| 1 | 1.0)Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor singlecorecableinsurface/recessedmediumclassPVC conduit,withpianotypeswitch,phenoliclaminatedsheet,suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 2 | 2.0) Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 3 | 3.0)Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | 4.0)Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | 5.0) Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 6 | 5.1)2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 7 | 5.2)2 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 8 | 5.3) 4 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 9 | 6.0) Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 10 | 6.1)2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 11 | 6.2) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 12 | 6.3) 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 13 | 7.0) Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 14 | 8.0) Supply and replacement of fan regulator switch in the existing electric board i/c connection, testing etc. as required. |
| 15 | 9.0) Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and connections, painting etc. as required. |
| 16 | 10.0) Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size ofphenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. |
| 17 | 11.0) Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 18 | 11.1)5/6 A switch |
| 19 | 11.2)15/16 A switch |
| 20 | 11.3) 3 pin 5/6 A socket outlet |
| 21 | 11.4) 6 pin 15/16 A socket outlet |
| 22 | 12.0)Replacement & fixing following way, single pole & neutral, sheet steel, MCB distribution board, 240V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing testing & commissioning etc. as required.(But without MCB/RCCB/Isolator) |
| 23 | 12.1)16 way, Double door |
| 24 | 13.0) Replacement and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 25 | 13.1)Single pole |
| 26 | 13.2)Double Pole |
| 27 | 14.0)Supplying and fixing single pole blanking plate in the existingMCB DB complete etc. as required. |
| 28 | 15.0) Replacement of ultra bright (single side connection with very high efficency 20 watt approx.4 feet longLED luminaire with diffused cover in polycarbonate body with 5 year manfacturer warrently directly on wall / surface including connection with 1.5 mm2 FRLS PVC insulated copper conductor single core cable and earthing etc. includingtesting & commissionong as reqd. |
| 29 | 16.0) Replacement of lighting fittings / fixtures with indoor Surface/ceiling mounted approx. 2 ft.x2 ft LED Panel light of minimum 34 W with CRCA housing of min. 100 lm/W, with 5 year warranty/guarantee complete as required. |
| 30 | 17.0) Replacement & Installation of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitablefor 230 V, 50 Hz,i/c Testing and Commissioning single phase AC Supply, earthing etc. complete as required. |
| 31 | 18.0) Replacement and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 32 | 19.0) Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required. |
| 33 | 20.0) Providing and fixing 12mm MS Fan hooks/ clamps of standard shape and sizein existing RCC slab/any structure, including cutting chase, anchoring clamp to reinforcement bar, including cleaning, refilling, making good the chase with matching concrete, plastering and painting the exposed portion of the clamps complete. |
| 34 | 21.0) Replacement & installation of exhaust fan(metallic body) ofsize 12\" i/c connections,making good the damages ,iron angle & painting with screws,nuts & bolts etc. complete as required. |
| 35 | 22.0) Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 36 | 20 mm |
| 37 | 25 mm |
| 38 | 23.0) Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 39 | 20 mm |
| 40 | 25 mm |
| 41 | 24.0)Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.with charcoal/ coke and salt as required. |
| 42 | 25.0) Providing & fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/cable as required. |
| 43 | 26.0)Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 44 | 27.0) Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 45 | 28.0) Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in recessed steel/ PVC conduit as required. the existing surface28.1)1 x 1.5 sq. mm |
| 46 | 29.0) Providing and fixing 125 A, 16 KA,TP MCCB rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 47 | 30.0) Replacement & installationof 80 watt LED flood light fittings withIP 66 protection & impact resistance of IK-08 & min. luminous efficacy of 110 l/m with housing made up of aluminium pressure die-cast with toughened glass on existing surafaceincluding testing & commissioning dismantling of existing defective fittings complete as required. |
| 48 | 31.0) Supply of 2C X 10 Sq.mm. size of 1.1 KV grade multicore aluminium conductor XLPE insulated and PVC sheathed armoured cable as per IS : 7098:1988 with upto date amendments. |