|
| 1 | Installation of 3 feet height path way LED garden light fittings with proper cement concrete foundation at a depth of 0.5 mtrs. at main entrance of Shri.Babu Jagajeevan Ram Sports Complex as described in the Schedule –‘A’. |
| 2 | Supply and installation of FRP / Polycarbonate / Thermoplastic Modular control box as described in the Schedule –‘A’. |
| 3 | Supply and Installation of earthing as described in the Schedule –‘A’. |
| 4 | Supply and fixing of suitable size of IP66 heavy duty, 6 pole terminal block for loop in loop out copper cable connection at foundation level of each LED garden light fittings as described in the Schedule –‘A’.. |
| 5 | Supply of 3 core x 2.5 Sq.mm PVC round sheathed flexible copper conductor cable |
| 6 | Laying of 3 core x 2.5 Sq.mm PVC round sheathed flexible copper conductor cable as described in the Schedule –‘A’. |
| 7 | Earth excavation of 2 feet depth x 1 feet breadth from Main Switch Board in Room No.7 at sports complex to LED Garden light fittings No.1 to 40and re-closing the earth excavation with excavated soil and make it original level as described in the Schedule –‘A’. |
| 8 | Testing and commissioning of 40 Nos. 3 feet height path way LED garden light fittings as described in the Schedule –‘A’. |
| 9 | Supply of FRP / PC suitable size distribution boards. Each distribution board comprising of 1 No. 100 Amps 25 KA 4 Pole MCCB as incomer and 7 Nos. 32 Amps 2 Pole C-Series MCB as outgoing as described in Schedule ‘A’. |
| 10 | Installation of 2 Nos. FRP / PC suitable size distribution boards as DB No.1 and DB No.2 in the Meeting / Assembly hall of Higher Secondary School as described in Schedule ‘A’. |
| 11 | Supply FRP / PC suitable size distribution board. The distribution board comprising of 1 No. 63 Amps 4 Pole C-Series MCB as incomer and 5 Nos. 32 Amps 2 Pole C-Series MCB as outgoing as described in Schedule ‘A’. |
| 12 | Installation of FRP / PC suitable size distribution board in the library room as described in Schedule ‘A’. |
| 13 | Supply of 3 1/2 core x 50 sq.mm. UG aluminium armoured PVC XLPE LT Cable as described in Schedule ‘A’. |
| 14 | Laying / Clamping of 3 1/2 core x 50 sq.mm. UG aluminium armoured PVC XLPE LT Cable from Higher Secondary School pillar box to distribution box No.1 at first floor of the higher secondary school Meeting / Assembly hall. as described in Schedule ‘A’. |
| 15 | Supply of 3 1/2 core x 25 sq.mm. UG aluminium armoured PVC XLPE LT Cable as described in Schedule ‘A’. |
| 16 | Laying / Clamping of 3 1/2 core x 25 sq.mm. UG aluminium armoured PVC XLPE LT Cable from DB No.1 to DB No.2 at the Meeting / Assembly hall in Chennai Port and Dock Educational Higher Secondary School as described in Schedule ‘A’. andLaying / Clamping of 3 1/2 core x 25 sq.mm. UG aluminium armoured PVC XLPE LT Cable from Main Switch Board to FRP / Polycarbonate / Thermoplastic Modular Control box at Room No.7 in Shri.Babu Jagajeevan Ram Sports Complex as described in Schedule ‘A’. |
| 17 | 3” Concrete road cutting of 2 feet depth x 1 feet breadth from higher secondary school pillar box to eastern side of the higher secondary school building wall and rebuild the concrete road to original condition as described in the Schedule –‘A’. |
| 18 | Supply of 4 core x 16 sq.mm. UG aluminium armoured PVC XLPE LT Cable as described in Schedule ‘A’. |
| 19 | Laying / Clamping of 4 core x 16 sq.mm. UG aluminium armoured PVC XLPE LT Cable from first floor northern side near stair case Distribution Board to library room distribution board as described in Schedule ‘A’. |
| 20 | Supply 25 Amps C-Series 2 Pole MCB with enclosure for operating of each Air Conditioners as described in Schedule ‘A’. |
| 21 | Installation of 25 Amps C-Series 2 Pole MCB with enclosure for operating of each Air Conditioners in the Meeting /Assembly hall and library rooms on the first floor of higher secondary school as described in Schedule ‘A’. |
| 22 | Supply of all materials and accessories of suitable size of PVC pipe with 2 runs of 4 sq.mm and 1 run of 2.5 sq. mm for earth PVC insulated unsheathed copper conductor FR wires as described in Schedule ‘A’. |
| 23 | Surface conduit wiring by using suitable size of PVC pipe with 2 runs of 4 sq.mm and 1 run of 2.5 sq. mm for earth PVC insulated unsheathed copper conductor FR wiresa) from 6 Nos. of each 32 Amps 2 Pole C-Series MCB in the distribution board No.1 to 6 Nos. of each AC points in the Meeting/ Assembly hall and 1 No. 32 Amps 2 Pole C-Series MCB in the distribution board No.1 as spare as described in Schedule ‘A’.b) from 6 Nos. of each 32 Amps 2 Pole C-Series MCB in the distribution board No.2 to 6 Nos. of each AC points in the Meeting/ Assembly hall and 1 No. 32 Amps 2 Pole C-Series MCB in the distribution board No.2 as spare as described in Schedule ‘A’.c) from 4 Nos. of each 32 Amps 2 Pole C-Series MCB in the distribution board at library room to 4 Nos. of each AC points in the library rooms and 1 No. 32 Amps 2 Pole C-Series MCB in the distribution board as spare as described in Schedule ‘A’. |
| 24 | Removing of existing old / damaged concealed switch boxes with switches from the Meeting / Assembly hall on the first floor of Higher Secondary School as described in the Schedule –‘A’.’ |
| 25 | Supply of a) 16 module 5A Switch box with switch plate -as described in Schedule ‘A’. |
| 26 | Supply of b) 12 module 5A Switch box with switch plateas described in Schedule ‘A’. |
| 27 | Supply of c) 6 module 5A Switch box with switch plate as described in Schedule ‘A’ |
| 28 | Supply of d) 5A Switch as described in Schedule ‘A’ |
| 29 | Supply of e) 5A Socket as described in Schedule ‘A |
| 30 | Supply of f) 5A Electronic fan regulator as described in Schedule ‘A’. |
| 31 | Installation of concealed modular type switch boxes with switch plates, switches, sockets and fan regulators mentioned under Sl.No.22, in the place of the existing old concealed switch boxes in the Meeting / Assembly hall.The existing wires to be connected to the individual modular type switches & sockets in the newly fixed concealed modular type switch boxes as described in Schedule ‘A’. |
| 32 | Supply of 1 x 20 Watts LED, 230 V batten type cool white tube light as described in Schedule ‘A’. |
| 33 | Installation of 1 x 20 Watts LED, 230 V batten type cool white tube light in the old auditorium as described in Schedule ‘A’ |
| 34 | Supply of 1x50 watts LED flood light fittings made up of die cast aluminium housing with high power LED IP66 integral type with suitable GI bracket and adjustable wall mounting fittings as described in Schedule ‘A’. |
| 35 | Installation of 1x50 watts LED flood light fittings made up of die cast aluminium housing with high power LED IP66 integral type with suitable GI bracket and adjustable wall mounting fittings to be fixed on the old auditorium wall at higher secondary school as required at site as described in Schedule ‘A’. |
| 36 | Supply of distribution board with enclosures made up of FRP/ PC / Thermoplastic. The distribution board comprising of 1 No. 63 Amps C-Series 4 Pole MCB as incomer, 6 Nos. 32 A, C-Series, 4 Pole MCBs as outgoing, with suitable copper wire/bus bars for each phase and neutral along with all other components and accessories etc. as described in Schedule ‘A’. |
| 37 | Installation of distribution board with enclosures made up of FRP/ PC / Thermoplastic. The distribution board comprising of 1 No. 63 Amps C-Series 4 Pole MCB as incomer, 6 Nos. 32 A, C-Series, 4 Pole MCBs as outgoing, with suitable copper wire/bus bars for each phase and neutral along with all other components and accessories etc., to be mounted in the distribution board at the old auditorium of higher secondary school including making proper wiring etc., complete as described in Schedule ‘A’. |
| 38 | Excavation of 2 feet depth x 1 feet breadth for a distance of 55 mtrs. for laying of 3 1/2 core x 90 Sq.mm UG aluminium armoured PVC XLPE LT cable from Higher Secondary School pillar box to the distribution board in the old auditorium as described in Schedule ‘A’. |
| 39 | Supply of 3 1/2 core x 90 Sq.mm UG aluminium armoured PVC XLPE LT cable as described in Schedule ‘A’. |
| 40 | Laying / Clamping of 3 1/2 core x 90 Sq.mm UG aluminium armoured PVC XLPE LT cable. from Higher Secondary School pillar box to the distribution box in the old auditorium as described in Schedule ‘A’. |
| 41 | Supply of 5 Nos. 15 A / 5 A flush type modular switch with socket outlet along with base plates and switch box as described in Schedule ‘A’. |
| 42 | Installation of 5 Nos. 15 A / 5 A flush type modular switch with socket outlet along with base plates and switch box to be mounted on the old auditorium wall as described in Schedule ‘A’. |
| 43 | Supply and fixing of new modular type10 module 5A switch boxes with switch plates, 5A switches, 5A sockets and 5A fan regulators to be mounted on the old auditorium wall as described in Schedule ‘A’. |
| 44 | Supply and fixing of new modular type 12 module 5A switch boxes with switch plates, 5A switches, 5A sockets and 5A fan regulators to be mounted on the old auditorium wall as described in Schedule ‘A’. |
| 45 | Supply of all materials and accessories to carry out the surface conduit wiring by using suitable size of PVC pipe with 2 runs of 4 sq.mm and 1 run of 2.5 sq. mm for earth PVC insulated unsheathed copper conductor FR wires as described in Schedule ‘A’. |
| 46 | Wiring of 2 runs of 4 sq.mm and 1 run of 2.5 sq. mm for earth PVC insulated unsheathed copper conductor FR wiresa)from 2 Nos. 32 Amps 2 Pole C-Series MCB in the distribution board to 12 and 10 module modular type switch boxes in the old auditorium.b)from 1 No. 32 Amps 2 Pole C-Series MCB in the distribution board to 3 Nos. 15 A / 5 A flush type modular switch boxes as loop in & loop out in each 15 A / 5 A flush type modular switch boxes.c)from 1 No. 32 Amps 2 Pole C-Series MCB in the distribution board to 2 Nos. 15 A / 5 A flush type modular switch boxes as loop in & loop out in each 15 A / 5 A flush type modular switch boxes.d)from 2 Nos. 32 Amps 2 Pole C-Series MCB in the distribution board to 2 Nos. 15 A / 5 A flush type modular switch boxes as loop in & loop out in each 15 A / 5 A flush type modular switch boxes. |
| 47 | Supply of all materials and accessories to carry out the surface conduit wiring by suitable size of PVC pipe with 3 runs of 1.5 sq.mm. for phase, neutral and earth PVC insulated FR rated copper wire for ceiling fans, LED Tube light fittings, LED flood light fittings and wall mounting fans from new modular type 12 and 10 modular switch boxes to individual points. |
| 48 | Supply and installation of all materials and accessories to carry out the surface conduit wiring by suitable size of PVC pipe with 2 runs of 2.5 sq.mm phase, neutral and 1 run of 1.5 sq.mm for earth PVC insulated FR rated coper wire for 2 Nos. 5 A switch with 2 Nos. 5A sockets modular type switch boxes. |
| 49 | Supply and installation of 2 Nos. 5A switch with 2 Nos. 5A sockets modular type switch boxes for bottom of front side and back side both north and south side wall. |