| Sl. No. | Item Description |
| 1 | 11 KV DOUBLE POLE STRUCTURE |
| 2 | Supply, erection, testing and commissioning of 2 pole structure for providing 1 No. 11KV,200A GOS in accordance with IE rules, & local authority specification and drawings and comprising of the following. |
| 3 | a. 2 Nos. 11 mtr. long MS STEEL poles complete with, pole excavation, MS STEEL foundation, and back filling complete MS steel channel/angle iron etc. |
| 4 | b. 1 Set of cross arms, branching, clamps and painting complete with GI nut, bolts & washers as required (for GO & DO), LA connection. |
| 5 | c .1 set 11KV Insulator complete with spindles & hardware complete as required. |
| 6 | d .1 No. 11KV 400A TP Gang operated Air break switches complete with 25mm dia GI pipe operating machanism, handle & locking arrangement. |
| 7 | e. 1 set of 3 nos.11KV single pole drop out fuse complete with barrel fuses, and mounting arrangement. |
| 8 | f. 1 set (3 nos.) 11KV lightning arrestor and connecting to all phases. |
| 9 | g. 1 No. 150 mm dia GI pipe class \"B\" (for XLPE cable protection) as required. |
| 10 | h. 2 Set 50mm dia 3m long GI pipe earting with 25 x 6 mm GI earth strip complete as required (for GO & DO & LA) |
| 11 | i 1 nos. 11KV HT danger boards and 2 set of anticlimbing devices. |
| 12 | 11 KV DOUBLE POLE STRUCTURE |
| 13 | a. 2 Nos. 11 mtr. long MS STEEL poles complete with, pole excavation, MS STEEL foundation, and back filling complete MS steel channel/angle iron etc. |
| 14 | b. 1 Set of cross arms, branching, clamps and painting complete with GI nut, bolts & washers as required (for GO & DO), LA connection. |
| 15 | c .3 set 11KV Insulator complete with spindles & hardware complete as required. |
| 16 | e. 1 No. 150 mm dia GI pipe class \"B\" (for XLPE cable protection) as required. |
| 17 | f. 2 Set 50mm dia 3m long GI pipe earting with 25 x 3 mm GI earth strip complete as required |
| 18 | g. 1 nos. 11KV HT danger boards and 2 set of anticlimbing devices. |
| 19 | Supply, installing, testing and commissioning of INDOOR TYPE 11KV, HT VCB Panel Board\" having Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 11KV, 800Amp, 18.4kA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Internal Arc tested as per IEC 62271 - 200, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus-Bar of 8OOAmp, Earthing Truck of suitable making capacity along with safety interlocking for complete board \"and control voltage of 24V DCwith SCADA compatibility .The VCB Panel board supplied with mandatory spares such as 4 Nos. Trip Coil, 4 Nos. Closing Coil, 3 Nos. Spring Charging Motors, 2 Nos. Space Heaters, 2 Nos. Rack-in & Rack-out handle. The Board shall consist following panels : |
| 20 | 11 KV INCOMER VCB PANEL : |
| 21 | 11 KV, 800Amp, 18.4KA/3 Se, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated shunt type trip & close coils (24 V DC) |
| 22 | Current Transformer |
| 23 | 1 set of 3 Nos. Single Phase, 11 KV, 800/400/1+1+PS Class, core 1 : Class 5P10, 15VA, Core 2 :Class 0.5, 15VA and Core 3: PS Class for Transformer Differential Protection (PS Class: VK > 200V, Imag < 30mA @ Vk/2) |
| 24 | Potential Transformer |
| 25 | 1 set .of ,3 Nos. Draw-out Type Feeder Connected PTs having ratio 11KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protection. |
| 26 | Accessories : TNC Switeh, Panel Space Heater, Push Button Trip Circuit Healthy- Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local &. Remote Switch, Emergency Trip Button, AC &. DC control illumination lamp with switch 3 Pin plug with socket of 15 Amp., Local & remote Switch, Emergency Trip Button, AC & DC Control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device. |
| 27 | Indications: LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service position, AC & DC Healthy. |
| 28 | Metering Instruments : 1 No. Tri-vector Meter (Ace. CI. 0.5) of L&T/Secure make, 1 No. Digital Voltmeter (Acc. CI. 0.5) of Rishabh, AE &. Elmeasure make, 1 No. Digital Ammeter (Acc. CI. 0.5) of Rishabh, AE & Elmeasure make. |
| 29 | Protection & Auxiliary Relay : |
| 30 | 1 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing over Current (Low Set: 5% - 200% / High Set: 50% - 1600% in step of 1%), Earth Fault (Low Set: 5% - 200% / High Set: 50% - 1600% in steps of 1%). Relay wil/be communicable on IEC 603 Protocol. |
| 31 | 1 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (15% :. 90% in steps of 1 %), No Voltage Protection (3% ~ 20% in steps of 1V). Relay will be communicable on IEC 603 Protocol. |
| 32 | 1 No. Trip Circuit Supervision Relay |
| 33 | 1 No. High Speed Master Trip Relay |
| 34 | Additional Accessories and Features : |
| 35 | Electrical Interlocking between Incomers & Bus-Coupler to prevent mixing of suppliers. |
| 36 | Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated close & Trip coils. Type tested for Internal Arc for 18.4KA Vacuum Bottels, VCB &. Panel should be of same make. Control Circuit shall operate on 24V,DC except Spring Charging Motor &. Space eater which. shall operate on 24V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. |
| 37 | 11 KV OUT GOING VCB PANEL : |
| 38 | Same description as INCOMER PANEL above except following changes |
| 39 | Potential Transformer, Voltmeter, R - Y - \"B Phase Indication, Under Voltage +relay are not required in Outgoing Panels |
| 40 | Current Transformer : |
| 41 | 1 Set 3 Nos. Single Phase, 11 KV, 200/100/1+1, Core 1 : Class 5P1015 VA, Core-2 : Class 0.5., 15VA |
| 42 | 11 KV BUS-COUPLER VCB PANEL : |
| 43 | Same description as INCOMER PANEL above except following changes: |
| 44 | Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays 11KV 630 VCB Panel. |
| 45 | Supply of 11KV grade 3core Brand Stranded Compact Circular Aluminium Conductor, Conductor Screen With Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with extruded Semi Conducting Compound in combination with Copper Tape, cores laid up, innersheath of PVC tape, galvanised flat steel strip armoured and overall PVC Sheathed Cable conforming to IS 7098 / (PART-II) 1985 with latest amendments. |
| 46 | 240sq.mm 3 core |
| 47 | 300sq.mm 3 core |
| 48 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 49 | Above 120 sq. mm and upto 400 sq. mm |
| 50 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 51 | Above 120 sq. mm and upto 400 sq. mm |
| 52 | Laying of one number XLPE power cable of 11/33 kV grade of following size direct in ground by mechanical mean alongwith laying of pipe as required. |
| 53 | Above 120 sq. mm and upto 400 sq. mm |
| 54 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required . |
| 55 | 240sq.mm 3 core |
| 56 | 300sq.mm 3 core |
| 57 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : |
| 58 | 240sq.mm 3 core/300sq.mm 3 core |
| 59 | 300sq.mm 3 core |
| 60 | Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : |
| 61 | 240sq.mm 3 core/300sq.mm 3 core |
| 62 | 300sq.mm 3 core |
| 63 | Supply of Heavy density poly ethylene pipes ISI marked anti radiant grade OD-160mm dia PN-6 grade having minimum wall thickness 9.5mm as per IS Code 4984 with socket coupler with trenchless excavation system. Complete in all respects. |
| 64 | Unitised Sub Station (11KV / 415 V) 800 KVA With 1 I/C & 2 O/G (With Natural cooling) |
| 65 | Supply & InstallationOutdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Cu. Busbarand connections from transformer to LT ACB will be by busbar connections. |
| 66 | Unitised Sub Station will have the following equipment |
| 67 | H.T SWITCHGEAR |
| 68 | Three way, 11KV 630Amp. 25KA for 1 sec. SF6 insulated Non-Extensible compact switchgear consisting of two nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection. |
| 69 | RMU NON Extensible (2 isolators, 1 VCB with CU Busbar |
| 70 | Function type- 3 position disconnector and earthing switch equipped with separate drive unit. |
| 71 | 1. Operation of LBS manual |
| 72 | 2. Cable switch rating 11KV,630A, 25KA for 1 sec |
| 73 | 3. Cable bushing rating 630A. |
| 74 | 4. Cable cover- As per our standard. |
| 75 | 5. Fixed type capacitive voltage indication provided. |
| 76 | 6. ON/OFF/Earth indication on the front mimic of the panel. |
| 77 | 7. Bottom cable termination-suitable upto 1 No. 3C X 300sq.mm |
| 78 | 8. Cable entry bottom, front. |
| 79 | 9. Fault passage indicator (FPI)-E/F |
| 80 | FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. Breaker equipped with over current time release for transformer protection. |
| 81 | 1. VCB 11KV, 630A, 25kA/1sec. |
| 82 | 2. Operation of breaker-Manual |
| 83 | 3. Self powered electronic numerical protection relay providing over current and earth fault protection. |
| 84 | 4. Tape wound protection current transformer |
| 85 | 5. Capacitive voltage indication fixed type. |
| 86 | 6. ON, OFF, EARTH indication on the frount mimic of the panel |
| 87 | 7. Cable box for termination of cable. |
| 88 | 8. Cable cover stand. |
| 89 | 9. Emergency trip push button. |
| 90 | 10. Shunt trip coil. |
| 91 | 11. Operation counter. |
| 92 | 12. Ammeter. |
| 93 | RMU accessories- |
| 94 | Manual Operating handle-1nos. |
| 95 | Standard manometer for SF6 GAS pressure indication. |
| 96 | Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm |
| 97 | Transformer (Manufactured as per IS 1180 Level-II) |
| 98 | Type- ONAN, Hermatically sealed corrugated tack. |
| 99 | 1. Ratio- 11KV/433V |
| 100 | 2. Capacity 800KVA |
| 101 | 3. Vector group DYn11 |
| 102 | 4. Off load tappings +5% to -10% in steps of 2.5% |
| 103 | 5. Winding- Double wound copper |
| 104 | 6. Class of insulation-A |
| 105 | 7. Ambient temp. 40 degree C |
| 106 | 8. Temp. rise in oil over ambient- 40 deg. C |
| 107 | 9. Temp. rise in winding over ambient- 45 deg. C |
| 108 | Transformer Accessories |
| 109 | Oil Temperature indicator |
| 110 | LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar |
| 111 | 1. Voltage rating 433V |
| 112 | 2. Current rating- 1500 Amp. |
| 113 | L.T Panel |
| 114 | Incoming # 1 |
| 115 | 1600Amp. 50KA, 4P EDO ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture |
| 116 | ON, OFF TRIP lamp. |
| 117 | R/Y/B indicating lamp. |
| 118 | Multifunction meter |
| 119 | CT-1600/5A, CL1.0, 10VA |
| 120 | Incoming # 2 For Inbuilt 380KVAR APFC Panel |
| 121 | 800Amp. 50KA, TP ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel |
| 122 | ON, OFF TRIP lamp. |
| 123 | R/Y/B indicating lamp. |
| 124 | Multifunction meter |
| 125 | CT-800/5A, CL1.0, 10VA |
| 126 | ENCLOSURE for PSS |
| 127 | Rated temperature enclosure class should be K10 |
| 128 | Outdoor type 2mm thick galvenised enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for transformer compartment. The enclosure exterior shall be powder coated with PP based paint. HT & LT compartment will be provided with the door and pad locking arrengement. Transformer compartment will be provided with cover. The compartment illumination lamp with door operated switch shall be provided for lifting arrengement shall be provided with PSS. Base frame of PSS shall be 4mm thick |
| 129 | Earthing- Internal earthing connection by using 50X6 Aluminium strips. |
| 130 | Unitised Sub Station (11KV / 415 V) 800 KVA With 1 I/C & 3 O/G (With Natural cooling) |
| 131 | Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Busbarand connections from transformer to LT ACB will be by busbar connections. |
| 132 | Unitised Sub Station will have the following equipment |
| 133 | H.T SWITCHGEAR |
| 134 | Three way, 11KV 630Amp. 25KA for 1 sec. SF6 insulated Non-Extensible compact switchgear consisting of 3 nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection. |
| 135 | RMU NON Extensible (3 isolators, 1 VCB with CU Busbar |
| 136 | Function type- 3 position disconnector and earthing switch equipped with separate drive unit. |
| 137 | 1. Operation of LBS manual |
| 138 | 2. Cable switch rating 11KV,630A, 25KA for 1 sec |
| 139 | 3. Cable bushing rating 630A. |
| 140 | 4. Cable cover- As per our standard. |
| 141 | 5. Fixed type capacitive voltage indication provided. |
| 142 | 6. ON/OFF/Earth indication on the front mimic of the panel. |
| 143 | 7. Bottom cable termination-suitable upto 1 No. 3C X 300sq.mm |
| 144 | 8. Cable entry bottom, front. |
| 145 | 9. Fault passage indicator (FPI)-E/F |
| 146 | FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. Breaker equipped with over current time release for transformer protection. |
| 147 | 1. VCB 11KV, 630A, 25kA/1sec. |
| 148 | 2. Operation of breaker-Manual |
| 149 | 3. Self powered electronic numerical protection relay providing over current and earth fault protection. |
| 150 | 4. Tape wound protection current transformer |
| 151 | 5. Capacitive voltage indication fixed type. |
| 152 | 6. ON, OFF, EARTH indication on the frount mimic of the panel |
| 153 | 7. Cable box for termination of cable. |
| 154 | 8. Cable cover stand. |
| 155 | 9. Emergency trip push button. |
| 156 | 10. Shunt trip coil. |
| 157 | 11. Operation counter. |
| 158 | 12. Ammeter. |
| 159 | RMU accessories- |
| 160 | Manual Operating handle-1nos. |
| 161 | Standard manometer for SF6 GAS pressure indication. |
| 162 | Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm |
| 163 | Transformer (Manufactured as per IS 1180 Level-II) |
| 164 | Type- ONAN, Hermatically sealed corrugated tack. |
| 165 | 1. Ratio- 11KV/433V |
| 166 | 2. Capacity 800KVA |
| 167 | 3. Vector group DYn11 |
| 168 | 4. Off load tappings +5% to -10% in steps of 2.5% |
| 169 | 5. Winding- Double wound copper |
| 170 | 6. Class of insulation-A |
| 171 | 7. Ambient temp. 40 degree C |
| 172 | 8. Temp. rise in oil over ambient- 40 deg. C |
| 173 | 9. Temp. rise in winding over ambient- 45 deg. C |
| 174 | Transformer Accessories |
| 175 | Oil Temperature indicator |
| 176 | LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar |
| 177 | 1. Voltage rating 433V |
| 178 | 2. Current rating- 1500 Amp. |
| 179 | L.T Panel |
| 180 | Incoming # 1 |
| 181 | 1600Amp. 50KA, 4P EDO ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexure |
| 182 | ON, OFF TRIP lamp. |
| 183 | R/Y/B indicating lamp. |
| 184 | Multifunction meter |
| 185 | CT-1600/5A, CL1.0, 10VA |
| 186 | Incoming # 2 For Inbuilt 380KVAR APFC Panel |
| 187 | 800Amp. 50KA, TP ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel |
| 188 | ON, OFF TRIP lamp. |
| 189 | R/Y/B indicating lamp. |
| 190 | Multifunction meter |
| 191 | CT-800/5A, CL1.0, 10VA |
| 192 | ENCLOSURE for PSS |
| 193 | Rated temperature enclosure class should be K10 |
| 194 | Outdoor type 2mm thick galvenised enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for transformer compartment. The enclosure exterior shall be powder coated with PP based paint. HT & LT compartment will be provided with the door and pad locking arrengement. Transformer compartment will be provided with cover. The compartment illumination lamp with door operated switch shall be provided for lifting arrengement shall be provided with PSS. Base frame of PSS shall be 4mm thick |
| 195 | Earthing- Internal earthing connection by using 50X6 Aluminium strips. |
| 196 | Unitised Sub Station (11KV / 415 V) 400 KVA With 1 I/C & 2 O/G (With Natural cooling) |
| 197 | Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Busbarand connections from transformer to LT ACB will be by busbar connections. |
| 198 | Unitised Sub Station will have the following equipment |
| 199 | H.T SWITCHGEAR |
| 200 | Three way, 11KV 630Amp. 25KA for 1 sec. SF6 insulated Non-Extensible compact switchgear consisting of two nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection. |
| 201 | RMU NON Extensible (2 isolators, 1 VCB with Cu. Busbar |
| 202 | Function type- 3 position disconnector and earthing switch equipped with separate drive unit. |
| 203 | 1. Operation of LBS manual |
| 204 | 2. Cable switch rating 11KV,630A, 25kA/1sec. |
| 205 | 3. Cable bushing rating 630A. |
| 206 | 4. Cable cover- As per our standard. |
| 207 | 5. Fixed type capacitive voltage indication provided. |
| 208 | 6. ON/OFF/Earth indication on the front mimic of the panel. |
| 209 | 7. Bottom cable termination-suitable upto 1 no. 3C X 300sq.mm |
| 210 | 8. Cable entry bottom, front. |
| 211 | 9. Fault passage indicator (FPI)-E/F |
| 212 | FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. T2 equipped with over current time release for transformer protection. |
| 213 | 1. VCB 11KV, 630A, 25kA/1sec. |
| 214 | 2. Operation of breaker-Manual |
| 215 | 3. Self powered electronic numerical protection relay providing over current and earth fault protection. |
| 216 | 4. Tape wound protection current transformer |
| 217 | 5. Capacitive voltage indication fixed type. |
| 218 | 6. ON, OFF, EARTH indication on the frount mimic of the panel |
| 219 | 7. Cable box for termination of cable. |
| 220 | 8. Cable cover stand. |
| 221 | 9. Emergency trip push button. |
| 222 | 10. Shunt trip coil. |
| 223 | 11. Operation counter. |
| 224 | 12. Ammeter. |
| 225 | RMU accessories- |
| 226 | Manual Operating handle-1nos. |
| 227 | Standard manometer for SF6 GAS pressure indication. |
| 228 | Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm |
| 229 | Transformer (Manufactured as per IS 1180 Level-II) |
| 230 | Type- ONAN, Hermatically sealed corrugated tack. |
| 231 | 1. Ratio- 11KV/433V |
| 232 | 2. Capacity 400KVA |
| 233 | 3. Vector group DYn11 |
| 234 | 4. off load tappings +5% to -10% in steps of 2.5% |
| 235 | 5. Winding- Double wound copper |
| 236 | 6. Class of insulation-A |
| 237 | 7. Ambient temp. 40 degree C |
| 238 | 8. Temp. rise in oil over ambient- 40 deg. C |
| 239 | 9. Temp. rise in winding over ambient- 45 deg. C |
| 240 | Transformer Accessories |
| 241 | Oil Temperature indicator |
| 242 | LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar |
| 243 | 1. Voltage rating 433V |
| 244 | 2. Current rating- 1000 Amp. |
| 245 | L.T Panel |
| 246 | Incoming |
| 247 | 800Amp. 50KA, 4P EDO ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture |
| 248 | ON, OFF TRIP lamp. |
| 249 | R/Y/B indicating lamp. |
| 250 | Multifunction meter |
| 251 | CT-1000/5A, CL1.0, 10VA |
| 252 | Incoming # 2 For Inbuilt 200KVAR APFC Panel |
| 253 | 400Amp. 50KA, TP MCCB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel |
| 254 | ON, OFF TRIP lamp. |
| 255 | R/Y/B indicating lamp. |
| 256 | Multifunction meter |
| 257 | CT-400/5A, CL1.0, 10VA |
| 258 | Earthing- Internal earthing connection by using 50X6 Aluminium strips. |
| 259 | Unitised Sub Station (11KV / 415 V) 250 KVA With 1 I/C & 3 O/G (With Natural cooling) |
| 260 | Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Busbarand connections from transformer to LT ACB will be by busbar connections. |
| 261 | Unitised Sub Station will have the following equipment |
| 262 | H.T SWITCHGEAR |
| 263 | Three way, 11KV 630Amp. 25KA for 1sec. SF6 insulated Non-Extensible compact switchgear consisting of two nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection. |
| 264 | RMU NON Extensible (3 isolators, 1 VCB with AL Busbar |
| 265 | Function type- 3 position disconnector and earthing switch equipped with separate drive unit. |
| 266 | 1. Operation of LBS manual |
| 267 | 2. Cable switch rating 11KV,630A, 25kA/1sec. |
| 268 | 3. Cable bushing rating 630A. |
| 269 | 4. Cable cover- As per our standard. |
| 270 | 5. Fixed type capacitive voltage indication provided. |
| 271 | 6. ON/OFF/Earth indication on the front mimic of the panel. |
| 272 | 7. Bottom cable termination-suitable upto 1 no. 3C X 300sq.mm |
| 273 | 8. Cable entry bottom, front. |
| 274 | 9. Fault passage indicator (FPI)-E/F |
| 275 | FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. T2 equipped with over current time release for transformer protection. |
| 276 | 1. VCB 11KV, 630A, 25kA/1sec. |
| 277 | 2. Operation of breaker-Manual |
| 278 | 3. Self powered electronic numerical protection relay providing over current and earth fault protection. |
| 279 | 4. Tape wound protection current transformer |
| 280 | 5. Capacitive voltage indication fixed type. |
| 281 | 6. ON, OFF, EARTH indication on the frount mimic of the panel |
| 282 | 7. Cable box for termination of cable. |
| 283 | 8. Cable cover stand. |
| 284 | 9. Emergency trip push button. |
| 285 | 10. Shunt trip coil. |
| 286 | 11. Operation counter. |
| 287 | 12. Ammeter. |
| 288 | RMU accessories- |
| 289 | Manual Operating handle-1nos. |
| 290 | Standard manometer for SF6 GAS pressure indication. |
| 291 | Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm |
| 292 | Transformer (Manufactured as per IS 1180 Level-II) |
| 293 | Type- ONAN, Hermatically sealed corrugated tack. |
| 294 | 1. Ratio- 11KV/433V |
| 295 | 2. Capacity 250KVA |
| 296 | 3. Vector group DYn11 |
| 297 | 4. off load tappings +5% to -10% in steps of 2.5% |
| 298 | 5. Winding- Double wound copper |
| 299 | 6. Class of insulation-A |
| 300 | 7. Ambient temp. 40 degree C |
| 301 | 8. Temp. rise in oil over ambient- 40 deg. C |
| 302 | 9. Temp. rise in winding over ambient- 45 deg. C |
| 303 | Transformer Accessories |
| 304 | Oil Temperature indicator |
| 305 | LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar |
| 306 | 1. Voltage rating 433V |
| 307 | 2. Current rating- 500 Amp. |
| 308 | L.T Panel |
| 309 | Incoming |
| 310 | 500Amp. 50KA, 4P MCCB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture |
| 311 | ON, OFF TRIP lamp. |
| 312 | R/Y/B indicating lamp. |
| 313 | Multifunction meter |
| 314 | CT-630/5A, CL1.0, 10VA |
| 315 | Incoming # 2 For Inbuilt 125KVAR APFC Panel |
| 316 | 250Amp. 50KA, TP MCCB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel |
| 317 | ON, OFF TRIP lamp. |
| 318 | R/Y/B indicating lamp. |
| 319 | Multifunction meter |
| 320 | CT-250/5A, CL1.0, 10VA |
| 321 | ENCLOSURE for PSS |
| 322 | Rated temperature enclosure class should be K10 |
| 323 | Outdoor type 2mm thick galvenised enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for transformer compartment. The enclosure exterior shall be powder coated with PP based paint. HT & LT compartment will be provided with the door and pad locking arrengement. Transformer compartment will be provided with cover. The compartment illumination lamp with door operated switch shall be provided for lifting arrengement shall be provided with PSS. Base frame of PSS shall be 4mm thick. |
| 324 | Earthing- Internal earthing connection by using 50X6 Aluminium strips. |
| 325 | Construction of fencing & shed work |
| 326 | Supply & Construction of fencing & shed work arround the CSS & Panel including excavation refilling, painting etc. as required as per details given below:- |
| 327 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. |
| 328 | Ordinary rock |
| 329 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 330 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 331 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: |
| 332 | Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 333 | Structural steel work in single section, fixed with or without connecting plate,including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 334 | CEMENT PLASTER (IN FINE SAND) |
| 335 | 12 mm cement plaster of mix : |
| 336 | 1:6 (1 cement: 6 fine sand) |
| 337 | R.C.C. Standards post/ struts/rails/ pales of mix 1:1.5:3 (1 cement : 1.5 coarsesand : 3 graded stone aggregate 12.5 mm nominal size) with wooden plugs or 6mm bar nibs wherever required as per direction of Engineer-incharge (cost of earth works in excavation, concrete works in foundation to be paid separately). |
| 338 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. |
| 339 | Made of G.I. wire of dia 4 mm |
| 340 | Providing corrugated G.S. sheet roofing including vertical / curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 341 | 1.00 mm thick with zinc coating not less than 275 gm/m² |
| 342 | SUB STATION SAFETY EQUIPMENT : |
| 343 | Supplying and fixing 1800 mm x 900 mm wide checkered rubber matting conforming to IS5424-1969 complete as required. |
| 344 | Suitable for 11KV |
| 345 | Supplying & fixing standard shock treatment charts in English & Hindi duly framed and covered with glass. |
| 346 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 347 | Supplyand erection of ISI marked portable fire extinguishers, wall mounted type, wall brackets complete in all respects, including fixing on walls as per the direction of engineer-in-charge. (CO2 gastype 6.5 kg. Capacity) |
| 348 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 349 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 350 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 351 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 352 | HOSPITAL BUILDING MAIN L.T PANEL |
| 353 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 354 | The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall haveAMF facilityto achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfaultprotection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec) |
| 355 | Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec).MCCB, with microprocessor release with protection functionLCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics) |
| 356 | INCOMING |
| 357 | 4 Nos. 800 Amp FP EDO ACB 50KA , |
| 358 | BUSCOUPLER |
| 359 | 1 Nos. 800Amp ACB 50KA , |
| 360 | AUTO OPERATION OF INCOMER / BUSCOUPLERACB\"s. |
| 361 | Load Management through PLC |
| 362 | Contactor for Load Management System |
| 363 | Auto changeover. |
| 364 | Buscoupler switching. |
| 365 | Electrial & Mechnical Interlocking. |
| 366 | BUSBARS |
| 367 | 2 Nos. 1000 Amp TPN busbars of aluminium alloy . |
| 368 | OUTGOING |
| 369 | 6Nos. 200 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 370 | 3Nos. 500 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 371 | 1Nos. 400 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 372 | 2Nos. 315 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 373 | 2 Nos. 250 Amp FP MCCB50 kA, with On, Off Indication lamp and A/V/KW meter |
| 374 | 2 Nos. 160 Amp FP MCCB50 kA, with On, Off Indication lamp and A/V/KW meter |
| 375 | 1 Nos. 125 Amp FP MCCB50 kA, with On, Off Indication lamp and A/V/KW meter |
| 376 | 4 Nos. 100 Amp FP MCCB50 kA, with On, Off Indication lamp and A/V/KW meter |
| 377 | INSTRUMENTS |
| 378 | 4 sets of multifunction meter with parameter current, voltage, KWH, KVAH, Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 379 | 4 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 380 | 4 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 381 | 4 Sets auto trip indicating lamp . |
| 382 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 383 | Short Circuit Breaking capacity should not less than 50KA. |
| 384 | RELAYS |
| 385 | MEDICINE WARD & BURN WARD SIDE L.T PANEL |
| 386 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 387 | The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall haveAMF facilityto achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfaultprotection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec) |
| 388 | Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec). MCCB, with microprocessor release with protection functionLCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics) |
| 389 | INCOMING |
| 390 | 1 Nos. 315 Amp FP MCCB 25 kA, |
| 391 | BUSBARS |
| 392 | 1 Nos. 400 Amp TPN busbars of aluminium alloy . |
| 393 | OUTGOING |
| 394 | 1 Nos. 160 Amp FP MCCB 25 kA, with On, Off Indication lamp and A/V/KW meter |
| 395 | 5 Nos. 125 Amp FP MCCB 25 kA, with On, Off Indication lamp and A/V/KW meter |
| 396 | INSTRUMENTS |
| 397 | 1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. With RS 485 |
| 398 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 399 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 400 | 1 Sets auto trip indicating lamp . |
| 401 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 402 | Short Circuit Breaking capacity should not less than 25KA. |
| 403 | RELAYS |
| 404 | ICU & EMERGENCY BLOCK MAIN L.T PANEL |
| 405 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 406 | The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall haveAMF facilityto achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfaultprotection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec) |
| 407 | Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec).MCCB, with microprocessor release with protection functionLCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics) |
| 408 | INCOMING |
| 409 | 4 Nos. 800 Amp FP EDO ACB 50KA , |
| 410 | BUSCOUPLER |
| 411 | 1 Nos. 800Amp ACB 50KA , |
| 412 | AUTO OPERATION OF INCOMER / BUSCOUPLERACB\"s. |
| 413 | Load Management through PLC |
| 414 | Contactor for Load Management System |
| 415 | Auto changeover. |
| 416 | Buscoupler switching. |
| 417 | Electrial & Mechnical Interlocking. |
| 418 | BUSBARS |
| 419 | 2 Nos. 1000 Amp TPN busbars of aluminium alloy . |
| 420 | OUTGOING |
| 421 | 2Nos. 800 Amp FP EDO ACB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 422 | 2Nos. 500 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 423 | 2Nos. 400 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 424 | 2Nos. 250 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 425 | 2Nos. 200 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 426 | 2Nos. 63 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 427 | INSTRUMENTS |
| 428 | 4 sets of multifunction meter with parameter current, voltage, KWH, KVAH, Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 429 | 4 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 430 | 4 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 431 | 4 Sets auto trip indicating lamp . |
| 432 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 433 | Short Circuit Breaking capacity should not less than 50KA. |
| 434 | RELAYS |
| 435 | OPD BLOCK MAIN L.T PANEL |
| 436 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 437 | The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall haveAMF facilityto achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfaultprotection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec) |
| 438 | Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec).MCCB, with microprocessor release with protection functionLCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics) |
| 439 | INCOMING |
| 440 | 1 Nos. 1600 Amp FP EDO ACB 50KA , |
| 441 | 2 Nos. 800 Amp FP EDO ACB 50KA , |
| 442 | AUTO OPERATION OF INCOMER / BUSCOUPLERACB\"s. |
| 443 | Load Management through PLC |
| 444 | Contactor for Load Management System |
| 445 | Auto changeover. |
| 446 | Buscoupler switching. |
| 447 | Electrial & Mechnical Interlocking. |
| 448 | BUSBARS |
| 449 | 1 Nos. 2000 Amp TPN busbars of aluminium alloy . |
| 450 | OUTGOING |
| 451 | 1Nos. 1000 Amp FP EDO ACB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 452 | 1Nos. 800 Amp FP EDO ACB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 453 | 4Nos. 500 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 454 | INSTRUMENTS |
| 455 | 3 sets of multifunction meter with parameter current, voltage, KWH, KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 456 | 3 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 457 | 3 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 458 | 3 Sets auto trip indicating lamp . |
| 459 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 460 | Short Circuit Breaking capacity should not less than 50KA. |
| 461 | RELAYS |
| 462 | NURSES HOSTEL & RESIDENCES OUTDOOR TYPE PANEL |
| 463 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 464 | INCOMING |
| 465 | 1 Nos. 500 Amp FP MCCB 25 KA, |
| 466 | BUSBARS |
| 467 | 1 Nos. 630 Amp TPN busbars of aluminium alloy . |
| 468 | OUTGOING |
| 469 | 1 Nos. 200 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 470 | 1 Nos. 125 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 471 | 3 Nos. 100 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 472 | 2 Nos. 63 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 473 | INSTRUMENTS |
| 474 | 1 sets of multifunction meter with parameter current, voltage, KWH, KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 475 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 476 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 477 | 1 Sets auto trip indicating lamp . |
| 478 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 479 | Short Circuit Breaking capacity should not less than 25KA. |
| 480 | RELAYS |
| 481 | NURSES HOSTEL MAIN L.T PANEL |
| 482 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 483 | INCOMING |
| 484 | 1 Nos. 200 Amp FP MCCB 25 KA, |
| 485 | BUSBARS |
| 486 | 1 Nos. 250 Amp TPN busbars of aluminium alloy . |
| 487 | OUTGOING |
| 488 | 5 Nos. 100 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 489 | 1 Nos. 63 Amp TP MCCB50 KA, with On, Off Indication lamp and A/V/KW meter |
| 490 | INSTRUMENTS |
| 491 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 492 | 1 sets of 0-200Amp. digital type ammeter with ammeter selector switch. |
| 493 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 494 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 495 | 1 Sets auto trip indicating lamp . |
| 496 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 497 | Short Circuit Breaking capacity should not less than 25KA. |
| 498 | RELAYS |
| 499 | 12 FLAT NURSES BLOCK METER PANEL 1/2 |
| 500 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 501 | INCOMING |
| 502 | 1 Nos. 100 Amp FP MCCB 25 KA, |
| 503 | BUSBARS |
| 504 | 1 Nos. 125 Amp TPN busbars of aluminium alloy . |
| 505 | OUTGOING |
| 506 | 14 Nos. 40 Amp DP MCB |
| 507 | 12Nos. 40Amp. KWh 1 Phase Energy meter |
| 508 | INSTRUMENTS |
| 509 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 510 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 511 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 512 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 513 | 1 Sets auto trip indicating lamp . |
| 514 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 515 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 516 | RELAYS |
| 517 | 13 FLAT NURSES BLOCK METER PANEL 3/4 |
| 518 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 519 | INCOMING |
| 520 | 1 Nos. 100 Amp FP MCCB 25 KA, |
| 521 | BUSBARS |
| 522 | 1 Nos. 125 Amp TPN busbars of aluminium alloy . |
| 523 | OUTGOING |
| 524 | 15 Nos. 40 Amp DP MCB |
| 525 | 13Nos. 40Amp. KWh 1 Phase Energy meter |
| 526 | INSTRUMENTS |
| 527 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 528 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 529 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 530 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 531 | 1 Sets auto trip indicating lamp . |
| 532 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 533 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 534 | RELAYS |
| 535 | MARRIED DOCTOR NRH HOSTEL & WARD BLOCK |
| 536 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 537 | INCOMING |
| 538 | 1 Nos. 1250 Amp FP EDO ACB 50 KA, |
| 539 | BUSBARS |
| 540 | 1 Nos. 1600 Amp TPN busbars of aluminium alloy . |
| 541 | OUTGOING |
| 542 | 3 Nos. 400 Amp FP MCCB 50 KA, with On, Off Indication lamp and A/V/KW meter |
| 543 | 2 Nos. 250 Amp FP MCCB 50 KA, with On, Off Indication lamp and A/V/KW meter |
| 544 | 1 Nos. 200 Amp FP MCCB 50 KA, with On, Off Indication lamp and A/V/KW meter |
| 545 | 2 Nos. 125 Amp TP MCCB50 KA, with On, Off Indication lamp and A/V/KW meter |
| 546 | INSTRUMENTS |
| 547 | 1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 548 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 549 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 550 | 1 Sets auto trip indicating lamp . |
| 551 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 552 | Short Circuit Breaking capacity should not less than 50KA. |
| 553 | RELAYS |
| 554 | MARRIED DOCTOR HOSTEL L.T PANEL |
| 555 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 556 | INCOMING |
| 557 | 1 Nos. 400 Amp FP MCCB 25 KA, |
| 558 | BUSBARS |
| 559 | 1 Nos. 500 Amp TPN busbars of aluminium alloy . |
| 560 | OUTGOING |
| 561 | 5 Nos. 125 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 562 | 1 Nos. 63 Amp TP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 563 | INSTRUMENTS |
| 564 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 565 | 1 sets of 0-400Amp. digital type ammeter with ammeter selector switch. |
| 566 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 567 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 568 | 1 Sets auto trip indicating lamp . |
| 569 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 570 | Short Circuit Breaking capacity should not less than 25KA. |
| 571 | RELAYS |
| 572 | 12 FLAT DOCTORS BLOCK METER PANEL 1/2/3/4 |
| 573 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 574 | INCOMING |
| 575 | 1 Nos. 125 Amp FP MCCB 25 KA, |
| 576 | BUSBARS |
| 577 | 1 Nos. 150 Amp TPN busbars of aluminium alloy . |
| 578 | OUTGOING |
| 579 | 14 Nos. 40 Amp FP MCB |
| 580 | 12Nos. 40Amp. KWh 3 Phase Energy meter |
| 581 | INSTRUMENTS |
| 582 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 583 | 1 sets of 0-150Amp. digital type ammeter with ammeter selector switch. |
| 584 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 585 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 586 | 1 Sets auto trip indicating lamp . |
| 587 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 588 | Cost of 3 Phase Energy meter is inclusive in above rates. |
| 589 | RELAYS |
| 590 | NRH HOSTEL L.T PANEL |
| 591 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 592 | INCOMING |
| 593 | 1 Nos. 400 Amp FP MCCB 25 KA, |
| 594 | BUSBARS |
| 595 | 1 Nos. 500 Amp TPN busbars of aluminium alloy . |
| 596 | OUTGOING |
| 597 | 3 Nos. 160 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 598 | 1 Nos. 125 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 599 | 1 Nos. 63 Amp TP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 600 | INSTRUMENTS |
| 601 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 602 | 1 sets of 0-400Amp. digital type ammeter with ammeter selector switch. |
| 603 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 604 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 605 | 1 Sets auto trip indicating lamp . |
| 606 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 607 | Short Circuit Breaking capacity should not less than 25KA. |
| 608 | RELAYS |
| 609 | PRIVATE WARD MAIN L.T PANEL |
| 610 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 611 | INCOMING |
| 612 | 1 Nos. 250 Amp FP MCCB 25 KA, |
| 613 | BUSBARS |
| 614 | 1 Nos. 320 Amp TPN busbars of aluminium alloy . |
| 615 | OUTGOING |
| 616 | 6 Nos. 125 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 617 | INSTRUMENTS |
| 618 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 619 | 1 sets of 0-250Amp. digital type ammeter with ammeter selector switch. |
| 620 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 621 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 622 | 1 Sets auto trip indicating lamp . |
| 623 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 624 | Short Circuit Breaking capacity should not less than 25KA. |
| 625 | RELAYS |
| 626 | 4TH CLASS EMPLOYEE TYPE-1 RESIDENTIAL AREA MAIN L.T PANEL (OUTDOOR TYPE) |
| 627 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 628 | INCOMING |
| 629 | 1 Nos. 800 Amp FP EDO ACB 25 KA, |
| 630 | BUSBARS |
| 631 | 1 Nos. 1000 Amp TPN busbars of aluminium alloy . |
| 632 | OUTGOING |
| 633 | 3 Nos. 125 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 634 | 8 Nos. 100 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 635 | 3 Nos. 63 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 636 | INSTRUMENTS |
| 637 | 1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 638 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 639 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 640 | 1 Sets auto trip indicating lamp . |
| 641 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 642 | Short Circuit Breaking capacity should not less than 25KA. |
| 643 | RELAYS |
| 644 | Type-II Block Main L.T Panel |
| 645 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 646 | INCOMING |
| 647 | 1 Nos. 125 Amp FP MCCB 25 KA, |
| 648 | BUSBARS |
| 649 | 1 Nos. 150 Amp TPN busbars of aluminium alloy . |
| 650 | OUTGOING |
| 651 | 2 Nos. 100 Amp DP MCB |
| 652 | 2 Nos. 63 Amp DP MCB |
| 653 | INSTRUMENTS |
| 654 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 655 | 1 sets of 0-150Amp. digital type ammeter with ammeter selector switch. |
| 656 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 657 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 658 | 1 Sets auto trip indicating lamp . |
| 659 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 660 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 661 | RELAYS |
| 662 | 12 TYPE-II RESIDENCE OUTDOOR TYPE METER PANEL 1/2/3/4 |
| 663 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 664 | INCOMING |
| 665 | 1 Nos. 100 Amp FP MCCB 25 KA, |
| 666 | BUSBARS |
| 667 | 1 Nos. 150 Amp TPN busbars of aluminium alloy . |
| 668 | OUTGOING |
| 669 | 15 Nos. 40 Amp DP MCB |
| 670 | 12Nos. 40Amp. KWh 1 Phase Energy meter |
| 671 | INSTRUMENTS |
| 672 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 673 | 1 sets of 0-150Amp. digital type ammeter with ammeter selector switch. |
| 674 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 675 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 676 | 1 Sets auto trip indicating lamp . |
| 677 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 678 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 679 | RELAYS |
| 680 | 17/15 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2 |
| 681 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 682 | INCOMING |
| 683 | 1 Nos. 100 Amp FP MCCB 25 KA, |
| 684 | BUSBARS |
| 685 | 1 Nos. 150 Amp TPN busbars of aluminium alloy . |
| 686 | OUTGOING |
| 687 | 18 Nos. 40 Amp DP MCB |
| 688 | 17Nos. 40Amp. KWh 1 Phase Energy meter |
| 689 | INSTRUMENTS |
| 690 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 691 | 1 sets of 0-150Amp. digital type ammeter with ammeter selector switch. |
| 692 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 693 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 694 | 1 Sets auto trip indicating lamp . |
| 695 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 696 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 697 | RELAYS |
| 698 | 13 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2 |
| 699 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 700 | INCOMING |
| 701 | 1 Nos. 100 Amp FP MCCB 25 KA, |
| 702 | BUSBARS |
| 703 | 1 Nos. 125 Amp TPN busbars of aluminium alloy . |
| 704 | OUTGOING |
| 705 | 14 Nos. 40 Amp DP MCB |
| 706 | 13Nos. 40Amp. KWh 1 Phase Energy meter |
| 707 | INSTRUMENTS |
| 708 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 709 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 710 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 711 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 712 | 1 Sets auto trip indicating lamp . |
| 713 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 714 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 715 | RELAYS |
| 716 | 11 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2 |
| 717 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 718 | INCOMING |
| 719 | 1 Nos. 100 Amp FP MCCB 25 KA, |
| 720 | BUSBARS |
| 721 | 1 Nos. 125 Amp TPN busbars of aluminium alloy . |
| 722 | OUTGOING |
| 723 | 12 Nos. 40 Amp DP MCB |
| 724 | 11Nos. 40Amp. KWh 1 Phase Energy meter |
| 725 | INSTRUMENTS |
| 726 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 727 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 728 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 729 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 730 | 1 Sets auto trip indicating lamp . |
| 731 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 732 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 733 | RELAYS |
| 734 | 8 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2 |
| 735 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 736 | INCOMING |
| 737 | 1 Nos. 100 Amp FP MCCB 25 KA, |
| 738 | BUSBARS |
| 739 | 1 Nos. 125 Amp TPN busbars of aluminium alloy . |
| 740 | OUTGOING |
| 741 | 9 Nos. 40 Amp DP MCB |
| 742 | 8Nos. 40Amp. KWh 1 Phase Energy meter |
| 743 | INSTRUMENTS |
| 744 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 745 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 746 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). |
| 747 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker). |
| 748 | 1 Sets auto trip indicating lamp . |
| 749 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 750 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 751 | RELAYS |
| 752 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge ,complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 753 | 6 sq. mm 2 core |
| 754 | 10 sq. mm 2 core |
| 755 | 25 sq. mm 3-1/2 core |
| 756 | 35 sq. mm 3-1/2 core |
| 757 | 50 sq. mm 3-1/2 core |
| 758 | 70 sq. mm 3-1/2 core |
| 759 | 95 sq. mm 3-1/2 core |
| 760 | 150 sq. mm 3-1/2 core |
| 761 | 240 sq. mm 3-1/2 core |
| 762 | 300 sq. mm 3-1/2 core |
| 763 | 400 sq. mm 3-1/2 core |
| 764 | Supplying and making end termination with brass compressiongland and aluminium lugs for following size of PVC insulatedand PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required. |
| 765 | 6 sq. mm 2 core |
| 766 | 10 sq. mm 2 core |
| 767 | 25 sq. mm 3-1/2 core |
| 768 | 35 sq. mm 3-1/2 core |
| 769 | 50 sq. mm 3-1/2 core |
| 770 | 70 sq. mm 3-1/2 core |
| 771 | 95 sq. mm 3-1/2 core |
| 772 | 150 sq. mm 3-1/2 core |
| 773 | 240 sq. mm 3-1/2 core |
| 774 | 300 sq. mm 3-1/2 core |
| 775 | 400 sq. mm 3-1/2 core |
| 776 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. |
| 777 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 778 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 779 | 450 mm width X 62.5 mm depth X 2 mm thickness |
| 780 | 600 mm width X 62.5 mm depth X 2 mm thickness |
| 781 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 Way SPN DB |
| 782 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4WAY TPN DB |
| 783 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar formounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4WAY VTPN DB |
| 784 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6WAY TPN DB |
| 785 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8WAY VTPN DB |
| 786 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8WAY TPN DB |
| 787 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 788 | Single pole |
| 789 | Double pole |
| 790 | Triple pole |
| 791 | Triple pole and neutral |
| 792 | S&F of 40 Amp. TP MCB (10 KA) C CurveCAT-A |
| 793 | S&F of 63 Amp. TP MCB (10 KA) C CurveCAT-A |
| 794 | S&F of 6 Amp. to 40 Amp. 4 pole MCB (10 KA) C Curve CAT-A |
| 795 | S&F of 6 Amp. to 63 Amp. 4 pole MCB (10 KA) C Curve CAT-A |
| 796 | Dismantlinmg of ExistingPanel & shifting of same at appropriate location as per Direction of Engineer In-charge |
| 797 | Repairing of Floor L.T panel including painting, fixing of rating plates, repairing of door lock etc. as required. |
| 798 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 799 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 800 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 801 | EXTERNAL LIGHT FEEDER PILLAR |
| 802 | Supply installing testing & commissioning of outdoor type Distribution Panel compartmentalised design, dust tight & vermin proof made out of 14 gauge M.S. sheet, stove powder coated complete as required with following incomming & outgoing as per detail below. |
| 803 | Incoming |
| 804 | 63 Amp. 25 KA FP MCCB1 No. |
| 805 | Suitable contractor and timer for down & dusk |
| 806 | 100 Amp. TPN Alu. Bus bar |
| 807 | Outgoing |
| 808 | 25 Amp. 10KA FP MCB5 No. |
| 809 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge ,complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 810 | 6 sq. mm 4 core |
| 811 | 10 sq. mm 4 core |
| 812 | 16 sq. mm 4 core |
| 813 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 814 | 6 sq. mm 4 core |
| 815 | 4 X 10 sq. mm (25mm) |
| 816 | 4 X 16 sq. mm (28mm) |
| 817 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge . |
| 818 | 6 sq. mm |
| 819 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness backlite sheet & 4 way connectorwith single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts,xcavation & back filling and Required T&P completee in all respect. |
| 820 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness backlite sheet & 4 way connectorwith Double arm bracket (1 Mtr length) on RCCoundation including the cost of foundation, foundation bolts, xcavation & back filling and Required T&P completee in all respect. |
| 821 | Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuserwith driver set suitable1.5 Sqmm 3 core multistand copper unarmored cable suitable lenght and 1 no 10 Amp SPMCBfor 52 watt to 72 Watt. Confirming to IP65 and above Protection complete in all respect. Cat.-AAA 6600-7920 system lumens High Power LED with lenses, > 110lm/W, PF>0.95, Potted driver set (Not Circuitory) Phase to Phase Protection at 440 V & > 300V auto cut re-start feature. with 5 year warantee. as peras per direction of E/I. |
| 822 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 823 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of+B944 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 824 | Supply and laying of 25 mm X 3mm G.I. strip from earth electrode irectly in the ground as required complete in all respect. |
| 825 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |