| 1 | Safe carriage of following materials from Store centre or any other place to the respective site of work through the Kachha/Pacca roadincluding loading, unloading at the respective ends and erection of same including the work of dragging as per site requirement, jumphering of Transformer with 11 KV line through LT ABC cable, Weasal conductor etc.Cost of labour, T&P carrier etc. required for proper completion of work as per RESPO Norms/Estimate of the work. |
| 2 | ST Pole 11 Meter Long |
| 3 | ST Pole 09 Meter Long |
| 4 | Distribution Box with Clamp |
| 5 | Earthing of Pole |
| 6 | Stay Set Complete |
| 7 | 11 KV XLPE Cable 3x185sq.mm. (Underground) |
| 8 | ACSR Dog Conductor |
| 9 | ABC Cable 3x120+1x95+1x16 sq.mm. |
| 10 | 11 KV TPMO |
| 11 | 11 KV Fuse Set |
| 12 | L.T. PVCCable 3.5x150 mm. |
| 13 | 11 KV Pin Insulator |
| 14 | 11 KVPin with Nut |
| 15 | 11KV Disk Insulator |
| 16 | 11KV Diskfitting |
| 17 | Supply, fixing and erection of following materials as per site requirement as per RESPO Norms:- |
| 18 | Stone Pad |
| 19 | ABC Connector 120mm |
| 20 | Suspention Clamp with I Hook |
| 21 | Deadend Clamp withI Hook |
| 22 | 11 KV cable Jointing Kit 3x185sq.mm. |
| 23 | 160 mm. ODPN-4PE-80 grade uv stabliyed HDPE |
| 24 | Cross Bracing Angle |
| 25 | Top Channel |
| 26 | Dropper Channel |
| 27 | F Braket |
| 28 | 11 KV Tee off Chennal |
| 29 | Base Angle |
| 30 | GI Pile 6\" Dia |
| 31 | Pole Clamp |
| 32 | Danger Board with Clamp |
| 33 | Barbed wire |
| 34 | Aluminum winding wire |
| 35 | Aluminum Paint |
| 36 | Red Oxide Paint |
| 37 | Nut Bolt & Washer |
| 38 | AL Leg long Barrel |
| 39 | Number Plate with clamp |
| 40 | Road Restroration (Pacca Road) |
| 41 | After opening of HT & LT Connections, dismantalling of250 KVA KVA Distribution Transformer from double pole and its safe carriage from respective site to other site including loading & unloading at both ends and also mounting on double pole including proper jumpering from 11 KV line to the transformer and also connecting the LT site cables as per RESSPO Manual. |
| 42 | Construction of plinth at various 11/0.4 KV Sub-station suitable for distribution transformer having size 5’x 5’ x 5’ out which 2’ below the ground. Work will include digging of foundation 2’ deep & brick work with Ist class bricks having cement and sand mortar of ratio 1:6 on all the walls, each of 9” thickness. The area inside the wall shall be duly filled by mud up to the height of appropriate level from ground level and shall be duly watered & rammed. Above the filling C.C. of ration 1:6:12 (Cement sand and brick ballast) giving 4” layer shall be provided. Above C.C. layer RCC layer having 4” thickness and with ratio 1:2:4 of cement sand and stone ballast shall be provided Re-enforcement shall be provided by providing net of (8 Nos. + 8 Nos.) M.S. rods of size 10 mm dia and each of 5’ length in the middle of the top of C.C. layer. The plinth shall be plastered with 12mm thick plaster in ratio 1:4 at all sides. This work will include cost of labour, T&P and all material required for construction of plinth which shall be provided by the contractor as per RESSPO Norms. |
| 43 | Neutral & body earthing of Distribution Transformer installed at various 11/0.4 kV Sub-stations by digging of pit upto water level depth (approx. 125 feet) and then inserting 1-¼” dia GI pipe of ‘A’ grade, conforming to the requirement of IS specification and then connecting the top of the inserted pipe and transformer body through GI strip of size 40x6 mm with the help of nut and bolt or through gas welding, as per direction of supervising engineer. It includes the cost of all material labour, T&P, carrier etc. required for proper completion of work. The aforesaid work shall be carried out as per RESSPO norms. |
| 44 | Dismantling and removal of following material from the existing line and then stacking in the respective JE’s (Store) as per direction of Supervising Engineer. It includes the work of cartage, cost of labour, T&P carrier etc. required for proper completion of work. |
| 45 | Dismentling of old and used ST Pole |
| 46 | Dismentling of old and used Iron Scrap |
| 47 | Dismentling of Dog Conductor |