. Weight analysis 25 X 6 mm GI Strip ,1.2 Kg / mtr for total length 30 mt/LA total weight 1.2kg X 750 = 900(this item proposed to installed as per the Technicalspecifications & General Arrangements Drawingattached complete with testing . ) |
| 706 | Supplying and erecting pole clamp made from required size MS flat for pole post galvanized & painted with one coat of red oxide and two coats of aluminium paint and erected with necessary GIbolts and nuts, complete suitable for erecting Test Joint & Lightning flash counter this item proposed to installed as per the Technicalspecifications & General Arrangements Drawingattached complete |
| 707 | Supplying and Erecting Test Joint[Test Clamp] mounted in between the Earth Electrode(EC) and Down Conductor(DC)at the height of about 2meterabove ground level to be done as per relevant IS specifications designed and situated so as the resistance of Earth Electrode can be measured Test Clamp to be attached to pole with provided Pole clamp this item proposed to installed as per the Technical specifications & General Arrangements Drawingattached complete with testing. |
| 708 | Supply, Installation, Testing & Commissioning of minimum 2 Digit Digital Lightning StrikeCounter(LSC) Electronically controlled andmounted on down conductor having following features:a. Strike detection range: 1 KA to 100 KA.b. Minimum current sensitivity (id/3): 500 Ac. Protection class: IP 67 (Without Enclosure)d. Easy to monitor and install and No maintenancerequired.e. Standards applicable: IEC 62561 Lightning protection system components (LPSC) - Part 6: Requirements for lightning strike counters (LSC) Lightning strike Counter to be mounted at a heightof about 2mtr from Ground level with provided Poleclamp this item proposed to installed as per the Technicalspecifications &General Arrangements Drawingattached complete with Testing |
| 709 | Supplying, erecting, testing & commissioning of Maintenance free earthing system suitable for lightning protection system. The earth pit comprisesof 125 to 150mm inner dia bore up to suitable depth from ground surface and a high corrosion resistance material of minimum 250 micron copper bonded solid steel rod electrode of 2meter long having 17.2 mm dia. with necessary conductor clamps for Earth rod/Earth rod to tape connector clamp etc. as per site requirements. with backfill earthing compound with Ground Enhancing compound combination ofminimum 30Kg as per IS 3043- 2018 and IEEE 80- 2000 with satisfactory Test report from Govt. owned Test Laboratory .The requirements of Ground enhancing Compundare as Follows:a ) The compound shall have Ionic property to create ions for easy conduction. b) The compound shall be enable to disperse the ions equally in the earth pits. c) The compound should expand so much to remove entrapped air (bad Conductor of electricity) and create a strong conduction between electrode andsoil.d) The compound should diffuse in the soil to createconductive silicate. This Silicate should expand into the soil with the edge of the earth pits and result in progressive reduction of earth pit resistance. e) The compound should have a property to assist in absorbing humidity from the neighbouring soil to keep earth pit moist, which in turn helps better conduction. f) The compound should have the property to ensure moisture is retained throughout the year irrespectiveof the weather condition without addition of water during the life of the earth pit. g) The compound should be non toxic, non reactive, non explosive & non corrosive. h) The compound shall be permanent &maintenance free and in its “set form”, maintain constant earthresistance with time.this item proposed to installed as per the Technical specifications& General Arrangements Drawingattached complete with testing |
| 710 | Suppling & erecting HDPE (High Density Polyethylene) earthing pit inspection chamber with Cover having factory Built Holes for accessing Strip/Wires easily at two sides made of Environment friendly Withstand colour /UV unaffected Resistant materials, assuring durability and 5Ton load bearing capacity. Minimum Dimensions are 260mm at Top, 260mm at Bottom, 210mm Height this item proposed to installed as per the Technicalspecifications & General Arrangements Drawingattached complete with testing |
| 711 | Shanti,Bhakti,Tirupati Bldg 8A and Tirupati 8B BldgSITC ofElectricTractionPassengerLift with Rated capacity :6 Passenger/408Kg Floors :- G+7floor(8Stops/8Landings)·Travel:-4 mtrs·Locationof Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 800 mm wide x 2000 mm high ·Clear Car size of 1100mm wide x 1000mm deep x 2250mm high· Liftshaftavailablehaving clear size of 1800mm wide x 1700mm deep, 1500mm Pit depth,5000mm Overhead.·Doors type:-COPO/TOPO Doorswithframemade fromSS304 grade solid(non-cladded) sheetof 1.5mm thick in hairline finishforcarandall landing doors with SSdoor architraves/frames The lift doors shall have minimum 1hourfire rating(with submissionofnecessaryvalidtest certificate issued byNABLaccredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safetyfactorof5, withToe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interiordesign shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD withaudio- visualalarm,VASinMarathi,Hindi& English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswithscrollingUP/DNLED indicator having metallic push buttons with Braille code & luminousindicatoraround buttonwithCPI,Lift cararrival&nexttraveldirectionaudio-visualindication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drivehaving closedloopcontrolsystem, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protectionforphase loss at inputoroutputetc.various operation modes such asmaintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility,auto returnto homelanding,firemanevacuation operation, earthquake operation,door open/close operation from COP etc. The system can record information ·Other mechanicalparts such as \"T\" section adequate size guide rails for car & counterweightwith brackets fasteners, counterweightframe with necessary blocks, buffers with necessary support arrangement, MS pitladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary forerectionof landing door frames and it\"s accessories e.g. sill, header, hole pass etc complete with plasterfinish,civil work forerection buffers,erectionofliftmachinery, adequate size core cuts if required & scaffolding forerecting guide rails, providing and fixing steel girders/RCCworkhavingadequatestrength for mounting and hoisting lift machine etc. complete as per specification no.LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCCwithHDRdata backup for min. 90 days with min.18” FHD TV monitor, tobe keptinFCC/LMRas directed by EngineerInCharge.·Lift MachineofGearless PMSMof suitable kW with duty cycleof minimum120 starts/hr(withsubmission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entireassemblymountedon adequatesize girdersdulyfixedonLMR floor/ shaftwalls completewith main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real-timeclockmanagementandhandheld keypad with LCD screen for viewand setting of parameters.Thecontrolpanelduly ·ARD completewithnecessary SMFVRLA batteries.·wiredwithproper size & strength, copperwireforpower &controlcircuit,with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCAsheetwithpowdercoatingwith IP54 Protection class.General:-Job includes entire procedure of obtaining all necessary erection permissions & \"License to Work the Lift\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.·The above rate includes Fully Comprehensive AMCforoneyear fromthedateof commissioning |
| 712 | Dismantling the existing 6 Passenger lift of all types travelling G+7 floors (8 Landings/8 Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/sectionstore and handing over to the section engineer/store keeper in charge complete. |
| 713 | APNA Ladies HostelSITCofElectricTractionPassengerLift with Rated capacity :5 Passenger/340Kg Floors :- G+5floor(6Stops/6Landings)·Travel:-4 mtrs·Locationof Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 800 mm wide x 2000 mm high ·Clear Car size of 1100mm wide x 1000mm deep x 2250mm high· Liftshaftavailablehaving clear size of 1800mm wide x 1700mm deep, 1500mmPitdepth,5000mm Overhead.·Doors type:-COPO/TOPO Doorswithframemade fromSS304 grade solid(non-cladded) sheetof 1.5mm thick in hairline finishforcarandall landing doors with SSdoor architraves/frames The lift doors shall have minimum 1hourfire rating(with submissionofnecessaryvalidtest certificate issued byNABLaccredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safetyfactorof5, withToe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interiordesign shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD withaudio- visualalarm,VASinMarathi,Hindi & English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswithscrollingUP/DNLED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift cararrival&next traveldirectionaudio-visualindication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drivehaving closedloopcontrolsystem, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protectionforphase loss at inputoroutputetc.various operation modes such asmaintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility,auto returnto homelanding,firemanevacuation operation, earthquakedoor open/close operation from COP etc. The system can record information ·Other mechanicalparts such as \"T\" section adequate size guide rails for car & counterweight with brackets fasteners, counterweight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary for erection of landing door frames and it\"s accessories e.g. sill, header, hole pass etc complete with plasterfinish,civil work forerection buffers,erectionofliftmachinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCCworkhavingadequatestrength for mounting and hoisting lift machine etc. complete as per specification no.LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCCwithHDRdata backup for min. 90 days with min.18” FHD TV monitor, tobe keptinFCC/LMRas directed by EngineerInCharge.·Lift MachineofGearless PMSMof suitable kW with duty cycleof minimum120 starts/hr(withsubmission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entireassemblymountedon adequatesize girdersdulyfixedonLMR floor/ shaftwalls completewith main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real-time clock managementandhandheld keypad with LCD screenforviewand setting of parameters.The control panel duly ·ARD completewithnecessary SMFVRLA batteries.·wiredwithproper size & strength, copperwireforpower &controlcircuit,with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCAsheetwithpowdercoatingwith IP54 Protection class.General:-Job includes entire procedure of obtaining all necessary erection permissions & \"License to Work the Lift\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.·The above rate includes Fully Comprehensive AMCforoneyear from thedateof commissioningoperation, |
| 714 | Dismantling the existing 5 Passenger lift of all types travelling G+5 floors (6 Landings/6 Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up todivision/section store and handing over to thesection engineer/store keeper in charge complete. |
| 715 | METRON BuildingSITCofElectricTractionPassengerLift with Rated capacity :5 Passenger/340Kg Floors :- G+4floor(5Stops/5Landings)·Travel:-4 mtrs·Locationof Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 800 mm wide x 2000 mm high ·Clear Car size of 1100mm wide x 1000mm deep x 2250mm high· Liftshaftavailablehaving clear size of 1800mm wide x 1700mm deep, 1500mm Pit depth,5000mm Overhead.·Doors type:-COPO/TOPO Doorswithframemade fromSS304 grade solid(non-cladded) sheetof 1.5mm thick in hairline finishforcarandall landing doors with SSdoor architraves/frames The lift doors shall have minimum 1hourfire rating(with submissionofnecessaryvalidtest certificate issued byNABLaccredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safetyfactorof5, withToe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interiordesign shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD withaudio- visualalarm,VASinMarathi,Hindi& English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswithscrollingUP/DNLED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift cararrival&next travel direction audio-visual indication at all landings.·Lift controller based on microprocessor IOT/PLCwithVVVF Drivehaving closedloopcontrolsystem, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protectionforphase loss at inputoroutputetc.various operation modes such asmaintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility,auto returnto homelanding,firemanevacuation operation, earthquake operation,door open/close operation from COP etc. The system can record information ·Other mechanicalparts such as \"T\" section adequate size guide rails for car & counterweightwith brackets fasteners, counterweightframe with necessary blocks, buffers with necessary support arrangement, MS pitladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary forerectionof landing door frames and it\"s accessories e.g. sill, header, hole pass etc complete with plasterfinish,civil work forerection buffers,erectionofliftmachinery, adequate size core cuts if required & scaffolding forerecting guide rails, providing and fixing steel girders/RCCworkhavingadequatestrength for mounting and hoisting lift machine etc. complete as per specification no.LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC withHDRdata backup for min. 90 days with min.18” FHD TV monitor, to be keptinFCC/LMRas directed by Engineer InCharge.·Lift MachineofGearless PMSMofsuitable kW with duty cycle of minimum 120 starts/hr(with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Tractionpulley,OSG,electromagnetic brakes, entireassemblymountedon adequatesize girdersdulyfixedonLMR floor/ shaftwalls completewith main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real-time clock managementandhandheld keypad with LCD screen forviewand setting of parameters.The control panel duly ·ARD completewithnecessary SMFVRLA batteries.·wiredwithproper size&strength, copperwireforpower&controlcircuit,with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCAsheetwithpowdercoatingwith IP54 Protection class.General:-Job includes entire procedure of obtaining all necessary erection permissions & \"License to Work the Lift\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.·The above rate includes FullyComprehensive AMCforoneyear fromthedateof commissioning |
| 716 | Dismantling the existing 5 Passenger lift of all types travelling G+4 floors (5 Landings/5 Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the sectionengineer/store keeper in charge complete. |
| 717 | Balaram BuildingSITCofElectricTractionPassengerLift with Rated capacity :20 Passenger/1360Kg Floors :- G+4floor(5Stops/5Landings)·Travel:-4 mtrs·Locationof Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landingdoorclear opening of 1200 mm wide x 2000 mm high ·Clear Car size of 1300mm wide x 2400mm deep x 2250mm high· Lift shaft availablehaving clear size of 2300mm wide x 3100mm deep, 1500mm Pit depth,5000mm Overhead.·Doors type:-COPO/TOPO Doorswithframe made fromSS304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish forcarandall landing doors with SSdoor architraves/frames Theliftdoorsshallhave minimum 1hourfire rating(with submission ofnecessaryvalidtest certificate issued by NABLaccredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairlinefinishwith framemadefromMS girders, bracing of adequate size with minimum safetyfactorof5, withToe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation& SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interiordesignshall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminousindicator around button with FPI,scrolling UP/DN LED indicator & with /without attendant key switch, OWD with audio- visualalarm,VASinMarathi,Hindi & English with intercom system with telephoneinstrument in Lift car,LMR & FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswith scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator aroundbuttonwithCPI,Lift cararrival& nexttraveldirectionaudio-visualindication at all landings.·Lift controller based onmicroprocessor IOT/ PLC with VVVF Drivehaving closedloopcontrol system,withIBMS compatible having necessary port.The controller shall have necessary protections suchasovercurrent,overvoltage, over speed, overheatforalldevices including lift motor and travel direction protection,protectionforphase lossatinputoroutputetc.variousoperation modes suchasmaintenance,change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information ·Other mechanical parts such as \"T\" section adequate size guide rails for car & counterweightwithbrackets fasteners, counter weight framewith necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessarysteel work.·Minor civil work such as alteration work if any necessary for erectionoflandingdoor frames and it\"s accessories e.g. sill, header, hole pass etc complete with plasterfinish, civil work for erectionbuffers,erectionof lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.·Firemancontrollerhavingfiremanswitchatfire Landing.·CCTVsurveillancesystem comprises of 2 nos minimum 2.0MP FHD IP based vandal proofDome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery&controller withNVRkeptin LMR/FCCwithHDRdata backupformin. 90dayswithmin.18”FHDTV monitor,to be kept in FCC/LMRasdirectedby Engineer In Charge.·LiftMachineof Gearless PMSM of suitable kW with dutycycleof minimum120starts/hr(withsubmission of necessaryvalidtestcertificate issued by NABL accredited or Independent test laboratory), with Traction pulley,OSG,electromagneticbrakes, entire assemblymountedonadequate size girders duly fixed onLMRfloor/shaft walls completewithmain/divertertraction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real-time clock managementandhandheld keypad with LCD screenforviewand setting of parameters.The control panel duly ·ARD completewithnecessary SMFVRLA batteries.·wiredwithproper size & strength, copperwireforpower &controlcircuit,with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCAsheetwithpowdercoatingwith IP54 Protection class.General:-Job includes entire procedure of obtaining all necessary erection permissions & \"License to Work the Lift\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.·The above rate includes Fully Comprehensive AMCforoneyear fromthedateof commissioning\" |
| 718 | Dismantling the existing 20 Passenger/Stretcher/Goods lift of all types travelling G+4 floors (5 Landings/5Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes withcement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store andhanding over to the section engineer/store keeper in charge complete. |
| 719 | OPD BuildingSITCofElectricTractionPassengerLift with Rated capacity :20 Passenger/1360Kg Floors :- G+2floor(3Stops/3Landings)·Travel:-4 mtrs·Locationof Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landingdoorclear opening of 1200 mm wide x 2000 mm high ·Clear Car size of 1300mm wide x 2400mm deep x 2250mm high· Lift shaft availablehaving clear size of 2300mm wide x 3100mm deep, 1500mm Pit depth,5000mm Overhead.·Doors type:-COPO/TOPO Doorswithframemade fromSS304 grade solid(non-cladded) sheetof 1.5mm thick in hairline finishforcarandall landing doors with SSdoor architraves/frames The lift doors shall have minimum 1hourfire rating(with submissionofnecessaryvalidtest certificate issued byNABLaccredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safetyfactorof5, withToe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interiordesign shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD withaudio- visualalarm,VASinMarathi,Hindi& English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswithscrollingUP/DNLED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift cararrival&next traveldirectionaudio-visualindication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drivehaving closedloopcontrolsystem, with IBMS compatible having necessary port.The controller shall have necessaryprotections suchasovercurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc.various operation modes such as maintenance, changedirection by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility,auto returnto homelanding,firemanevacuation operation, earthquake operation,door open/close operation from COP etc. The system can record information ·Other mechanicalparts such as \"T\" section adequate size guide rails for car & counterweightwith brackets fasteners, counterweightframe with necessary blocks, buffers with necessary support arrangement, MS pitladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary forerectionof landing door frames and it\"s accessories e.g. sill, header, hole pass etc complete with plasterfinish,civil work forerection buffers,erectionofliftmachinery, adequate size core cuts if required & scaffolding forerecting guide rails, providing and fixing steel girders/RCCworkhavingadequatestrength for mounting and hoisting lift machine etc. complete as per specification no. LFT.· Firemancontrollerhavingfiremanswitchat fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proofDome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCCwithHDRdata backupformin. 90dayswithmin.18”FHDTV monitor,to be kept in FCC/LMRasdirectedby Engineer In Charge.·LiftMachineof Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assemblymountedon adequate size girders dulyfixedonLMRfloor/shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real-time clock managementandhandheld keypad with LCD screenforviewand setting of parameters.The control panel duly ·ARD completewithnecessary SMFVRLA batteries.·wiredwithproper size & strength, copperwireforpower &controlcircuit,with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCAsheetwithpowdercoatingwith IP54 Protection class.General:-Job includes entire procedure of obtaining all necessary erection permissions & \"License to Work the Lift\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.·The above rate includes Fully Comprehensive AMCforoneyear fromthedateof commissioning For Lift having 1200mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade solid (non- cladded) landing door [Two panel], this includes all necessaryaccessories like LOP\"s with UP/DN buttons-arrows- indicators, extension of guide rails, shaft wiringwithtrunking,travelingcables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessaryforthenormal safe functioning of lift installation complete. |
| 720 | Dismantling the existing 20 Passenger/Stretcher/Goods lift of all types travelling G+2 floors (3 Landings/3Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes withcement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store andhanding over to the section engineer/store keeper in charge complete. |
| 721 | V D Skin BuildingSITCofElectricTractionPassengerLift with Rated capacity :20 Passenger/1360Kg Floors :- G+2floor(3Stops/3Landings)·Travel:-4 mtrs·Locationof Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landingdoorclear opening of 1200 mm wide x 2000 mm high ·Clear Car size of 1300mm wide x 2400mm deep x 2250mm high· Lift shaft availablehaving clear size of 2300mm wide x 3100mm deep, 1500mm Pit depth,5000mm Overhead.·Doors type:-COPO/TOPO Doorswithframemade fromSS304 grade solid(non-cladded) sheetof 1.5mm thick in hairline finishforcarandall landing doors with SSdoor architraves/frames The lift doors shall have minimum 1hourfire rating(with submissionofnecessaryvalidtest certificate issued byNABLaccredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safetyfactorof5, withToe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interiordesign shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD withaudio- visualalarm,VASinMarathi,Hindi& English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswithscrollingUP/DNLED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift cararrival&next traveldirectionaudio-visualindication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drivehaving closedloopcontrolsystem, with IBMS compatible having necessary port.The controller shall have necessaryprotections suchasovercurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc.various operation modes such as maintenance, changedirection by attendant, full load bypass, VIP call operation, self levellingoperation, call cancel facility,auto returnto homelanding,firemanevacuation operation, earthquake operation,door open/close operation from COP etc. The system can record information ·Other mechanicalparts such as \"T\" section adequate size guide rails for car & counterweightwith brackets fasteners, counterweightframe with necessary blocks, buffers with necessary support arrangement, MS pitladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary forerectionof landing door frames and it\"s accessories e.g. sill, header, hole pass etc complete with plasterfinish,civil work forerection buffers,erectionofliftmachinery, adequate size core cuts if required & scaffolding forerecting guide rails, providing and fixing steel girders/RCCworkhavingadequatestrength for mounting and hoisting lift machine etc. complete as per specification no.LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCCwithHDRdata backup for min. 90 days with min.18” FHD TV monitor, tobe keptinFCC/LMRas directed by EngineerInCharge.·Lift MachineofGearless PMSMof suitable kW with duty cycleof minimum120 starts/hr(withsubmission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entireassemblymountedon adequatesize girdersdulyfixedonLMR floor/ shaftwalls completewith main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real-time clock managementandhandheld keypad with LCD screenforviewand setting of parameters.The control panel duly ·ARD completewithnecessary SMFVRLA batteries.·wiredwithproper size & strength, copperwireforpower &controlcircuit,with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCAsheetwithpowdercoatingwith IP54 Protection class.General:-Job includes entire procedure of obtaining all necessary erection permissions & \"License to Work the Lift\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.·The above rate includes Fully Comprehensive AMCforoneyear from thedateof commissioning |
| 722 | Dismantling the existing 20 Passenger/Stretcher/Goods lift of all types travelling G+2 floors (3 Landings/3Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes withcement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store andhanding over to the section engineer/store keeper in charge complete. |
| 723 | CJ BuildingSITCofElectricTractionPassengerLift with Rated capacity :20 Passenger/1360Kg Floors :- G+3floor(4Stops/4Landings)·Travel:-4 mtrs·Locationof Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landingdoorclear opening of 1200 mm wide x 2000 mm high ·Clear Car size of 1300mm wide x 2400mm deep x 2250mm high· Lift shaft availablehaving clearsizeof2300mmwidex3100mmdeep, 1500mmPitdepth,5000mm Overhead.·Doors type:-COPO/TOPO Doorswithframemade fromSS304 grade solid(non-cladded) sheetof 1.5mm thick in hairline finishforcarandall landing doors with SSdoor architraves/frames The lift doors shall have minimum 1hourfire rating(with submissionofnecessaryvalidtest certificate issued byNABLaccredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safetyfactorof5, withToe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interiordesign shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD withaudio- visualalarm,VASinMarathi,Hindi & English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswithscrollingUP/DNLED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift cararrival&next traveldirectionaudio-visualindication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drivehaving closedloopcontrolsystem, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protectionforphase loss at inputoroutputetc.various operation modes such asmaintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility,auto returnto homelanding,firemanevacuation operation, earthquake operation,door open/close operation from COP etc. The system can record information ·Other mechanicalparts such as \"T\" section adequate size guide rails for car & counterweight with brackets fasteners, counterweight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladderetc.erectedwithnecessarysteel work.·Minor civil work such as alteration work if anynecessaryforerectionof landing door frames and it\"s accessories e.g. sill, header, hole pass etc complete with plasterfinish,civil work forerection buffers,erectionofliftmachinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCCworkhavingadequatestrength for mounting and hoisting lift machine etc. complete as per specification no.LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCCwithHDRdata backup for min. 90 days with min.18” FHD TV monitor, tobe keptinFCC/LMRas directed by EngineerInCharge.·Lift MachineofGearless PMSMof suitable kW with duty cycleof minimum120 starts/hr(withsubmission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entireassemblymountedon adequatesize girdersdulyfixedonLMR floor/ shaftwalls completewith main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real-time clock managementandhandheld keypad with LCD screenforviewand setting of parameters.The control panel duly ·ARD completewithnecessary SMFVRLA batteries.·wiredwithproper size & strength, copperwireforpower &controlcircuit,with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCAsheetwithpowdercoatingwith IP54 Protection class.General:-Job includes entire procedure of obtaining all necessary erection permissions & \"License to Work the Lift\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.·The above rate includes Fully Comprehensive AMCforoneyear fromthedateof commissioning |
| 724 | Dismantling the existing 20 Passenger/Stretcher/Goods lift of all types travelling G+3 floors (4 Landings/4Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes withcementmortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete. |
| 725 | Providing removal of granite door photo frame ateachlandingdoorwithplaster&carrying necessary repairs to lift Hoistway,LMR & pit as per requirements with extensionof theLift pits depth & increasing Landing door height as perrequirementsbychisellingandfinishing complete with providing RCC with necessary steel lintel suitable for mounting Lift Landing doorProvidingandapplyingwhite-washin two coatsto theinside Lift shafts, pit and LMR in anapprovedmannercompleteand providinganderectionof theapprovedshade granitelanding doorphotoframeasperthe actualsiterequirementswithnecessarybase plasterandfinishinginanapprovedmanner withdisposal ofthedebrisaspermunicipal corporationguidelinesandmakingthesite clean in allrespectfor6nos13passngerLifthavingminimum clear entrance of 900mm wide x 2200mm high traveling Gnd+6Upper Floors as per the followingdetails&specificationsRemoving cementtiles,ormarbleordadowithoutbed concreteincludingstackingthematerialsas directedwithallleads,liftsetc. complete Removingthe existingcement plaster of any thicknesswithoutcausingdustnuisanceand stacking the debris or spreading in the compound and cleaning the site etc. complete. ExcavatingCCfoundationbychisellingfor preparing pit & clearing the site by removing debris & making the site as required complete. Makingcementconcretefoundationin1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete.Supplyinganderectingironworkconsisting of rods, bars, MS pipes, etc. for Steel in RCC oranyotherpurposewithbending,cutting, drillingandweldingcompleteerectedatthe position with necessary materialsProviding internalcementplaster20mmthickintwo coats in cement mortar 1:5 withoutneeru finish, toconcrete,bricksurface,inallpositions including scaffolding and curing etc.complete Providingandlayingtelephoneblack/Amba White/Cadburybrown/Rubyred/Ocean Brown granite stone of 18 to 20 mm thick for doorframeOnC.M.1:6includingfilling jointswithpolymerbasefillernosingthesharpedgeswherevernecessary,curing,etc. Providingandapplyingwhite-washintwo coats on old / new plastered or masonry surfaces and asbestos cement sheets including scaffolding and preparing the surface by brushingandbroomingdownetc.complete. Removing any kind of debris including loading intruck& conveyingto approoveddumping point beyond MCGM limits,unloading, spreading etc. complete |
| 726 | Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete. |
| 727 | Supplying and erecting modular type 3 pin 16A multi socket with safety shutter, duly erected on provided plate and box with wiringconnections complete. |
| 728 | Supplying and erecting PVC Surface modular switch box with doublemounting plate for 4 module duly erected. |
| 729 | Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modulartype switch, earthing and required accessories as per specification No: WG-PW/SW |
| 730 | Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., THD<10%, p.f. >0.95, operating range of 140- 260V, in built surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, IP66, IK09 rated on provided PVCBlock / wooden board with 3 years warranty. |
| 731 | Supplying and erecting CRCA powder coated corridor/passage light LED fitting (4 feet) Max. 17W with high transitivity diffuser with system lumens output of Min. 2000 lumens , min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 4 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block/ wooden board with 3 years warranty. |
| 732 | Supplying and erecting exhaust fan heavy duty 230 V, A.C. 50 cycles 375/380mm. 900 RPM complete erected in position as per specification no. FG-FN/EXF |
| 733 | Supplying & erecting 22 SWG G.I sheet metal cawl sector shaped with 25 x 25 x3 (mm) angle iron frame, metal mesh to avoid birds entry with necessary material,suitable for exhaust fan of 400 mm as per specification no FG-FAS/MSC |
| 734 | Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provideddistribution board as per specification no. SW- SWR/MCB |
| 735 | Supplying, erecting & marking DPMCB 6 A to 32 A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as perspecification no. SW-SWR/MCB |
| 736 | Supplying and erecting single pole and neutral distribution board (SPNDB),with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW- SWR/MCBDB |
| 737 | Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FPMCB/RCCB/RCBO complete erected on angle iron/GI frame. |
| 738 | Supplying, fixing and commissioning 2 pole,RCBO 6/10/16/20/25A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakageprotection, with 30/100/300 mA sensitivity and short circuit and earth leakagetrip indication as per specification no SW- RCCB/RCBO |
| 739 | Supplying, fixing and commissioning 4 pole RCBO 32/40A, with overcurrent, rated short- circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indicationas per specification no SW-RCCB/RCBO |
| 740 | Supplying, erecting & terminating FR XLPE insulated, galvanised steelformed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copperconductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 741 | Supplying, erecting & terminating FR XLPE insulated, galvanised steelformed wire armoured (strip) cable 1100 V, 2 core 2.5 sq. mm. copperconductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 742 | Supplying, erecting & terminating FR XLPE insulated, galvanised steelformed wire armoured (strip) cable 1100 V, 2 core 4 sq mm copperconductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 743 | Supplying, installation and testing of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth withrequired quantity complete, and recording the results Specification no. EA-MOBI |
| 744 | Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.=5*2*1=10mtr*25x6 mm -1.2 kg/mtr =12 kg |
| 745 | Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete.Outside of Building connection to GI Wire to flate=1 nos lift*2 Run*5 mtr each floor*8 floor+Horizontal distance 60mtr=140 mtr*0.103KG/MTR=27.81 |
| 746 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mmwidth & 100 mm height comprising all required standard accessories. |
| 747 | Dismantling of existing fluorescent fittings of any type & size. |
| 748 | Dismantling the existing ceiling fan /exhaust fan / cabin fan / bracket fan complete with accessories, G.I. down rod, frame etc. andmaking the site clear. |
| 749 | Dismantling the existing switchgears, DB, and bus bar of any size completewith/ without board or angle iron frame |
| 750 | Dismantling the existing cables of all types & size above 10 sq mm up to 50 sq.mm. |